Author SHA1 Message Date
Marius
1011d9202c Fix UPS notifications and add periodic battery status emails
- Fix permission denied on log files (chown nut:nut)
- Fix upssched.conf permissions (root:nut)
- Add sudo for perl to allow PVE::Notify from user nut
- Add periodic battery status emails every minute when on battery
- Add charging status emails at 5, 10, 30 min after power restore
- Remove diacritics from all notification messages
- Update documentation with sudo and permissions setup

Co-Authored-By: Claude Opus 4.5 <noreply@anthropic.com>
2026-01-14 13:06:25 +02:00
Marius
ab6ac77d50 Add UPS email notifications and automatic UPS shutdown
- Add email notifications via PVE::Notify for all UPS events:
  - ONBATT: when UPS switches to battery
  - ONLINE: when power is restored
  - LOWBATT: critical battery level
  - SHUTDOWN_START/NODE/PRIMARY: during cluster shutdown
  - COMMBAD: communication lost with UPS

- Add automatic UPS shutdown command after cluster shutdown
  (protects against power surge when power returns)

- Update upssched.conf with ONLINE handler and immediate ONBATT notification

- Add notification templates for HTML and text emails

- Update documentation with new features and timer configuration

Co-Authored-By: Claude Opus 4.5 <noreply@anthropic.com>
2026-01-13 20:11:30 +02:00
Marius
87b9709a0d Add complete UPS monitoring system with monthly battery testing
This commit adds a comprehensive UPS monitoring and management system for
the Proxmox cluster with automated shutdown orchestration and monthly
battery health testing.

Features:
- NUT (Network UPS Tools) configuration for INNO TECH USB UPS
- Automated cluster shutdown on power failure (3-minute grace period)
- Monthly automated battery testing with health evaluation
- Email notifications via PVE::Notify system
- WinNUT monitoring client for Windows VM 201

Components added:
- config/: NUT configuration files (ups.conf, upsd.conf, upsmon.conf, etc.)
- scripts/ups-shutdown-cluster.sh: Orchestrated cluster shutdown
- scripts/ups-monthly-test.sh: Monthly battery test with email reports
- scripts/upssched-cmd: Event handler for UPS state changes
- docs/: Complete installation and usage documentation

Key findings:
- UPS battery.charge reporting has 10-40 second delay after test start
- Test must monitor voltage drop (1.5-2V) and charge drop (9-27%)
- Battery health evaluation: EXCELLENT/GOOD/FAIR/POOR based on discharge rate
- Email notifications use Handlebars templates without Unicode emojis for compatibility

Configuration:
- UPS: INNO TECH (Voltronic protocol, vendor 0665:5161)
- Primary node: pvemini (10.0.20.201) with USB connection
- Monthly test: cron 0 0 1 * * /opt/scripts/ups-monthly-test.sh
- Shutdown timer: 180 seconds on battery before cluster shutdown

Documentation includes complete installation guides for NUT server,
WinNUT client, and troubleshooting procedures.

🤖 Generated with [Claude Code](https://claude.com/claude-code)

Co-Authored-By: Claude <noreply@anthropic.com>
2025-10-06 21:39:46 +03:00