This commit adds a comprehensive UPS monitoring and management system for the Proxmox cluster with automated shutdown orchestration and monthly battery health testing. Features: - NUT (Network UPS Tools) configuration for INNO TECH USB UPS - Automated cluster shutdown on power failure (3-minute grace period) - Monthly automated battery testing with health evaluation - Email notifications via PVE::Notify system - WinNUT monitoring client for Windows VM 201 Components added: - config/: NUT configuration files (ups.conf, upsd.conf, upsmon.conf, etc.) - scripts/ups-shutdown-cluster.sh: Orchestrated cluster shutdown - scripts/ups-monthly-test.sh: Monthly battery test with email reports - scripts/upssched-cmd: Event handler for UPS state changes - docs/: Complete installation and usage documentation Key findings: - UPS battery.charge reporting has 10-40 second delay after test start - Test must monitor voltage drop (1.5-2V) and charge drop (9-27%) - Battery health evaluation: EXCELLENT/GOOD/FAIR/POOR based on discharge rate - Email notifications use Handlebars templates without Unicode emojis for compatibility Configuration: - UPS: INNO TECH (Voltronic protocol, vendor 0665:5161) - Primary node: pvemini (10.0.20.201) with USB connection - Monthly test: cron 0 0 1 * * /opt/scripts/ups-monthly-test.sh - Shutdown timer: 180 seconds on battery before cluster shutdown Documentation includes complete installation guides for NUT server, WinNUT client, and troubleshooting procedures. 🤖 Generated with [Claude Code](https://claude.com/claude-code) Co-Authored-By: Claude <noreply@anthropic.com>
24 lines
809 B
Plaintext
24 lines
809 B
Plaintext
# Configurare upssched pentru shutdown orchestrat cluster Proxmox
|
|
#
|
|
# Acest fișier definește acțiuni temporale pentru evenimente UPS
|
|
|
|
CMDSCRIPT /usr/local/bin/upssched-cmd
|
|
PIPEFN /run/nut/upssched.pipe
|
|
LOCKFN /run/nut/upssched.lock
|
|
|
|
# Când UPS trece pe baterie (ONBATT), așteaptă 180 secunde (3 minute)
|
|
# Dacă curentul revine în acest timp, anulează shutdown-ul
|
|
AT ONBATT * START-TIMER onbatt 180
|
|
|
|
# Când UPS raportează baterie scăzută (LOWBATT), shutdown imediat
|
|
AT LOWBATT * EXECUTE lowbatt
|
|
|
|
# Când curentul revine (ONLINE), anulează toate timer-ele
|
|
AT ONLINE * CANCEL-TIMER onbatt
|
|
|
|
# Când comunicația cu UPS se pierde (COMMBAD), așteaptă 30 secunde
|
|
AT COMMBAD * START-TIMER commbad 30
|
|
|
|
# Când comunicația este restabilită (COMMOK), anulează timer-ul
|
|
AT COMMOK * CANCEL-TIMER commbad
|