This commit adds a comprehensive UPS monitoring and management system for the Proxmox cluster with automated shutdown orchestration and monthly battery health testing. Features: - NUT (Network UPS Tools) configuration for INNO TECH USB UPS - Automated cluster shutdown on power failure (3-minute grace period) - Monthly automated battery testing with health evaluation - Email notifications via PVE::Notify system - WinNUT monitoring client for Windows VM 201 Components added: - config/: NUT configuration files (ups.conf, upsd.conf, upsmon.conf, etc.) - scripts/ups-shutdown-cluster.sh: Orchestrated cluster shutdown - scripts/ups-monthly-test.sh: Monthly battery test with email reports - scripts/upssched-cmd: Event handler for UPS state changes - docs/: Complete installation and usage documentation Key findings: - UPS battery.charge reporting has 10-40 second delay after test start - Test must monitor voltage drop (1.5-2V) and charge drop (9-27%) - Battery health evaluation: EXCELLENT/GOOD/FAIR/POOR based on discharge rate - Email notifications use Handlebars templates without Unicode emojis for compatibility Configuration: - UPS: INNO TECH (Voltronic protocol, vendor 0665:5161) - Primary node: pvemini (10.0.20.201) with USB connection - Monthly test: cron 0 0 1 * * /opt/scripts/ups-monthly-test.sh - Shutdown timer: 180 seconds on battery before cluster shutdown Documentation includes complete installation guides for NUT server, WinNUT client, and troubleshooting procedures. 🤖 Generated with [Claude Code](https://claude.com/claude-code) Co-Authored-By: Claude <noreply@anthropic.com>
5.7 KiB
Documentație Sistem UPS Shutdown Orchestrat
Configurare Completă
Hardware
- UPS: INNO TECH USB to Serial (ID: 0665:5161)
- Conectat la: pvemini (10.0.20.201) - via USB
- Cluster Proxmox:
- pvemini (10.0.20.201) - PRIMARY (are UPS-ul conectat)
- pve1 (10.0.20.200) - SECONDARY
- pve2 (10.0.20.202) - SECONDARY
Software
- NUT (Network UPS Tools) versiunea 2.8.0
- WinNUT pe VM 201 (Windows 11) pentru monitorizare vizuală
Fișiere de Configurare
1. /etc/nut/ups.conf
Configurează driver-ul pentru UPS:
[nutdev1]
driver = nutdrv_qx
port = auto
vendorid = 0665
productid = 5161
subdriver = cypress
desc = "UPS Cypress via USB"
2. /etc/nut/upsd.conf
Server NUT - ascultă pe localhost și rețea:
LISTEN 127.0.0.1 3493
LISTEN 10.0.20.201 3493
3. /etc/nut/upsd.users
Utilizatori autorizați:
[admin]
password = parola99
actions = SET
instcmds = ALL
upsmon master
4. /etc/nut/upsmon.conf
Monitor local:
MONITOR nutdev1@localhost 1 admin parola99 master
NOTIFYCMD /usr/sbin/upssched
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
5. /etc/nut/upssched.conf
Scheduler pentru evenimente:
- ONBATT: Așteaptă 180 secunde (3 minute) înainte de shutdown
- LOWBATT: Shutdown imediat
- ONLINE: Anulează toate timer-ele
Scripturi Create
1. /usr/local/bin/ups-shutdown-cluster.sh
Script principal de shutdown orchestrat
Ordinea de operații:
- Verifică status UPS (trebuie OB sau LB)
- Oprește toate VM-urile de pe toate nodurile (paralel)
- Așteaptă 90 secunde
- Shutdown pve1 și pve2 (secundare)
- Așteaptă 30 secunde
- Shutdown pvemini (primary - ultimul)
Logare: /var/log/ups-shutdown.log
2. /usr/local/bin/ups-shutdown-test.sh
Script de test (DRY RUN) - NU oprește nimic
Folosește-l pentru a testa:
/usr/local/bin/ups-shutdown-test.sh
tail -f /var/log/ups-shutdown-test.log
3. /usr/local/bin/upssched-cmd
Handler pentru evenimente UPS
Apelat automat de upssched când:
- UPS pe baterie 3 minute → lansează shutdown orchestrat
- Baterie scăzută → shutdown imediat
- Pierdere comunicație → doar logging
Logare: /var/log/ups-events.log
Testare și Verificare
Verificare Status UPS
# Status general
upsc nutdev1
# Doar status
upsc nutdev1 ups.status
# Baterie
upsc nutdev1 battery.charge
# Tensiuni
upsc nutdev1 input.voltage output.voltage
Verificare Servicii
systemctl status nut-server
systemctl status nut-monitor
journalctl -u nut-server -f
journalctl -u nut-monitor -f
Test Manual Shutdown (DRY RUN)
/usr/local/bin/ups-shutdown-test.sh
Test Simulare UPS pe Baterie
⚠️ ATENȚIE: Acest test va iniția shutdown real dacă îl lași 3 minute!
# Deconectează fizic UPS-ul de la priză pentru 30 secunde
# Monitorizează logs:
tail -f /var/log/ups-events.log
# Reconectează înainte de 3 minute pentru a anula shutdown-ul
Monitorizare din WinNUT (VM 201)
Conexiune
- Server: 10.0.20.201
- Port: 3493
- UPS Name: nutdev1
- Username: admin
- Password: parola99
- Polling Interval: 15 secunde
Ce Vezi în WinNUT
- Input/Output Voltage
- Frequency
- Battery Charge (%)
- Battery Voltage
- UPS Load (%)
- UPS Status (Online/On Battery/Low Battery)
Scenarii de Funcționare
Scenario 1: Întrerupere Scurtă (< 3 minute)
- Curent se întrerupe → UPS trece pe baterie
- Timer de 180 secunde pornește
- Curent revine → Timer anulat
- Rezultat: Niciun sistem nu se oprește
Scenario 2: Întrerupere Lungă (> 3 minute)
- Curent se întrerupe → UPS trece pe baterie
- Timer 180 secunde expiră
- Scriptu de shutdown pornește:
- VM-uri se opresc pe toate nodurile
- După 90s: pve1, pve2 se opresc
- După încă 30s: pvemini se oprește
- Rezultat: Shutdown orchestrat complet
Scenario 3: Baterie Scăzută Imediată
- UPS raportează LOWBATT
- Shutdown IMEDIAT (fără timer)
- Același flux de shutdown orchestrat
- Rezultat: Shutdown rapid pentru protecție
Loguri și Troubleshooting
Fișiere de Log
/var/log/ups-shutdown.log # Shutdown orchestrat real
/var/log/ups-shutdown-test.log # Test dry-run
/var/log/ups-events.log # Evenimente UPS (upssched)
journalctl -u nut-server # Server NUT
journalctl -u nut-monitor # Monitor NUT
Comenzi Utile
# Liste conexiuni active la NUT
ss -tnp | grep :3493
# Test conectivitate de pe alt nod
ssh root@10.0.20.200 'upsc nutdev1@10.0.20.201'
# Restart servicii
systemctl restart nut-server nut-monitor
Întreținere
Verificare Săptămânală
# Status UPS
upsc nutdev1 ups.status battery.charge
# Test dry-run
/usr/local/bin/ups-shutdown-test.sh
# Verificare logs
tail -20 /var/log/ups-events.log
Verificare Lunară
- Test fizic: deconectează UPS 30 secunde
- Verifică că WinNUT detectează schimbarea
- Verifică că logs arată evenimentul
- Reconectează înainte de 3 minute
⚠️ IMPORTANT
-
Nu modifica timpul de 3 minute fără consultare - trebuie să fie suficient pentru:
- VM-uri să se oprească graceful
- Noduri secundare să se închidă
- pvemini să rămână ultimul funcțional
-
Testează periodic scriptul dry-run pentru a verifica că SSH funcționează între noduri
-
Monitorizează statusul bateriei UPS - înlocuiește bateria când charge devine sub 80%
-
WinNUT este doar pentru monitorizare - shutdown-ul este automat de pe Proxmox