Adds complete procedure for replacing UPS battery when entire cluster is powered by the same UPS, requiring full cluster shutdown. New files: - scripts/ups-maintenance-shutdown.sh: Automated orchestrated shutdown for maintenance operations with confirmation prompts and progress display - docs/UPS-BATTERY-REPLACEMENT.md: Complete step-by-step guide for battery replacement including pre-shutdown, physical replacement, and post-startup verification procedures Features: - Orchestrated shutdown: VMs → LXC containers → secondary nodes → primary - Interactive confirmation before shutdown - Color-coded progress indicators - Countdown timers for each phase - Post-replacement verification checklist - Troubleshooting guide for common issues - Recovery procedures for cluster/quorum problems The procedure accounts for all 3 cluster nodes (pve1, pvemini, pveelite) being on the same UPS, requiring complete infrastructure shutdown. Documentation includes: - When to replace battery (based on monthly test results) - Pre-planning and user notification templates - Physical battery replacement safety procedures - Cluster recovery and VM restart procedures - Post-replacement testing and verification - 24-hour and 1-week monitoring checklists Estimated maintenance window: 30-60 minutes 🤖 Generated with [Claude Code](https://claude.com/claude-code) Co-Authored-By: Claude <noreply@anthropic.com>
424 lines
12 KiB
Markdown
424 lines
12 KiB
Markdown
# Documentație UPS - Cluster Proxmox
|
|
|
|
## Despre
|
|
|
|
Această documentație descrie configurarea completă a sistemului UPS (Uninterruptible Power Supply) pentru cluster-ul Proxmox, incluzând monitorizare automată și shutdown orchestrat.
|
|
|
|
## Structură Directoare
|
|
|
|
```
|
|
proxmox/ups/
|
|
├── README.md # Acest fișier
|
|
├── config/ # Fișiere de configurare NUT
|
|
│ ├── ups.conf # Configurare driver UPS
|
|
│ ├── upsd.conf # Configurare server NUT
|
|
│ ├── upsd.users # Utilizatori și permisiuni
|
|
│ ├── upsmon.conf # Configurare monitor local
|
|
│ └── upssched.conf # Scheduler evenimente UPS
|
|
├── scripts/ # Scripturi de shutdown și testare
|
|
│ ├── ups-shutdown-cluster.sh # Script principal shutdown orchestrat
|
|
│ ├── ups-shutdown-test.sh # Script test (dry-run)
|
|
│ ├── upssched-cmd # Handler evenimente upssched
|
|
│ ├── ups-monthly-test.sh # Test lunar automat baterie
|
|
│ └── ups-maintenance-shutdown.sh # Shutdown pentru mentenanță UPS (NOU!)
|
|
└── docs/ # Documentație
|
|
├── INSTALARE-NUT.md # Ghid instalare NUT pe Proxmox
|
|
├── INSTALARE-WINNUT.md # Ghid instalare WinNUT pe Windows
|
|
├── UPS-SHUTDOWN-README.md # Documentație completă sistem
|
|
├── UPS-MONTHLY-TEST.md # Documentație test lunar baterie
|
|
└── UPS-BATTERY-REPLACEMENT.md # Procedură înlocuire baterie (NOU!)
|
|
```
|
|
|
|
🎯 Utilizare:
|
|
Pentru instalare nouă:
|
|
Citește README.md
|
|
Urmează docs/INSTALARE-NUT.md
|
|
Copiază fișiere din config/ și scripts/ pe server
|
|
Pentru backup:
|
|
Tot ce trebuie este salvat în proxmox/ups/
|
|
Versionat în Git
|
|
Pentru recovery:
|
|
Restaurează fișiere din config/ în /etc/nut/
|
|
Restaurează fișiere din scripts/ în /usr/local/bin/
|
|
Restart servicii
|
|
|
|
## Arhitectură Sistem
|
|
|
|
### Hardware
|
|
- **UPS:** INNO TECH USB to Serial (Vendor ID: 0665, Product ID: 5161)
|
|
- **Conectat la:** pvemini (10.0.20.201) via USB
|
|
- **Tip:** Voltronic/Megatec protocol (driver: nutdrv_qx)
|
|
|
|
### Cluster Proxmox
|
|
- **pvemini (10.0.20.201)** - Nod PRIMARY
|
|
- Are UPS-ul conectat fizic
|
|
- Rulează NUT server și driver
|
|
- Ultimul nod care se oprește
|
|
- **pve1 (10.0.20.200)** - Nod SECONDARY
|
|
- Se oprește primul în caz de baterie critică
|
|
- **pve2 (10.0.20.202)** - Nod SECONDARY
|
|
- Se oprește primul în caz de baterie critică
|
|
|
|
### Monitorizare
|
|
- **VM 201 (Windows 11)** - Monitorizare vizuală via WinNUT
|
|
- Afișează status UPS în timp real
|
|
- NU controlează shutdown-ul
|
|
|
|
## Flux Automat Shutdown
|
|
|
|
### Scenario 1: Întrerupere scurtă (< 3 minute)
|
|
1. Curent se întrerupe → UPS trece pe baterie (status: OB)
|
|
2. upssched pornește timer de 180 secunde
|
|
3. Curent revine înainte de 3 minute
|
|
4. Timer anulat → **Niciun sistem nu se oprește**
|
|
|
|
### Scenario 2: Întrerupere lungă (> 3 minute)
|
|
1. Curent se întrerupe → UPS pe baterie
|
|
2. Timer 180 secunde expiră
|
|
3. `/usr/local/bin/ups-shutdown-cluster.sh` pornește:
|
|
- **Step 1:** Oprește toate VM-urile de pe toate nodurile (paralel)
|
|
- **Step 2:** Așteaptă 90 secunde pentru oprire graceful
|
|
- **Step 3:** Shutdown pve1 și pve2 (noduri secundare)
|
|
- **Step 4:** Așteaptă 30 secunde
|
|
- **Step 5:** Shutdown pvemini (nod primary - ultimul)
|
|
|
|
### Scenario 3: Baterie scăzută imediată
|
|
1. UPS raportează LOWBATT (baterie critică)
|
|
2. Shutdown **IMEDIAT** (fără timer)
|
|
3. Același flux de shutdown orchestrat ca mai sus
|
|
|
|
## Quick Start
|
|
|
|
### Pentru Administrator Nou
|
|
|
|
1. **Citește documentația:**
|
|
- Start: [`docs/UPS-SHUTDOWN-README.md`](docs/UPS-SHUTDOWN-README.md)
|
|
- Detalii NUT: [`docs/INSTALARE-NUT.md`](docs/INSTALARE-NUT.md)
|
|
- WinNUT: [`docs/INSTALARE-WINNUT.md`](docs/INSTALARE-WINNUT.md)
|
|
|
|
2. **Verifică status UPS:**
|
|
```bash
|
|
ssh root@10.0.20.201
|
|
upsc nutdev1
|
|
```
|
|
|
|
3. **Test dry-run:**
|
|
```bash
|
|
ssh root@10.0.20.201
|
|
/usr/local/bin/ups-shutdown-test.sh
|
|
cat /var/log/ups-shutdown-test.log
|
|
```
|
|
|
|
4. **Monitorizează în WinNUT:**
|
|
- Pornește WinNUT pe VM 201
|
|
- Verifică că se conectează la 10.0.20.201:3493
|
|
|
|
### Verificare Săptămânală
|
|
|
|
```bash
|
|
# Conectează-te la pvemini
|
|
ssh root@10.0.20.201
|
|
|
|
# Status UPS
|
|
upsc nutdev1 ups.status battery.charge input.voltage
|
|
|
|
# Status servicii
|
|
systemctl status nut-server nut-monitor
|
|
|
|
# Logs evenimente recente
|
|
tail -20 /var/log/ups-events.log
|
|
|
|
# Test dry-run
|
|
/usr/local/bin/ups-shutdown-test.sh
|
|
```
|
|
|
|
### Verificare Lunară
|
|
|
|
**🔋 Test Automat Baterie (1 ale lunii la 00:00):**
|
|
|
|
Scriptul `/opt/scripts/ups-monthly-test.sh` rulează automat lunar și:
|
|
- Testează capacitatea reală a bateriei
|
|
- Monitorizează scăderea charge și voltage
|
|
- Evaluează sănătatea bateriei (EXCELLENT/GOOD/FAIR/POOR)
|
|
- Trimite raport HTML prin email via PVE::Notify
|
|
|
|
**Verificare rezultat test:**
|
|
```bash
|
|
ssh root@10.0.20.201
|
|
# Vezi ultimul test
|
|
tail -50 /var/log/ups-monthly-test.log
|
|
|
|
# Rulare manuală (pentru testare)
|
|
/opt/scripts/ups-monthly-test.sh
|
|
```
|
|
|
|
**Documentație completă:** [`docs/UPS-MONTHLY-TEST.md`](docs/UPS-MONTHLY-TEST.md)
|
|
|
|
---
|
|
|
|
**Test fizic manual (opțional):**
|
|
- Deconectează UPS de la priză timp de 30 secunde
|
|
- Verifică că WinNUT detectează schimbarea (On Battery)
|
|
- Verifică logs: `tail -f /var/log/ups-events.log`
|
|
- Reconectează **înainte de 3 minute** pentru a evita shutdown
|
|
|
|
**Verificare SSH între noduri:**
|
|
```bash
|
|
ssh root@10.0.20.201
|
|
ssh root@10.0.20.200 "hostname"
|
|
ssh root@10.0.20.202 "hostname"
|
|
```
|
|
|
|
## Instalare de la Zero
|
|
|
|
### 1. Instalare NUT pe pvemini
|
|
|
|
```bash
|
|
# Instalare pachete
|
|
apt update
|
|
apt install -y nut nut-client nut-server
|
|
|
|
# Copiere fișiere de configurare
|
|
cd /path/to/ROMFASTSQL/proxmox/ups
|
|
scp config/* root@10.0.20.201:/etc/nut/
|
|
|
|
# Copiere scripturi shutdown
|
|
scp scripts/ups-shutdown-cluster.sh scripts/ups-shutdown-test.sh scripts/upssched-cmd root@10.0.20.201:/usr/local/bin/
|
|
ssh root@10.0.20.201 "chmod +x /usr/local/bin/ups-*.sh /usr/local/bin/upssched-cmd"
|
|
|
|
# Copiere script test lunar
|
|
scp scripts/ups-monthly-test.sh root@10.0.20.201:/opt/scripts/
|
|
ssh root@10.0.20.201 "chmod +x /opt/scripts/ups-monthly-test.sh"
|
|
|
|
# Configurare cron pentru test lunar
|
|
ssh root@10.0.20.201 "(crontab -l 2>/dev/null | grep -v ups-monthly-test; echo '# UPS Monthly Battery Test'; echo '0 0 1 * * /opt/scripts/ups-monthly-test.sh') | crontab -"
|
|
|
|
# Configurare permisiuni
|
|
ssh root@10.0.20.201 "chown nut:nut /etc/nut/ups*.conf /etc/nut/upsd.*"
|
|
ssh root@10.0.20.201 "chmod 640 /etc/nut/upsd.users"
|
|
|
|
# Pornire servicii
|
|
ssh root@10.0.20.201 "systemctl enable nut-server nut-monitor"
|
|
ssh root@10.0.20.201 "systemctl start nut-server nut-monitor"
|
|
|
|
# Verificare
|
|
ssh root@10.0.20.201 "upsc nutdev1"
|
|
```
|
|
|
|
### 2. Instalare WinNUT pe VM 201
|
|
|
|
Vezi ghid detaliat: [`docs/INSTALARE-WINNUT.md`](docs/INSTALARE-WINNUT.md)
|
|
|
|
```
|
|
Server: 10.0.20.201
|
|
Port: 3493
|
|
UPS: nutdev1
|
|
User: admin
|
|
Pass: parola99
|
|
Polling: 15
|
|
```
|
|
|
|
## Troubleshooting Rapid
|
|
|
|
### UPS nu răspunde
|
|
|
|
```bash
|
|
ssh root@10.0.20.201
|
|
|
|
# Verifică UPS conectat
|
|
lsusb | grep 0665
|
|
|
|
# Restart driver
|
|
upsdrvctl stop && upsdrvctl start
|
|
|
|
# Verifică status
|
|
upsc nutdev1
|
|
```
|
|
|
|
### WinNUT nu se conectează
|
|
|
|
1. **Verifică Polling Interval ≠ 0** (pune 15)
|
|
2. **Test port:**
|
|
```powershell
|
|
Test-NetConnection -ComputerName 10.0.20.201 -Port 3493
|
|
```
|
|
3. **Verifică server:**
|
|
```bash
|
|
ssh root@10.0.20.201 "ss -tulpn | grep 3493"
|
|
```
|
|
|
|
### Scriptul de shutdown nu funcționează
|
|
|
|
```bash
|
|
# Test SSH între noduri
|
|
ssh root@10.0.20.201 "ssh root@10.0.20.200 hostname"
|
|
|
|
# Dacă eșuează, reconfigurează SSH keys
|
|
ssh root@10.0.20.201
|
|
ssh-keygen -f /root/.ssh/known_hosts -R 10.0.20.200
|
|
ssh-keyscan -H 10.0.20.200 >> /root/.ssh/known_hosts
|
|
```
|
|
|
|
## Logs Important
|
|
|
|
| Fișier | Scop |
|
|
|--------|------|
|
|
| `/var/log/ups-shutdown.log` | Shutdown orchestrat real |
|
|
| `/var/log/ups-shutdown-test.log` | Test dry-run |
|
|
| `/var/log/ups-events.log` | Evenimente UPS (upssched) |
|
|
| `/var/log/ups-monthly-test.log` | **Test lunar baterie (NOU!)** |
|
|
| `journalctl -u nut-server` | Server NUT |
|
|
| `journalctl -u nut-monitor` | Monitor NUT |
|
|
|
|
## Comenzi Utile
|
|
|
|
```bash
|
|
# Status UPS complet
|
|
upsc nutdev1
|
|
|
|
# Doar câmpuri importante
|
|
upsc nutdev1 ups.status battery.charge input.voltage output.voltage
|
|
|
|
# Comenzi disponibile
|
|
upscmd -l nutdev1
|
|
|
|
# Conexiuni active NUT
|
|
ss -tnp | grep 3493
|
|
|
|
# Monitoring live
|
|
watch -n 2 'upsc nutdev1 ups.status battery.charge input.voltage'
|
|
|
|
# Test shutdown (DRY RUN - nu oprește nimic)
|
|
/usr/local/bin/ups-shutdown-test.sh
|
|
|
|
# Test lunar baterie (cu raport email)
|
|
/opt/scripts/ups-monthly-test.sh
|
|
|
|
# Verifică ultimul test lunar
|
|
tail -50 /var/log/ups-monthly-test.log
|
|
```
|
|
|
|
## Configurare Personalizată
|
|
|
|
### Modificare timp de așteptare (default: 3 minute)
|
|
|
|
Editează `/etc/nut/upssched.conf` pe pvemini:
|
|
|
|
```bash
|
|
# Schimbă din 180 (3 min) la 300 (5 min)
|
|
AT ONBATT * START-TIMER onbatt 300
|
|
```
|
|
|
|
Apoi:
|
|
```bash
|
|
systemctl restart nut-monitor
|
|
```
|
|
|
|
### Adăugare noduri noi în cluster
|
|
|
|
Editează `/usr/local/bin/ups-shutdown-cluster.sh`:
|
|
|
|
```bash
|
|
# Adaugă IP-ul noului nod
|
|
NODES=("10.0.20.200" "10.0.20.202" "10.0.20.XXX")
|
|
```
|
|
|
|
## Backup și Restore
|
|
|
|
### Backup configurație
|
|
|
|
```bash
|
|
# De pe stația locală
|
|
cd /path/to/ROMFASTSQL/proxmox/ups
|
|
|
|
# Backup configurație
|
|
ssh root@10.0.20.201 "tar czf /tmp/nut-backup.tar.gz /etc/nut/*.conf /usr/local/bin/ups*.sh /usr/local/bin/upssched-cmd"
|
|
scp root@10.0.20.201:/tmp/nut-backup.tar.gz ./nut-backup-$(date +%Y%m%d).tar.gz
|
|
```
|
|
|
|
### Restore configurație
|
|
|
|
```bash
|
|
# Extrage backup
|
|
tar xzf nut-backup-YYYYMMDD.tar.gz
|
|
|
|
# Copiază pe server
|
|
scp -r etc/nut/* root@10.0.20.201:/etc/nut/
|
|
scp usr/local/bin/* root@10.0.20.201:/usr/local/bin/
|
|
|
|
# Restart servicii
|
|
ssh root@10.0.20.201 "systemctl restart nut-server nut-monitor"
|
|
```
|
|
|
|
## Securitate
|
|
|
|
### Parole
|
|
|
|
**IMPORTANT:** Schimbă parolele default!
|
|
|
|
```bash
|
|
ssh root@10.0.20.201
|
|
nano /etc/nut/upsd.users
|
|
|
|
# Schimbă "parola99" cu ceva sigur
|
|
# Apoi restart:
|
|
systemctl restart nut-server
|
|
```
|
|
|
|
### Firewall
|
|
|
|
NUT portul 3493 trebuie accesibil din rețea locală. Dacă ai firewall:
|
|
|
|
```bash
|
|
# Permite port 3493 din subnet local
|
|
iptables -A INPUT -p tcp --dport 3493 -s 10.0.20.0/24 -j ACCEPT
|
|
```
|
|
|
|
## Suport și Documentație
|
|
|
|
- **NUT Official:** https://networkupstools.org/
|
|
- **NUT Documentation:** https://networkupstools.org/docs/user-manual.chunked/
|
|
- **Hardware Compatibility:** https://networkupstools.org/stable-hcl.html
|
|
- **WinNUT GitHub:** https://github.com/gawindx/WinNUT-V2
|
|
|
|
## Funcționalități Complete
|
|
|
|
### ✅ Shutdown Orchestrat Automat
|
|
- Detectare întrerupere curent (3 minute grace period)
|
|
- Oprire ordonată: VM-uri → noduri secundare → nod primary
|
|
- Notificări în timp real prin upssched
|
|
|
|
### ✅ Test Lunar Automat Baterie (NOU!)
|
|
- Rulare automată pe 1 ale lunii la 00:00
|
|
- Test real capacitate baterie (comutare pe baterie ~10 secunde)
|
|
- Evaluare sănătate: EXCELLENT/GOOD/FAIR/POOR
|
|
- Rapoarte HTML + email prin PVE::Notify
|
|
- Recomandări automate pentru înlocuire baterie
|
|
- Log detaliat istoric teste
|
|
|
|
### ✅ Monitorizare Continuă
|
|
- WinNUT pe VM 201 (Windows 11) pentru vizualizare real-time
|
|
- NUT server pe pvemini expune date la toate nodurile
|
|
- Logging complet evenimente și teste
|
|
|
|
### ✅ Mentenanță Baterie (NOU!)
|
|
- Script automat shutdown orchestrat pentru înlocuire baterie
|
|
- Procedură pas-cu-pas completă cu checklist-uri
|
|
- Recovery procedures pentru probleme comune
|
|
- Documentație: [`docs/UPS-BATTERY-REPLACEMENT.md`](docs/UPS-BATTERY-REPLACEMENT.md)
|
|
|
|
## Autori și Istoric
|
|
|
|
- **Creat:** 2025-10-06
|
|
- **Versiune:** 1.1
|
|
- **Ultima modificare:** 2025-10-06
|
|
- **Autor:** Configurat automat via Claude Code
|
|
- **Changelog:**
|
|
- v1.1 (2025-10-06): Adăugat test lunar automat baterie cu notificări PVE::Notify
|
|
- v1.0 (2025-10-06): Release inițial cu shutdown orchestrat și monitorizare NUT
|
|
|
|
## Licență
|
|
|
|
Documentația și scripturile sunt furnizate "as-is" fără garanție.
|
|
NUT și WinNUT sunt software open-source cu licențele lor respective.
|