Add complete UPS monitoring system with monthly battery testing
This commit adds a comprehensive UPS monitoring and management system for the Proxmox cluster with automated shutdown orchestration and monthly battery health testing. Features: - NUT (Network UPS Tools) configuration for INNO TECH USB UPS - Automated cluster shutdown on power failure (3-minute grace period) - Monthly automated battery testing with health evaluation - Email notifications via PVE::Notify system - WinNUT monitoring client for Windows VM 201 Components added: - config/: NUT configuration files (ups.conf, upsd.conf, upsmon.conf, etc.) - scripts/ups-shutdown-cluster.sh: Orchestrated cluster shutdown - scripts/ups-monthly-test.sh: Monthly battery test with email reports - scripts/upssched-cmd: Event handler for UPS state changes - docs/: Complete installation and usage documentation Key findings: - UPS battery.charge reporting has 10-40 second delay after test start - Test must monitor voltage drop (1.5-2V) and charge drop (9-27%) - Battery health evaluation: EXCELLENT/GOOD/FAIR/POOR based on discharge rate - Email notifications use Handlebars templates without Unicode emojis for compatibility Configuration: - UPS: INNO TECH (Voltronic protocol, vendor 0665:5161) - Primary node: pvemini (10.0.20.201) with USB connection - Monthly test: cron 0 0 1 * * /opt/scripts/ups-monthly-test.sh - Shutdown timer: 180 seconds on battery before cluster shutdown Documentation includes complete installation guides for NUT server, WinNUT client, and troubleshooting procedures. 🤖 Generated with [Claude Code](https://claude.com/claude-code) Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
415
proxmox/ups/README.md
Normal file
415
proxmox/ups/README.md
Normal file
@@ -0,0 +1,415 @@
|
|||||||
|
# Documentație UPS - Cluster Proxmox
|
||||||
|
|
||||||
|
## Despre
|
||||||
|
|
||||||
|
Această documentație descrie configurarea completă a sistemului UPS (Uninterruptible Power Supply) pentru cluster-ul Proxmox, incluzând monitorizare automată și shutdown orchestrat.
|
||||||
|
|
||||||
|
## Structură Directoare
|
||||||
|
|
||||||
|
```
|
||||||
|
proxmox/ups/
|
||||||
|
├── README.md # Acest fișier
|
||||||
|
├── config/ # Fișiere de configurare NUT
|
||||||
|
│ ├── ups.conf # Configurare driver UPS
|
||||||
|
│ ├── upsd.conf # Configurare server NUT
|
||||||
|
│ ├── upsd.users # Utilizatori și permisiuni
|
||||||
|
│ ├── upsmon.conf # Configurare monitor local
|
||||||
|
│ └── upssched.conf # Scheduler evenimente UPS
|
||||||
|
├── scripts/ # Scripturi de shutdown și testare
|
||||||
|
│ ├── ups-shutdown-cluster.sh # Script principal shutdown orchestrat
|
||||||
|
│ ├── ups-shutdown-test.sh # Script test (dry-run)
|
||||||
|
│ ├── upssched-cmd # Handler evenimente upssched
|
||||||
|
│ └── ups-monthly-test.sh # Test lunar automat baterie (NOU!)
|
||||||
|
└── docs/ # Documentație
|
||||||
|
├── INSTALARE-NUT.md # Ghid instalare NUT pe Proxmox
|
||||||
|
├── INSTALARE-WINNUT.md # Ghid instalare WinNUT pe Windows
|
||||||
|
├── UPS-SHUTDOWN-README.md # Documentație completă sistem
|
||||||
|
└── UPS-MONTHLY-TEST.md # Documentație test lunar baterie (NOU!)
|
||||||
|
```
|
||||||
|
|
||||||
|
🎯 Utilizare:
|
||||||
|
Pentru instalare nouă:
|
||||||
|
Citește README.md
|
||||||
|
Urmează docs/INSTALARE-NUT.md
|
||||||
|
Copiază fișiere din config/ și scripts/ pe server
|
||||||
|
Pentru backup:
|
||||||
|
Tot ce trebuie este salvat în proxmox/ups/
|
||||||
|
Versionat în Git
|
||||||
|
Pentru recovery:
|
||||||
|
Restaurează fișiere din config/ în /etc/nut/
|
||||||
|
Restaurează fișiere din scripts/ în /usr/local/bin/
|
||||||
|
Restart servicii
|
||||||
|
|
||||||
|
## Arhitectură Sistem
|
||||||
|
|
||||||
|
### Hardware
|
||||||
|
- **UPS:** INNO TECH USB to Serial (Vendor ID: 0665, Product ID: 5161)
|
||||||
|
- **Conectat la:** pvemini (10.0.20.201) via USB
|
||||||
|
- **Tip:** Voltronic/Megatec protocol (driver: nutdrv_qx)
|
||||||
|
|
||||||
|
### Cluster Proxmox
|
||||||
|
- **pvemini (10.0.20.201)** - Nod PRIMARY
|
||||||
|
- Are UPS-ul conectat fizic
|
||||||
|
- Rulează NUT server și driver
|
||||||
|
- Ultimul nod care se oprește
|
||||||
|
- **pve1 (10.0.20.200)** - Nod SECONDARY
|
||||||
|
- Se oprește primul în caz de baterie critică
|
||||||
|
- **pve2 (10.0.20.202)** - Nod SECONDARY
|
||||||
|
- Se oprește primul în caz de baterie critică
|
||||||
|
|
||||||
|
### Monitorizare
|
||||||
|
- **VM 201 (Windows 11)** - Monitorizare vizuală via WinNUT
|
||||||
|
- Afișează status UPS în timp real
|
||||||
|
- NU controlează shutdown-ul
|
||||||
|
|
||||||
|
## Flux Automat Shutdown
|
||||||
|
|
||||||
|
### Scenario 1: Întrerupere scurtă (< 3 minute)
|
||||||
|
1. Curent se întrerupe → UPS trece pe baterie (status: OB)
|
||||||
|
2. upssched pornește timer de 180 secunde
|
||||||
|
3. Curent revine înainte de 3 minute
|
||||||
|
4. Timer anulat → **Niciun sistem nu se oprește**
|
||||||
|
|
||||||
|
### Scenario 2: Întrerupere lungă (> 3 minute)
|
||||||
|
1. Curent se întrerupe → UPS pe baterie
|
||||||
|
2. Timer 180 secunde expiră
|
||||||
|
3. `/usr/local/bin/ups-shutdown-cluster.sh` pornește:
|
||||||
|
- **Step 1:** Oprește toate VM-urile de pe toate nodurile (paralel)
|
||||||
|
- **Step 2:** Așteaptă 90 secunde pentru oprire graceful
|
||||||
|
- **Step 3:** Shutdown pve1 și pve2 (noduri secundare)
|
||||||
|
- **Step 4:** Așteaptă 30 secunde
|
||||||
|
- **Step 5:** Shutdown pvemini (nod primary - ultimul)
|
||||||
|
|
||||||
|
### Scenario 3: Baterie scăzută imediată
|
||||||
|
1. UPS raportează LOWBATT (baterie critică)
|
||||||
|
2. Shutdown **IMEDIAT** (fără timer)
|
||||||
|
3. Același flux de shutdown orchestrat ca mai sus
|
||||||
|
|
||||||
|
## Quick Start
|
||||||
|
|
||||||
|
### Pentru Administrator Nou
|
||||||
|
|
||||||
|
1. **Citește documentația:**
|
||||||
|
- Start: [`docs/UPS-SHUTDOWN-README.md`](docs/UPS-SHUTDOWN-README.md)
|
||||||
|
- Detalii NUT: [`docs/INSTALARE-NUT.md`](docs/INSTALARE-NUT.md)
|
||||||
|
- WinNUT: [`docs/INSTALARE-WINNUT.md`](docs/INSTALARE-WINNUT.md)
|
||||||
|
|
||||||
|
2. **Verifică status UPS:**
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
upsc nutdev1
|
||||||
|
```
|
||||||
|
|
||||||
|
3. **Test dry-run:**
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
cat /var/log/ups-shutdown-test.log
|
||||||
|
```
|
||||||
|
|
||||||
|
4. **Monitorizează în WinNUT:**
|
||||||
|
- Pornește WinNUT pe VM 201
|
||||||
|
- Verifică că se conectează la 10.0.20.201:3493
|
||||||
|
|
||||||
|
### Verificare Săptămânală
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Conectează-te la pvemini
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
|
||||||
|
# Status UPS
|
||||||
|
upsc nutdev1 ups.status battery.charge input.voltage
|
||||||
|
|
||||||
|
# Status servicii
|
||||||
|
systemctl status nut-server nut-monitor
|
||||||
|
|
||||||
|
# Logs evenimente recente
|
||||||
|
tail -20 /var/log/ups-events.log
|
||||||
|
|
||||||
|
# Test dry-run
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
```
|
||||||
|
|
||||||
|
### Verificare Lunară
|
||||||
|
|
||||||
|
**🔋 Test Automat Baterie (1 ale lunii la 00:00):**
|
||||||
|
|
||||||
|
Scriptul `/opt/scripts/ups-monthly-test.sh` rulează automat lunar și:
|
||||||
|
- Testează capacitatea reală a bateriei
|
||||||
|
- Monitorizează scăderea charge și voltage
|
||||||
|
- Evaluează sănătatea bateriei (EXCELLENT/GOOD/FAIR/POOR)
|
||||||
|
- Trimite raport HTML prin email via PVE::Notify
|
||||||
|
|
||||||
|
**Verificare rezultat test:**
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
# Vezi ultimul test
|
||||||
|
tail -50 /var/log/ups-monthly-test.log
|
||||||
|
|
||||||
|
# Rulare manuală (pentru testare)
|
||||||
|
/opt/scripts/ups-monthly-test.sh
|
||||||
|
```
|
||||||
|
|
||||||
|
**Documentație completă:** [`docs/UPS-MONTHLY-TEST.md`](docs/UPS-MONTHLY-TEST.md)
|
||||||
|
|
||||||
|
---
|
||||||
|
|
||||||
|
**Test fizic manual (opțional):**
|
||||||
|
- Deconectează UPS de la priză timp de 30 secunde
|
||||||
|
- Verifică că WinNUT detectează schimbarea (On Battery)
|
||||||
|
- Verifică logs: `tail -f /var/log/ups-events.log`
|
||||||
|
- Reconectează **înainte de 3 minute** pentru a evita shutdown
|
||||||
|
|
||||||
|
**Verificare SSH între noduri:**
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
ssh root@10.0.20.200 "hostname"
|
||||||
|
ssh root@10.0.20.202 "hostname"
|
||||||
|
```
|
||||||
|
|
||||||
|
## Instalare de la Zero
|
||||||
|
|
||||||
|
### 1. Instalare NUT pe pvemini
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Instalare pachete
|
||||||
|
apt update
|
||||||
|
apt install -y nut nut-client nut-server
|
||||||
|
|
||||||
|
# Copiere fișiere de configurare
|
||||||
|
cd /path/to/ROMFASTSQL/proxmox/ups
|
||||||
|
scp config/* root@10.0.20.201:/etc/nut/
|
||||||
|
|
||||||
|
# Copiere scripturi shutdown
|
||||||
|
scp scripts/ups-shutdown-cluster.sh scripts/ups-shutdown-test.sh scripts/upssched-cmd root@10.0.20.201:/usr/local/bin/
|
||||||
|
ssh root@10.0.20.201 "chmod +x /usr/local/bin/ups-*.sh /usr/local/bin/upssched-cmd"
|
||||||
|
|
||||||
|
# Copiere script test lunar
|
||||||
|
scp scripts/ups-monthly-test.sh root@10.0.20.201:/opt/scripts/
|
||||||
|
ssh root@10.0.20.201 "chmod +x /opt/scripts/ups-monthly-test.sh"
|
||||||
|
|
||||||
|
# Configurare cron pentru test lunar
|
||||||
|
ssh root@10.0.20.201 "(crontab -l 2>/dev/null | grep -v ups-monthly-test; echo '# UPS Monthly Battery Test'; echo '0 0 1 * * /opt/scripts/ups-monthly-test.sh') | crontab -"
|
||||||
|
|
||||||
|
# Configurare permisiuni
|
||||||
|
ssh root@10.0.20.201 "chown nut:nut /etc/nut/ups*.conf /etc/nut/upsd.*"
|
||||||
|
ssh root@10.0.20.201 "chmod 640 /etc/nut/upsd.users"
|
||||||
|
|
||||||
|
# Pornire servicii
|
||||||
|
ssh root@10.0.20.201 "systemctl enable nut-server nut-monitor"
|
||||||
|
ssh root@10.0.20.201 "systemctl start nut-server nut-monitor"
|
||||||
|
|
||||||
|
# Verificare
|
||||||
|
ssh root@10.0.20.201 "upsc nutdev1"
|
||||||
|
```
|
||||||
|
|
||||||
|
### 2. Instalare WinNUT pe VM 201
|
||||||
|
|
||||||
|
Vezi ghid detaliat: [`docs/INSTALARE-WINNUT.md`](docs/INSTALARE-WINNUT.md)
|
||||||
|
|
||||||
|
```
|
||||||
|
Server: 10.0.20.201
|
||||||
|
Port: 3493
|
||||||
|
UPS: nutdev1
|
||||||
|
User: admin
|
||||||
|
Pass: parola99
|
||||||
|
Polling: 15
|
||||||
|
```
|
||||||
|
|
||||||
|
## Troubleshooting Rapid
|
||||||
|
|
||||||
|
### UPS nu răspunde
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
|
||||||
|
# Verifică UPS conectat
|
||||||
|
lsusb | grep 0665
|
||||||
|
|
||||||
|
# Restart driver
|
||||||
|
upsdrvctl stop && upsdrvctl start
|
||||||
|
|
||||||
|
# Verifică status
|
||||||
|
upsc nutdev1
|
||||||
|
```
|
||||||
|
|
||||||
|
### WinNUT nu se conectează
|
||||||
|
|
||||||
|
1. **Verifică Polling Interval ≠ 0** (pune 15)
|
||||||
|
2. **Test port:**
|
||||||
|
```powershell
|
||||||
|
Test-NetConnection -ComputerName 10.0.20.201 -Port 3493
|
||||||
|
```
|
||||||
|
3. **Verifică server:**
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "ss -tulpn | grep 3493"
|
||||||
|
```
|
||||||
|
|
||||||
|
### Scriptul de shutdown nu funcționează
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Test SSH între noduri
|
||||||
|
ssh root@10.0.20.201 "ssh root@10.0.20.200 hostname"
|
||||||
|
|
||||||
|
# Dacă eșuează, reconfigurează SSH keys
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
ssh-keygen -f /root/.ssh/known_hosts -R 10.0.20.200
|
||||||
|
ssh-keyscan -H 10.0.20.200 >> /root/.ssh/known_hosts
|
||||||
|
```
|
||||||
|
|
||||||
|
## Logs Important
|
||||||
|
|
||||||
|
| Fișier | Scop |
|
||||||
|
|--------|------|
|
||||||
|
| `/var/log/ups-shutdown.log` | Shutdown orchestrat real |
|
||||||
|
| `/var/log/ups-shutdown-test.log` | Test dry-run |
|
||||||
|
| `/var/log/ups-events.log` | Evenimente UPS (upssched) |
|
||||||
|
| `/var/log/ups-monthly-test.log` | **Test lunar baterie (NOU!)** |
|
||||||
|
| `journalctl -u nut-server` | Server NUT |
|
||||||
|
| `journalctl -u nut-monitor` | Monitor NUT |
|
||||||
|
|
||||||
|
## Comenzi Utile
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Status UPS complet
|
||||||
|
upsc nutdev1
|
||||||
|
|
||||||
|
# Doar câmpuri importante
|
||||||
|
upsc nutdev1 ups.status battery.charge input.voltage output.voltage
|
||||||
|
|
||||||
|
# Comenzi disponibile
|
||||||
|
upscmd -l nutdev1
|
||||||
|
|
||||||
|
# Conexiuni active NUT
|
||||||
|
ss -tnp | grep 3493
|
||||||
|
|
||||||
|
# Monitoring live
|
||||||
|
watch -n 2 'upsc nutdev1 ups.status battery.charge input.voltage'
|
||||||
|
|
||||||
|
# Test shutdown (DRY RUN - nu oprește nimic)
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
|
||||||
|
# Test lunar baterie (cu raport email)
|
||||||
|
/opt/scripts/ups-monthly-test.sh
|
||||||
|
|
||||||
|
# Verifică ultimul test lunar
|
||||||
|
tail -50 /var/log/ups-monthly-test.log
|
||||||
|
```
|
||||||
|
|
||||||
|
## Configurare Personalizată
|
||||||
|
|
||||||
|
### Modificare timp de așteptare (default: 3 minute)
|
||||||
|
|
||||||
|
Editează `/etc/nut/upssched.conf` pe pvemini:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Schimbă din 180 (3 min) la 300 (5 min)
|
||||||
|
AT ONBATT * START-TIMER onbatt 300
|
||||||
|
```
|
||||||
|
|
||||||
|
Apoi:
|
||||||
|
```bash
|
||||||
|
systemctl restart nut-monitor
|
||||||
|
```
|
||||||
|
|
||||||
|
### Adăugare noduri noi în cluster
|
||||||
|
|
||||||
|
Editează `/usr/local/bin/ups-shutdown-cluster.sh`:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Adaugă IP-ul noului nod
|
||||||
|
NODES=("10.0.20.200" "10.0.20.202" "10.0.20.XXX")
|
||||||
|
```
|
||||||
|
|
||||||
|
## Backup și Restore
|
||||||
|
|
||||||
|
### Backup configurație
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# De pe stația locală
|
||||||
|
cd /path/to/ROMFASTSQL/proxmox/ups
|
||||||
|
|
||||||
|
# Backup configurație
|
||||||
|
ssh root@10.0.20.201 "tar czf /tmp/nut-backup.tar.gz /etc/nut/*.conf /usr/local/bin/ups*.sh /usr/local/bin/upssched-cmd"
|
||||||
|
scp root@10.0.20.201:/tmp/nut-backup.tar.gz ./nut-backup-$(date +%Y%m%d).tar.gz
|
||||||
|
```
|
||||||
|
|
||||||
|
### Restore configurație
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Extrage backup
|
||||||
|
tar xzf nut-backup-YYYYMMDD.tar.gz
|
||||||
|
|
||||||
|
# Copiază pe server
|
||||||
|
scp -r etc/nut/* root@10.0.20.201:/etc/nut/
|
||||||
|
scp usr/local/bin/* root@10.0.20.201:/usr/local/bin/
|
||||||
|
|
||||||
|
# Restart servicii
|
||||||
|
ssh root@10.0.20.201 "systemctl restart nut-server nut-monitor"
|
||||||
|
```
|
||||||
|
|
||||||
|
## Securitate
|
||||||
|
|
||||||
|
### Parole
|
||||||
|
|
||||||
|
**IMPORTANT:** Schimbă parolele default!
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
nano /etc/nut/upsd.users
|
||||||
|
|
||||||
|
# Schimbă "parola99" cu ceva sigur
|
||||||
|
# Apoi restart:
|
||||||
|
systemctl restart nut-server
|
||||||
|
```
|
||||||
|
|
||||||
|
### Firewall
|
||||||
|
|
||||||
|
NUT portul 3493 trebuie accesibil din rețea locală. Dacă ai firewall:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Permite port 3493 din subnet local
|
||||||
|
iptables -A INPUT -p tcp --dport 3493 -s 10.0.20.0/24 -j ACCEPT
|
||||||
|
```
|
||||||
|
|
||||||
|
## Suport și Documentație
|
||||||
|
|
||||||
|
- **NUT Official:** https://networkupstools.org/
|
||||||
|
- **NUT Documentation:** https://networkupstools.org/docs/user-manual.chunked/
|
||||||
|
- **Hardware Compatibility:** https://networkupstools.org/stable-hcl.html
|
||||||
|
- **WinNUT GitHub:** https://github.com/gawindx/WinNUT-V2
|
||||||
|
|
||||||
|
## Funcționalități Complete
|
||||||
|
|
||||||
|
### ✅ Shutdown Orchestrat Automat
|
||||||
|
- Detectare întrerupere curent (3 minute grace period)
|
||||||
|
- Oprire ordonată: VM-uri → noduri secundare → nod primary
|
||||||
|
- Notificări în timp real prin upssched
|
||||||
|
|
||||||
|
### ✅ Test Lunar Automat Baterie (NOU!)
|
||||||
|
- Rulare automată pe 1 ale lunii la 00:00
|
||||||
|
- Test real capacitate baterie (comutare pe baterie ~10 secunde)
|
||||||
|
- Evaluare sănătate: EXCELLENT/GOOD/FAIR/POOR
|
||||||
|
- Rapoarte HTML + email prin PVE::Notify
|
||||||
|
- Recomandări automate pentru înlocuire baterie
|
||||||
|
- Log detaliat istoric teste
|
||||||
|
|
||||||
|
### ✅ Monitorizare Continuă
|
||||||
|
- WinNUT pe VM 201 (Windows 11) pentru vizualizare real-time
|
||||||
|
- NUT server pe pvemini expune date la toate nodurile
|
||||||
|
- Logging complet evenimente și teste
|
||||||
|
|
||||||
|
## Autori și Istoric
|
||||||
|
|
||||||
|
- **Creat:** 2025-10-06
|
||||||
|
- **Versiune:** 1.1
|
||||||
|
- **Ultima modificare:** 2025-10-06
|
||||||
|
- **Autor:** Configurat automat via Claude Code
|
||||||
|
- **Changelog:**
|
||||||
|
- v1.1 (2025-10-06): Adăugat test lunar automat baterie cu notificări PVE::Notify
|
||||||
|
- v1.0 (2025-10-06): Release inițial cu shutdown orchestrat și monitorizare NUT
|
||||||
|
|
||||||
|
## Licență
|
||||||
|
|
||||||
|
Documentația și scripturile sunt furnizate "as-is" fără garanție.
|
||||||
|
NUT și WinNUT sunt software open-source cu licențele lor respective.
|
||||||
7
proxmox/ups/config/ups.conf
Normal file
7
proxmox/ups/config/ups.conf
Normal file
@@ -0,0 +1,7 @@
|
|||||||
|
[nutdev1]
|
||||||
|
driver = nutdrv_qx
|
||||||
|
port = auto
|
||||||
|
vendorid = 0665
|
||||||
|
productid = 5161
|
||||||
|
subdriver = cypress
|
||||||
|
desc = "UPS Cypress via USB"
|
||||||
170
proxmox/ups/config/upsd.conf
Normal file
170
proxmox/ups/config/upsd.conf
Normal file
@@ -0,0 +1,170 @@
|
|||||||
|
# Network UPS Tools: example upsd configuration file
|
||||||
|
#
|
||||||
|
# This file contains access control data, you should keep it secure.
|
||||||
|
#
|
||||||
|
# It should only be readable by the user that upsd becomes. See the FAQ.
|
||||||
|
#
|
||||||
|
# Each entry below provides usage and default value.
|
||||||
|
#
|
||||||
|
# For more information, refer to upsd.conf manual page.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# MAXAGE <seconds>
|
||||||
|
# MAXAGE 15
|
||||||
|
#
|
||||||
|
# This defaults to 15 seconds. After a UPS driver has stopped updating
|
||||||
|
# the data for this many seconds, upsd marks it stale and stops making
|
||||||
|
# that information available to clients. After all, the only thing worse
|
||||||
|
# than no data is bad data.
|
||||||
|
#
|
||||||
|
# You should only use this if your driver has difficulties keeping
|
||||||
|
# the data fresh within the normal 15 second interval. Watch the syslog
|
||||||
|
# for notifications from upsd about staleness.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# TRACKINGDELAY <seconds>
|
||||||
|
# TRACKINGDELAY 3600
|
||||||
|
#
|
||||||
|
# This defaults to 1 hour. When instant commands and variables setting status
|
||||||
|
# tracking is enabled, status execution information are kept during this
|
||||||
|
# amount of time, and then cleaned up.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# ALLOW_NO_DEVICE <Boolean>
|
||||||
|
# ALLOW_NO_DEVICE true
|
||||||
|
#
|
||||||
|
# Normally upsd requires that at least one device section is defined in ups.conf
|
||||||
|
# when the daemon starts, to serve its data. For automatically managed services
|
||||||
|
# it may be preferred to have upsd always running, and reload the configuration
|
||||||
|
# when power devices become defined.
|
||||||
|
#
|
||||||
|
# Boolean values 'true', 'yes', 'on' and '1' mean that the server would not
|
||||||
|
# refuse to start with zero device sections found in ups.conf.
|
||||||
|
#
|
||||||
|
# Boolean values 'false', 'no', 'off' and '0' mean that the server should refuse
|
||||||
|
# to start if zero device sections were found in ups.conf. This is the default.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# STATEPATH <path>
|
||||||
|
# STATEPATH /var/run/nut
|
||||||
|
#
|
||||||
|
# Tell upsd to look for the driver state sockets in 'path' rather
|
||||||
|
# than the default that was compiled into the program.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# LISTEN <IP address or name> [<port>]
|
||||||
|
# LISTEN 127.0.0.1 3493
|
||||||
|
# LISTEN ::1 3493
|
||||||
|
# LISTEN myhostname 83493
|
||||||
|
# LISTEN myhostname.mydomain
|
||||||
|
#
|
||||||
|
# This defaults to the localhost listening addresses and port 3493.
|
||||||
|
# In case of IP v4 or v6 disabled kernel, only the available one will be used.
|
||||||
|
#
|
||||||
|
# You may specify each interface IP address or name that you want upsd to
|
||||||
|
# listen on for connections, optionally with a port number.
|
||||||
|
#
|
||||||
|
# You may need this if you have multiple interfaces on your machine and
|
||||||
|
# you don't want upsd to listen to all interfaces (for instance on a
|
||||||
|
# firewall, you may not want to listen to the external interface).
|
||||||
|
#
|
||||||
|
# This will only be read at startup of upsd. If you make changes here,
|
||||||
|
# you'll need to restart upsd, reload will have no effect.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# MAXCONN <connections>
|
||||||
|
# MAXCONN 1024
|
||||||
|
#
|
||||||
|
# This defaults to maximum number allowed on your system. Each UPS, each
|
||||||
|
# LISTEN address and each client count as one connection. If the server
|
||||||
|
# runs out of connections, it will no longer accept new incoming client
|
||||||
|
# connections. Only set this if you know exactly what you're doing.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# CERTFILE <certificate file>
|
||||||
|
# CERTFILE /usr/local/ups/etc/upsd.pem
|
||||||
|
#
|
||||||
|
# When compiled with SSL support with OpenSSL backend,
|
||||||
|
# you can enter the certificate file here.
|
||||||
|
# The certificates must be in PEM format and must be sorted starting with
|
||||||
|
# the subject's certificate (server certificate), followed by intermediate
|
||||||
|
# CA certificates (if applicable_ and the highest level (root) CA. It should
|
||||||
|
# end with the server key. See 'docs/security.txt' or the Security chapter of
|
||||||
|
# NUT user manual for more information on the SSL support in NUT.
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# CERTPATH <certificate file or directory>
|
||||||
|
# CERTPATH /usr/local/ups/etc/cert/upsd
|
||||||
|
#
|
||||||
|
# When compiled with SSL support with NSS backend,
|
||||||
|
# you can enter the certificate path here.
|
||||||
|
# Certificates are stored in a dedicated database (split into 3 files).
|
||||||
|
# Specify the path of the database directory.
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# CERTIDENT <certificate name> <database password>
|
||||||
|
# CERTIDENT "my nut server" "MyPasSw0rD"
|
||||||
|
#
|
||||||
|
# When compiled with SSL support with NSS backend,
|
||||||
|
# you can specify the certificate name to retrieve from database to
|
||||||
|
# authenticate itself and the password
|
||||||
|
# required to access certificate related private key.
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# CERTREQUEST <certificate request level>
|
||||||
|
# CERTREQUEST REQUIRE
|
||||||
|
#
|
||||||
|
# When compiled with SSL support with NSS backend and client certificate
|
||||||
|
# validation (disabled by default, see 'docs/security.txt'),
|
||||||
|
# you can specify if upsd requests or requires client's' certificates.
|
||||||
|
# Possible values are :
|
||||||
|
# - 0 to not request to clients to provide any certificate
|
||||||
|
# - 1 to require to all clients a certificate
|
||||||
|
# - 2 to require to all clients a valid certificate
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# DISABLE_WEAK_SSL <Boolean>
|
||||||
|
# DISABLE_WEAK_SSL true
|
||||||
|
#
|
||||||
|
# Tell upsd to disable older/weak SSL/TLS protocols and ciphers.
|
||||||
|
#
|
||||||
|
# With relatively recent versions of OpenSSL or NSS it will be restricted
|
||||||
|
# to TLSv1.2 or better.
|
||||||
|
#
|
||||||
|
# Unless you have really ancient clients, you probably want to enable this.
|
||||||
|
# Currently disabled by default to ensure compatibility with existing setups.
|
||||||
|
|
||||||
|
# =======================================================================
|
||||||
|
# DEBUG_MIN <Integer>
|
||||||
|
# DEBUG_MIN 2
|
||||||
|
#
|
||||||
|
# Optionally specify a minimum debug level for `upsd` data daemon, e.g. for
|
||||||
|
# troubleshooting a deployment, without impacting foreground or background
|
||||||
|
# running mode directly, and without need to edit init-scripts or service
|
||||||
|
# unit definitions. Note that command-line option `-D` can only increase
|
||||||
|
# this verbosity level.
|
||||||
|
#
|
||||||
|
# NOTE: if the running daemon receives a `reload` command, presence of the
|
||||||
|
# `DEBUG_MIN NUMBER` value in the configuration file can be used to tune
|
||||||
|
# debugging verbosity in the running service daemon (it is recommended to
|
||||||
|
# comment it away or set the minimum to explicit zero when done, to avoid
|
||||||
|
# huge journals and I/O system abuse). Keep in mind that for this run-time
|
||||||
|
# tuning, the `DEBUG_MIN` value *present* in *reloaded* configuration files
|
||||||
|
# is applied instantly and overrides any previously set value, from file
|
||||||
|
# or CLI options, regardless of older logging level being higher or lower
|
||||||
|
# than the newly found number; a missing (or commented away) value however
|
||||||
|
# does not change the previously active logging verbosity.
|
||||||
|
LISTEN 127.0.0.1 3493
|
||||||
|
LISTEN 10.0.20.201 3493
|
||||||
80
proxmox/ups/config/upsd.users
Normal file
80
proxmox/ups/config/upsd.users
Normal file
@@ -0,0 +1,80 @@
|
|||||||
|
# Network UPS Tools: Example upsd.users
|
||||||
|
#
|
||||||
|
# This file sets the permissions for upsd - the UPS network daemon.
|
||||||
|
# Users are defined here, are given passwords, and their privileges are
|
||||||
|
# controlled here too. Since this file will contain passwords, keep it
|
||||||
|
# secure, with only enough permissions for upsd to read it.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
|
||||||
|
# Each user gets a section. To start a section, put the username in
|
||||||
|
# brackets on a line by itself. To set something for that user, specify
|
||||||
|
# it under that section heading. The username is case-sensitive, so
|
||||||
|
# admin and AdMiN are two different users.
|
||||||
|
#
|
||||||
|
# Possible settings:
|
||||||
|
#
|
||||||
|
# password: The user's password. This is case-sensitive.
|
||||||
|
#
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
#
|
||||||
|
# actions: Let the user do certain things with upsd.
|
||||||
|
#
|
||||||
|
# Valid actions are:
|
||||||
|
#
|
||||||
|
# SET - change the value of certain variables in the UPS
|
||||||
|
# FSD - set the "forced shutdown" flag in the UPS
|
||||||
|
#
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
#
|
||||||
|
# instcmds: Let the user initiate specific instant commands. Use "ALL"
|
||||||
|
# to grant all commands automatically. There are many possible
|
||||||
|
# commands, so use 'upscmd -l' to see what your hardware supports. Here
|
||||||
|
# are a few examples:
|
||||||
|
#
|
||||||
|
# test.panel.start - Start a front panel test
|
||||||
|
# test.battery.start - Start battery test
|
||||||
|
# test.battery.stop - Stop battery test
|
||||||
|
# calibrate.start - Start calibration
|
||||||
|
# calibrate.stop - Stop calibration
|
||||||
|
#
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
#
|
||||||
|
# Example:
|
||||||
|
#
|
||||||
|
# [admin]
|
||||||
|
# password = mypass
|
||||||
|
# actions = SET
|
||||||
|
# instcmds = ALL
|
||||||
|
#
|
||||||
|
|
||||||
|
#
|
||||||
|
# --- Configuring for a user who can execute tests only
|
||||||
|
#
|
||||||
|
# [testuser]
|
||||||
|
# password = pass
|
||||||
|
# instcmds = test.battery.start
|
||||||
|
# instcmds = test.battery.stop
|
||||||
|
|
||||||
|
#
|
||||||
|
# --- Configuring for upsmon
|
||||||
|
#
|
||||||
|
# To add a user for your upsmon, use this example:
|
||||||
|
#
|
||||||
|
# [upsmon]
|
||||||
|
# password = pass
|
||||||
|
# upsmon primary
|
||||||
|
# or
|
||||||
|
# upsmon secondary
|
||||||
|
#
|
||||||
|
# The matching MONITOR line in your upsmon.conf would look like this:
|
||||||
|
#
|
||||||
|
# MONITOR myups@localhost 1 upsmon pass primary (or secondary)
|
||||||
|
#
|
||||||
|
# See comments in the upsmon.conf(.sample) file for details about this
|
||||||
|
# keyword and the difference of NUT secondary and primary systems.
|
||||||
|
[admin]
|
||||||
|
password = parola99
|
||||||
|
actions = SET
|
||||||
|
instcmds = ALL
|
||||||
|
upsmon master
|
||||||
466
proxmox/ups/config/upsmon.conf
Normal file
466
proxmox/ups/config/upsmon.conf
Normal file
@@ -0,0 +1,466 @@
|
|||||||
|
# Network UPS Tools: example upsmon configuration
|
||||||
|
#
|
||||||
|
# This file contains passwords, so keep it secure.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# RUN_AS_USER <userid>
|
||||||
|
#
|
||||||
|
# By default, upsmon splits into two processes. One stays as root and
|
||||||
|
# waits to run the SHUTDOWNCMD. The other one switches to another userid
|
||||||
|
# and does everything else.
|
||||||
|
#
|
||||||
|
# The default unprivileged user is set at compile-time with the option
|
||||||
|
# 'configure --with-user=...'
|
||||||
|
#
|
||||||
|
# You can override it with '-u <user>' when starting upsmon, or just
|
||||||
|
# define it here for convenience.
|
||||||
|
#
|
||||||
|
# Note: if you plan to use the reload feature, this file (upsmon.conf)
|
||||||
|
# must be readable by this user! Since it contains passwords, DO NOT
|
||||||
|
# make it world-readable. Also, do not make it writable by the upsmon
|
||||||
|
# user, since it creates an opportunity for an attack by changing the
|
||||||
|
# SHUTDOWNCMD to something malicious.
|
||||||
|
#
|
||||||
|
# For best results, you should create a new normal user like "nutmon",
|
||||||
|
# and make it a member of a "nut" group or similar. Then specify it
|
||||||
|
# here and grant read access to the upsmon.conf for that group.
|
||||||
|
#
|
||||||
|
# This user should not have write access to upsmon.conf.
|
||||||
|
#
|
||||||
|
# RUN_AS_USER nut
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# MONITOR <system> <powervalue> <username> <password> ("primary"|"secondary")
|
||||||
|
#
|
||||||
|
# List systems you want to monitor. Not all of these may supply power
|
||||||
|
# to the system running upsmon, but if you want to watch it, it has to
|
||||||
|
# be in this section.
|
||||||
|
#
|
||||||
|
# You must have at least one of these declared.
|
||||||
|
#
|
||||||
|
# <system> is a UPS identifier in the form <upsname>@<hostname>[:<port>]
|
||||||
|
# like ups@localhost, su700@mybox, etc.
|
||||||
|
#
|
||||||
|
# Examples:
|
||||||
|
#
|
||||||
|
# - "su700@mybox" means a UPS called "su700" on a system called "mybox"
|
||||||
|
#
|
||||||
|
# - "fenton@bigbox:5678" is a UPS called "fenton" on a system called
|
||||||
|
# "bigbox" which runs upsd on port "5678".
|
||||||
|
#
|
||||||
|
# The UPS names like "su700" and "fenton" are set in your ups.conf
|
||||||
|
# in [brackets] which identify a section for a particular driver.
|
||||||
|
#
|
||||||
|
# If the ups.conf on host "doghouse" has a section called "snoopy", the
|
||||||
|
# identifier for it would be "snoopy@doghouse".
|
||||||
|
#
|
||||||
|
# <powervalue> is an integer - the number of power supplies that this UPS
|
||||||
|
# feeds on this system. Most personal computers only have one power supply,
|
||||||
|
# so this value is normally set to 1, while most modern servers have at least
|
||||||
|
# two. You need a pretty big or special box to have any other value here.
|
||||||
|
#
|
||||||
|
# You can also set this to 0 for a system that doesn't take any power
|
||||||
|
# from the MONITORed supply, which you still want to monitor (e.g. for an
|
||||||
|
# administrative workstation fed from a different circuit than the datacenter
|
||||||
|
# servers it monitors). Use <powervalue> if 0 when you want to hear about
|
||||||
|
# changes for a given UPS without shutting down when it goes critical.
|
||||||
|
#
|
||||||
|
# <username> and <password> must match an entry in that system's
|
||||||
|
# upsd.users. If your username is "upsmon" and your password is
|
||||||
|
# "blah", the upsd.users would look like this:
|
||||||
|
#
|
||||||
|
# [upsmon]
|
||||||
|
# password = blah
|
||||||
|
# upsmon primary # (or secondary)
|
||||||
|
#
|
||||||
|
# "primary" means this system will shutdown last, allowing the secondary
|
||||||
|
# systems time to shutdown first.
|
||||||
|
#
|
||||||
|
# "secondary" means this system shuts down immediately when power goes
|
||||||
|
# critical and less than MINSUPPLIES power sources have reliable input feeds.
|
||||||
|
#
|
||||||
|
# The general assumption is that the "primary" system is the one with direct
|
||||||
|
# connection to an UPS (such as serial or USB cable), so the primary system
|
||||||
|
# runs the NUT driver and 'upsd' server locally and can manage the device,
|
||||||
|
# and it would often tell the UPS to completely power itself off as a step
|
||||||
|
# in power-race avoidance (see POWERDOWNFLAG for details).
|
||||||
|
#
|
||||||
|
# Also, since the primary system stays up the longest, it suffers higher risks
|
||||||
|
# of ungraceful shutdown if the estimation of remaining runtime (or of the
|
||||||
|
# time it takes to shut down this system) was guessed wrong. By consequence,
|
||||||
|
# the "secondary" systems typically monitor the power environment state
|
||||||
|
# through the 'upsd' processes running on the remote (often "primary") systems
|
||||||
|
# and do not directly interact with an UPS (no local NUT drivers are running
|
||||||
|
# on the secondary systems). As such, secondaries typically shut down as
|
||||||
|
# soon as there is a sufficiently long power outage, or a low-battery alert
|
||||||
|
# from the UPS, or a loss of connection to the primary while the power was
|
||||||
|
# last known to be missing.
|
||||||
|
#
|
||||||
|
# This assumption and configuration can also make sense for networked UPSes,
|
||||||
|
# where a rack full of servers might overload the communications capacity
|
||||||
|
# of the networked management card on the UPS - in this case you might either
|
||||||
|
# reduce the 'snmp-ups' or 'netxml-ups' driver polling rate, or dedicate a
|
||||||
|
# "primary" server and set up the rest as "secondary" systems.
|
||||||
|
#
|
||||||
|
# In case of such large setups as mentioned above, beware also that shutdown
|
||||||
|
# times of the rack done all at once can substantially differ from smaller
|
||||||
|
# scale experiments with single-server shutdowns, since systems can compete
|
||||||
|
# for shared storage and other limited resources as they go down (and also
|
||||||
|
# not everyone may safely shut down simultaneously - e.g. a NAS or DB server
|
||||||
|
# would better go down after all its clients). You would be well served by
|
||||||
|
# higher-end UPSes with manageable thresholds to declare a critical state.
|
||||||
|
#
|
||||||
|
# Examples:
|
||||||
|
#
|
||||||
|
# MONITOR myups@bigserver 1 upswired blah primary
|
||||||
|
# MONITOR su700@server.example.com 1 upsmon secretpass secondary
|
||||||
|
# MONITOR nutdev1@localhost 1 upsmon pass primary # (or secondary)
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# MINSUPPLIES <num>
|
||||||
|
#
|
||||||
|
# Give the number of power supplies that must be receiving power to keep
|
||||||
|
# this system running. Most systems have one power supply, so you would
|
||||||
|
# put "1" in this field.
|
||||||
|
#
|
||||||
|
# Large/expensive server type systems usually have more, and can run with
|
||||||
|
# a few missing. Some of these can run with 2 out of 4, for example,
|
||||||
|
# so you'd set that to 2. The idea is to keep the box running as long
|
||||||
|
# as possible, right?
|
||||||
|
#
|
||||||
|
# Obviously you have to put the redundant supplies on different UPS circuits
|
||||||
|
# for this to make sense! See big-servers.txt in the docs subdirectory
|
||||||
|
# for more information and ideas on how to use this feature.
|
||||||
|
|
||||||
|
MINSUPPLIES 1
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# SHUTDOWNCMD "<command>"
|
||||||
|
#
|
||||||
|
# upsmon runs this command when the system needs to be brought down.
|
||||||
|
#
|
||||||
|
# This should work just about everywhere ... if it doesn't, well, change it,
|
||||||
|
# perhaps to a more complicated custom script.
|
||||||
|
#
|
||||||
|
# Note that while you experiment with the initial setup and want to test how
|
||||||
|
# your configuration reacts to power state changes and ultimately when power
|
||||||
|
# is reported to go critical, but do not want your system to actually turn
|
||||||
|
# off, consider setting the SHUTDOWNCMD temporarily to do something benign -
|
||||||
|
# such as posting a message with 'logger' or 'wall' or 'mailx'. Do be careful
|
||||||
|
# to plug the UPS back into the wall in a timely fashion.
|
||||||
|
|
||||||
|
SHUTDOWNCMD "/sbin/shutdown -h +0"
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# NOTIFYCMD <command>
|
||||||
|
#
|
||||||
|
# upsmon calls this to send messages when things happen
|
||||||
|
#
|
||||||
|
# This command is called with the full text of the message (from NOTIFYMSG)
|
||||||
|
# as one argument.
|
||||||
|
#
|
||||||
|
# The environment string NOTIFYTYPE will contain the type string of
|
||||||
|
# whatever caused this event to happen.
|
||||||
|
#
|
||||||
|
# The environment string UPSNAME will contain the name of the system/device
|
||||||
|
# that generated the change.
|
||||||
|
#
|
||||||
|
# Note that this is only called for NOTIFY events that have EXEC set with
|
||||||
|
# NOTIFYFLAG. See NOTIFYFLAG below for more details.
|
||||||
|
#
|
||||||
|
# Making this some sort of shell script might not be a bad idea.
|
||||||
|
# Alternately you can use the upssched program as your NOTIFYCMD for some
|
||||||
|
# more complex setups (e.g. to ease handling of notification storms).
|
||||||
|
# For more information and ideas, see docs/scheduling.txt
|
||||||
|
#
|
||||||
|
# Example:
|
||||||
|
# NOTIFYCMD /bin/notifyme
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# POLLFREQ <n>
|
||||||
|
#
|
||||||
|
# Polling frequency for normal activities, measured in seconds.
|
||||||
|
#
|
||||||
|
# Adjust this to keep upsmon from flooding your network, but don't make
|
||||||
|
# it too high or it may miss certain short-lived power events.
|
||||||
|
|
||||||
|
POLLFREQ 5
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# POLLFREQALERT <n>
|
||||||
|
#
|
||||||
|
# Polling frequency in seconds while UPS on battery.
|
||||||
|
#
|
||||||
|
# You can make this number lower than POLLFREQ, which will make updates
|
||||||
|
# faster when any UPS is running on battery. This is a good way to tune
|
||||||
|
# network load if you have a lot of these things running.
|
||||||
|
#
|
||||||
|
# The default is 5 seconds for both this and POLLFREQ.
|
||||||
|
|
||||||
|
POLLFREQALERT 5
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# HOSTSYNC - How long upsmon will wait before giving up on another upsmon
|
||||||
|
#
|
||||||
|
# The primary upsmon process uses this number when waiting for secondary
|
||||||
|
# systems to disconnect once it has set the forced shutdown (FSD) flag.
|
||||||
|
# If they don't disconnect after this many seconds, it goes on without them.
|
||||||
|
#
|
||||||
|
# Similarly, upsmon secondary processes wait up to this interval for the
|
||||||
|
# primary upsmon to set FSD when an UPS they are monitoring goes critical -
|
||||||
|
# that is, on battery and low battery. If the primary doesn't do its job,
|
||||||
|
# the secondaries will shut down anyway to avoid damage to the file systems.
|
||||||
|
#
|
||||||
|
# This "wait for FSD" is done to avoid races where the status changes
|
||||||
|
# to critical and back between polls by the primary.
|
||||||
|
|
||||||
|
HOSTSYNC 15
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# DEADTIME - Interval to wait before declaring a stale ups "dead"
|
||||||
|
#
|
||||||
|
# upsmon requires a UPS to provide status information every few seconds
|
||||||
|
# (see POLLFREQ and POLLFREQALERT) to keep things updated. If the status
|
||||||
|
# fetch fails, the UPS is marked stale. If it stays stale for more than
|
||||||
|
# DEADTIME seconds, the UPS is marked dead.
|
||||||
|
#
|
||||||
|
# A dead UPS that was last known to be on battery is assumed to have gone
|
||||||
|
# to a low battery condition. This may force a shutdown if it is providing
|
||||||
|
# a critical amount of power to your system.
|
||||||
|
#
|
||||||
|
# Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
|
||||||
|
# Otherwise you'll have "dead" UPSes simply because upsmon isn't polling
|
||||||
|
# them quickly enough. Rule of thumb: take the larger of the two
|
||||||
|
# POLLFREQ values, and multiply by 3.
|
||||||
|
|
||||||
|
DEADTIME 15
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# POWERDOWNFLAG - Flag file for forcing UPS shutdown on the primary system
|
||||||
|
#
|
||||||
|
# upsmon will create a file with this name in primary mode when it's time
|
||||||
|
# to shut down the load. You should check for this file's existence in
|
||||||
|
# your shutdown scripts and run 'upsdrvctl shutdown' if it exists, to tell
|
||||||
|
# the UPS(es) to power off.
|
||||||
|
#
|
||||||
|
# See the config-notes.txt file in the docs subdirectory for more information.
|
||||||
|
# Refer to the section:
|
||||||
|
# [[UPS_shutdown]] "Configuring automatic shutdowns for low battery events"
|
||||||
|
# or refer to the online version.
|
||||||
|
|
||||||
|
POWERDOWNFLAG /etc/killpower
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# NOTIFYMSG - change messages sent by upsmon when certain events occur
|
||||||
|
#
|
||||||
|
# You can change the default messages to something else if you like.
|
||||||
|
#
|
||||||
|
# NOTIFYMSG <notify type> "message"
|
||||||
|
#
|
||||||
|
# NOTIFYMSG ONLINE "UPS %s on line power"
|
||||||
|
# NOTIFYMSG ONBATT "UPS %s on battery"
|
||||||
|
# NOTIFYMSG LOWBATT "UPS %s battery is low"
|
||||||
|
# NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
|
||||||
|
# NOTIFYMSG COMMOK "Communications with UPS %s established"
|
||||||
|
# NOTIFYMSG COMMBAD "Communications with UPS %s lost"
|
||||||
|
# NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
|
||||||
|
# NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
|
||||||
|
# NOTIFYMSG NOCOMM "UPS %s is unavailable"
|
||||||
|
# NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
|
||||||
|
#
|
||||||
|
# Note that %s is replaced with the identifier of the UPS in question.
|
||||||
|
#
|
||||||
|
# Possible values for <notify type>:
|
||||||
|
#
|
||||||
|
# ONLINE : UPS is back online
|
||||||
|
# ONBATT : UPS is on battery
|
||||||
|
# LOWBATT : UPS has a low battery (if also on battery, it's "critical")
|
||||||
|
# FSD : UPS is being shutdown by the primary (FSD = "Forced Shutdown")
|
||||||
|
# COMMOK : Communications established with the UPS
|
||||||
|
# COMMBAD : Communications lost to the UPS
|
||||||
|
# SHUTDOWN : The system is being shutdown
|
||||||
|
# REPLBATT : The UPS battery is bad and needs to be replaced
|
||||||
|
# NOCOMM : A UPS is unavailable (can't be contacted for monitoring)
|
||||||
|
# NOPARENT : The process that shuts down the system has died (shutdown impossible)
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# NOTIFYFLAG - change behavior of upsmon when NOTIFY events occur
|
||||||
|
#
|
||||||
|
# By default, upsmon sends walls (global messages to all logged in users)
|
||||||
|
# and writes to the syslog when things happen. You can change this.
|
||||||
|
#
|
||||||
|
# NOTIFYFLAG <notify type> <flag>[+<flag>][+<flag>] ...
|
||||||
|
#
|
||||||
|
# NOTIFYFLAG ONLINE SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG ONBATT SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG LOWBATT SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG FSD SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG COMMOK SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG COMMBAD SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG SHUTDOWN SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG REPLBATT SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG NOCOMM SYSLOG+WALL
|
||||||
|
# NOTIFYFLAG NOPARENT SYSLOG+WALL
|
||||||
|
#
|
||||||
|
# Possible values for the flags:
|
||||||
|
#
|
||||||
|
# SYSLOG - Write the message in the syslog
|
||||||
|
# WALL - Write the message to all users on the system
|
||||||
|
# EXEC - Execute NOTIFYCMD (see above) with the message
|
||||||
|
# IGNORE - Don't do anything
|
||||||
|
#
|
||||||
|
# If you use IGNORE, don't use any other flags on the same line.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# RBWARNTIME - replace battery warning time in seconds
|
||||||
|
#
|
||||||
|
# upsmon will normally warn you about a battery that needs to be replaced
|
||||||
|
# every 43200 seconds, which is 12 hours. It does this by triggering a
|
||||||
|
# NOTIFY_REPLBATT which is then handled by the usual notify structure
|
||||||
|
# you've defined above.
|
||||||
|
#
|
||||||
|
# If this number is not to your liking, override it here.
|
||||||
|
|
||||||
|
RBWARNTIME 43200
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# NOCOMMWARNTIME - no communications warning time in seconds
|
||||||
|
#
|
||||||
|
# upsmon will let you know through the usual notify system if it can't
|
||||||
|
# talk to any of the UPS entries that are defined in this file. It will
|
||||||
|
# trigger a NOTIFY_NOCOMM by default every 300 seconds unless you
|
||||||
|
# change the interval with this directive.
|
||||||
|
|
||||||
|
NOCOMMWARNTIME 300
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# FINALDELAY - last sleep interval before shutting down the system
|
||||||
|
#
|
||||||
|
# On a primary, upsmon will wait this long after sending the NOTIFY_SHUTDOWN
|
||||||
|
# before executing your SHUTDOWNCMD. If you need to do something in between
|
||||||
|
# those events, increase this number. Remember, at this point your UPS is
|
||||||
|
# almost depleted, so don't make this too high. If needed, on high-end UPS
|
||||||
|
# devices you can usually configure when the low-battery state is announced
|
||||||
|
# based on estimated remaining run-time or on charge level of the batteries.
|
||||||
|
#
|
||||||
|
# Alternatively, you can set this very low so you don't wait around when
|
||||||
|
# it's time to shut down. Some UPSes don't give much warning for low
|
||||||
|
# battery and will require a value of 0 here for a safe shutdown.
|
||||||
|
#
|
||||||
|
# Note: If FINALDELAY on the secondary is greater than HOSTSYNC on the
|
||||||
|
# primary, the primary will give up waiting for that secondary system
|
||||||
|
# to disconnect.
|
||||||
|
|
||||||
|
FINALDELAY 5
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# CERTPATH - path to certificates (database directory or directory with CA's)
|
||||||
|
#
|
||||||
|
# When compiled with SSL support, you can enter the certificate path here.
|
||||||
|
#
|
||||||
|
# With NSS:
|
||||||
|
# Certificates are stored in a dedicated database (split into 3 files).
|
||||||
|
# Specify the path of the database directory.
|
||||||
|
#
|
||||||
|
# CERTPATH /etc/nut/cert/upsmon
|
||||||
|
#
|
||||||
|
# With OpenSSL:
|
||||||
|
# Directory containing CA certificates in PEM format, used to verify
|
||||||
|
# the server certificate presented by the upsd server. The files each
|
||||||
|
# contain one CA certificate. The files are looked up by the CA subject
|
||||||
|
# name hash value, which must hence be available.
|
||||||
|
#
|
||||||
|
# CERTPATH /usr/ssl/certs
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# CERTIDENT - self certificate name and database password
|
||||||
|
# CERTIDENT <certificate name> <database password>
|
||||||
|
#
|
||||||
|
# When compiled with SSL support with NSS, you can specify the certificate
|
||||||
|
# name to retrieve from database to authenticate itself and the password
|
||||||
|
# required to access certificate related private key.
|
||||||
|
#
|
||||||
|
# CERTIDENT "my nut monitor" "MyPasSw0rD"
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# CERTHOST - security properties for an host
|
||||||
|
# CERTHOST <hostname> <certificate name> <certverify> <forcessl>
|
||||||
|
#
|
||||||
|
# When compiled with SSL support with NSS, you can specify security directive
|
||||||
|
# for each server you can contact.
|
||||||
|
# Each entry maps server name with the expected certificate name and flags
|
||||||
|
# indicating if the server certificate is verified and if the connection
|
||||||
|
# must be secure.
|
||||||
|
#
|
||||||
|
# CERTHOST localhost "My nut server" 1 1
|
||||||
|
#
|
||||||
|
# See 'docs/security.txt' or the Security chapter of NUT user manual
|
||||||
|
# for more information on the SSL support in NUT.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# CERTVERIFY - make upsmon verify all connections with certificates
|
||||||
|
# CERTVERIFY 1
|
||||||
|
#
|
||||||
|
# When compiled with SSL support, make upsmon verify all connections with
|
||||||
|
# certificates.
|
||||||
|
# Without this, there is no guarantee that the upsd is the right host.
|
||||||
|
# Enabling this greatly reduces the risk of man in the middle attacks.
|
||||||
|
# This effectively forces the use of SSL, so don't use this unless
|
||||||
|
# all of your upsd hosts are ready for SSL and have their certificates
|
||||||
|
# in order.
|
||||||
|
# When compiled with NSS support of SSL, can be overridden for host
|
||||||
|
# specified with a CERTHOST directive.
|
||||||
|
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# FORCESSL - force upsmon to use SSL
|
||||||
|
# FORCESSL 1
|
||||||
|
#
|
||||||
|
# When compiled with SSL, specify that a secured connection must be used
|
||||||
|
# to communicate with upsd.
|
||||||
|
# If you don't use 'CERTVERIFY 1', then this will at least make sure
|
||||||
|
# that nobody can sniff your sessions without a large effort. Setting
|
||||||
|
# this will make upsmon drop connections if the remote upsd doesn't
|
||||||
|
# support SSL, so don't use it unless all of them have it running.
|
||||||
|
# When compiled with NSS support of SSL, can be overridden for host
|
||||||
|
# specified with a CERTHOST directive.
|
||||||
|
|
||||||
|
# --------------------------------------------------------------------------
|
||||||
|
# DEBUG_MIN - specify minimal debugging level for upsmon daemon
|
||||||
|
# e.g. DEBUG_MIN 6
|
||||||
|
#
|
||||||
|
# Optionally specify a minimum debug level for `upsmon` daemon, e.g. for
|
||||||
|
# troubleshooting a deployment, without impacting foreground or background
|
||||||
|
# running mode directly, and without need to edit init-scripts or service
|
||||||
|
# unit definitions. Note that command-line option `-D` can only increase
|
||||||
|
# this verbosity level.
|
||||||
|
#
|
||||||
|
# NOTE: if the running daemon receives a `reload` command, presence of the
|
||||||
|
# `DEBUG_MIN NUMBER` value in the configuration file can be used to tune
|
||||||
|
# debugging verbosity in the running service daemon (it is recommended to
|
||||||
|
# comment it away or set the minimum to explicit zero when done, to avoid
|
||||||
|
# huge journals and I/O system abuse). Keep in mind that for this run-time
|
||||||
|
# tuning, the `DEBUG_MIN` value *present* in *reloaded* configuration files
|
||||||
|
# is applied instantly and overrides any previously set value, from file
|
||||||
|
# or CLI options, regardless of older logging level being higher or lower
|
||||||
|
# than the newly found number; a missing (or commented away) value however
|
||||||
|
# does not change the previously active logging verbosity.
|
||||||
|
|
||||||
|
# Monitorizare UPS - înlocuiește cu numele tău de UPS și credențialele
|
||||||
|
MONITOR nutdev1@localhost 1 admin parola99 master
|
||||||
|
|
||||||
|
# Folosește upssched pentru notificări
|
||||||
|
NOTIFYCMD /usr/sbin/upssched
|
||||||
|
|
||||||
|
# Activează notificările cu EXEC pentru a triggera upssched
|
||||||
|
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC
|
||||||
23
proxmox/ups/config/upssched.conf
Normal file
23
proxmox/ups/config/upssched.conf
Normal file
@@ -0,0 +1,23 @@
|
|||||||
|
# Configurare upssched pentru shutdown orchestrat cluster Proxmox
|
||||||
|
#
|
||||||
|
# Acest fișier definește acțiuni temporale pentru evenimente UPS
|
||||||
|
|
||||||
|
CMDSCRIPT /usr/local/bin/upssched-cmd
|
||||||
|
PIPEFN /run/nut/upssched.pipe
|
||||||
|
LOCKFN /run/nut/upssched.lock
|
||||||
|
|
||||||
|
# Când UPS trece pe baterie (ONBATT), așteaptă 180 secunde (3 minute)
|
||||||
|
# Dacă curentul revine în acest timp, anulează shutdown-ul
|
||||||
|
AT ONBATT * START-TIMER onbatt 180
|
||||||
|
|
||||||
|
# Când UPS raportează baterie scăzută (LOWBATT), shutdown imediat
|
||||||
|
AT LOWBATT * EXECUTE lowbatt
|
||||||
|
|
||||||
|
# Când curentul revine (ONLINE), anulează toate timer-ele
|
||||||
|
AT ONLINE * CANCEL-TIMER onbatt
|
||||||
|
|
||||||
|
# Când comunicația cu UPS se pierde (COMMBAD), așteaptă 30 secunde
|
||||||
|
AT COMMBAD * START-TIMER commbad 30
|
||||||
|
|
||||||
|
# Când comunicația este restabilită (COMMOK), anulează timer-ul
|
||||||
|
AT COMMOK * CANCEL-TIMER commbad
|
||||||
435
proxmox/ups/docs/INSTALARE-NUT.md
Normal file
435
proxmox/ups/docs/INSTALARE-NUT.md
Normal file
@@ -0,0 +1,435 @@
|
|||||||
|
# Instalare și Configurare NUT (Network UPS Tools) pe Proxmox
|
||||||
|
|
||||||
|
## Despre
|
||||||
|
|
||||||
|
Acest ghid descrie instalarea și configurarea NUT (Network UPS Tools) pe un cluster Proxmox pentru monitorizare UPS și shutdown orchestrat automat.
|
||||||
|
|
||||||
|
## Arhitectură
|
||||||
|
|
||||||
|
- **Nod PRIMARY (pvemini - 10.0.20.201):** Are UPS-ul conectat fizic via USB, rulează NUT server și driver
|
||||||
|
- **Noduri SECONDARY (pve1, pve2):** Pot monitoriza UPS-ul prin rețea (opțional)
|
||||||
|
- **VM 201 (Windows 11):** Monitorizare vizuală prin WinNUT client
|
||||||
|
|
||||||
|
## Prerequisite
|
||||||
|
|
||||||
|
- Proxmox VE instalat
|
||||||
|
- UPS conectat via USB la nodul primary
|
||||||
|
- Acces root la noduri
|
||||||
|
|
||||||
|
## 1. Instalare NUT pe Nodul PRIMARY
|
||||||
|
|
||||||
|
### 1.1. Instalare pachete
|
||||||
|
|
||||||
|
```bash
|
||||||
|
apt update
|
||||||
|
apt install -y nut nut-client nut-server
|
||||||
|
```
|
||||||
|
|
||||||
|
### 1.2. Detectare UPS
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Listează dispozitive USB
|
||||||
|
lsusb
|
||||||
|
|
||||||
|
# Exemple output:
|
||||||
|
# Bus 001 Device 002: ID 0665:5161 Cypress Semiconductor USB to Serial
|
||||||
|
|
||||||
|
# Verifică dacă kernel-ul a detectat UPS-ul
|
||||||
|
dmesg | grep -i ups
|
||||||
|
dmesg | grep -i hid
|
||||||
|
```
|
||||||
|
|
||||||
|
### 1.3. Testare driver NUT
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Caută driver potrivit pentru UPS-ul tău
|
||||||
|
nut-scanner -U
|
||||||
|
|
||||||
|
# sau
|
||||||
|
nut-scanner --usb_scan
|
||||||
|
```
|
||||||
|
|
||||||
|
## 2. Configurare NUT
|
||||||
|
|
||||||
|
### 2.1. Configurare Driver UPS (`/etc/nut/ups.conf`)
|
||||||
|
|
||||||
|
Creează configurația pentru UPS:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
cat > /etc/nut/ups.conf << 'EOF'
|
||||||
|
[nutdev1]
|
||||||
|
driver = nutdrv_qx
|
||||||
|
port = auto
|
||||||
|
vendorid = 0665
|
||||||
|
productid = 5161
|
||||||
|
subdriver = cypress
|
||||||
|
desc = "UPS Cypress via USB"
|
||||||
|
EOF
|
||||||
|
```
|
||||||
|
|
||||||
|
**Note:**
|
||||||
|
- Înlocuiește `vendorid` și `productid` cu valorile de la `lsusb`
|
||||||
|
- Driver-ul `nutdrv_qx` funcționează pentru majoritatea UPS-urilor Voltronic/Megatec/Q1
|
||||||
|
- Alte drivere comune: `usbhid-ups`, `blazer_usb`, `nutdrv_qx`
|
||||||
|
|
||||||
|
### 2.2. Configurare Server NUT (`/etc/nut/upsd.conf`)
|
||||||
|
|
||||||
|
```bash
|
||||||
|
cat >> /etc/nut/upsd.conf << 'EOF'
|
||||||
|
|
||||||
|
# Ascultă pe localhost pentru monitorul local
|
||||||
|
LISTEN 127.0.0.1 3493
|
||||||
|
|
||||||
|
# Ascultă pe IP-ul nodului pentru clienți din rețea
|
||||||
|
LISTEN 10.0.20.201 3493
|
||||||
|
EOF
|
||||||
|
```
|
||||||
|
|
||||||
|
**Note:**
|
||||||
|
- Înlocuiește `10.0.20.201` cu IP-ul nodului tău PRIMARY
|
||||||
|
- Portul default NUT este 3493
|
||||||
|
|
||||||
|
### 2.3. Configurare Utilizatori (`/etc/nut/upsd.users`)
|
||||||
|
|
||||||
|
```bash
|
||||||
|
cat > /etc/nut/upsd.users << 'EOF'
|
||||||
|
[admin]
|
||||||
|
password = parola99
|
||||||
|
actions = SET
|
||||||
|
instcmds = ALL
|
||||||
|
upsmon master
|
||||||
|
EOF
|
||||||
|
```
|
||||||
|
|
||||||
|
**IMPORTANT:** Schimbă parola `parola99` cu ceva sigur!
|
||||||
|
|
||||||
|
### 2.4. Configurare Monitor Local (`/etc/nut/upsmon.conf`)
|
||||||
|
|
||||||
|
Editează `/etc/nut/upsmon.conf` și adaugă:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Monitorizare UPS local
|
||||||
|
MONITOR nutdev1@localhost 1 admin parola99 master
|
||||||
|
|
||||||
|
# Folosește upssched pentru notificări
|
||||||
|
NOTIFYCMD /usr/sbin/upssched
|
||||||
|
|
||||||
|
# Activează notificările cu EXEC pentru evenimente
|
||||||
|
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC
|
||||||
|
```
|
||||||
|
|
||||||
|
**Note:**
|
||||||
|
- `master` = acest nod controlează UPS-ul (va fi ultimul care se închide)
|
||||||
|
- `1` = powervalue (câte surse de alimentare alimentează acest UPS)
|
||||||
|
|
||||||
|
### 2.5. Configurare NUT Mode (`/etc/nut/nut.conf`)
|
||||||
|
|
||||||
|
```bash
|
||||||
|
cat > /etc/nut/nut.conf << 'EOF'
|
||||||
|
MODE=netserver
|
||||||
|
EOF
|
||||||
|
```
|
||||||
|
|
||||||
|
Moduri disponibile:
|
||||||
|
- `none` - NUT dezactivat
|
||||||
|
- `standalone` - Doar local, fără rețea
|
||||||
|
- `netserver` - Server + local (recomandat pentru PRIMARY)
|
||||||
|
- `netclient` - Doar client (pentru noduri SECONDARY)
|
||||||
|
|
||||||
|
## 3. Pornire Servicii
|
||||||
|
|
||||||
|
### 3.1. Pornire driver UPS
|
||||||
|
|
||||||
|
```bash
|
||||||
|
upsdrvctl start
|
||||||
|
```
|
||||||
|
|
||||||
|
Ar trebui să vezi:
|
||||||
|
```
|
||||||
|
Network UPS Tools - UPS driver controller 2.8.0
|
||||||
|
Network UPS Tools - Megatec/Q1 protocol USB driver 0.32 (2.8.0)
|
||||||
|
Using subdriver: Cypress 0.10
|
||||||
|
```
|
||||||
|
|
||||||
|
### 3.2. Pornire server NUT
|
||||||
|
|
||||||
|
```bash
|
||||||
|
systemctl enable nut-server
|
||||||
|
systemctl start nut-server
|
||||||
|
systemctl status nut-server
|
||||||
|
```
|
||||||
|
|
||||||
|
### 3.3. Pornire monitor NUT
|
||||||
|
|
||||||
|
```bash
|
||||||
|
systemctl enable nut-monitor
|
||||||
|
systemctl start nut-monitor
|
||||||
|
systemctl status nut-monitor
|
||||||
|
```
|
||||||
|
|
||||||
|
## 4. Verificare Funcționare
|
||||||
|
|
||||||
|
### 4.1. Test status UPS
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Listează UPS-uri disponibile
|
||||||
|
upsc -l
|
||||||
|
|
||||||
|
# Afișează toate informațiile despre UPS
|
||||||
|
upsc nutdev1
|
||||||
|
|
||||||
|
# Doar status
|
||||||
|
upsc nutdev1 ups.status
|
||||||
|
|
||||||
|
# Baterie
|
||||||
|
upsc nutdev1 battery.charge
|
||||||
|
upsc nutdev1 battery.voltage
|
||||||
|
|
||||||
|
# Tensiuni
|
||||||
|
upsc nutdev1 input.voltage
|
||||||
|
upsc nutdev1 output.voltage
|
||||||
|
```
|
||||||
|
|
||||||
|
### 4.2. Verificare conexiuni
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică dacă upsd ascultă pe portul 3493
|
||||||
|
ss -tulpn | grep 3493
|
||||||
|
|
||||||
|
# Ar trebui să vezi:
|
||||||
|
# tcp LISTEN 0 16 127.0.0.1:3493 0.0.0.0:*
|
||||||
|
# tcp LISTEN 0 16 10.0.20.201:3493 0.0.0.0:*
|
||||||
|
```
|
||||||
|
|
||||||
|
### 4.3. Test de pe alt sistem
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# De pe un alt nod sau sistem:
|
||||||
|
upsc nutdev1@10.0.20.201
|
||||||
|
```
|
||||||
|
|
||||||
|
## 5. Configurare Scheduler Evenimente (upssched)
|
||||||
|
|
||||||
|
### 5.1. Creare `/etc/nut/upssched.conf`
|
||||||
|
|
||||||
|
```bash
|
||||||
|
cat > /etc/nut/upssched.conf << 'EOF'
|
||||||
|
CMDSCRIPT /usr/local/bin/upssched-cmd
|
||||||
|
PIPEFN /run/nut/upssched.pipe
|
||||||
|
LOCKFN /run/nut/upssched.lock
|
||||||
|
|
||||||
|
# UPS pe baterie - așteaptă 180 secunde (3 minute)
|
||||||
|
AT ONBATT * START-TIMER onbatt 180
|
||||||
|
|
||||||
|
# Baterie scăzută - acțiune imediată
|
||||||
|
AT LOWBATT * EXECUTE lowbatt
|
||||||
|
|
||||||
|
# Curent revenit - anulează timer
|
||||||
|
AT ONLINE * CANCEL-TIMER onbatt
|
||||||
|
|
||||||
|
# Comunicație pierdută - așteaptă 30 secunde
|
||||||
|
AT COMMBAD * START-TIMER commbad 30
|
||||||
|
|
||||||
|
# Comunicație restabilită
|
||||||
|
AT COMMOK * CANCEL-TIMER commbad
|
||||||
|
EOF
|
||||||
|
```
|
||||||
|
|
||||||
|
### 5.2. Creare handler script
|
||||||
|
|
||||||
|
Copiază scriptul `upssched-cmd` din directorul `scripts/` în `/usr/local/bin/`:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
cp scripts/upssched-cmd /usr/local/bin/
|
||||||
|
chmod +x /usr/local/bin/upssched-cmd
|
||||||
|
```
|
||||||
|
|
||||||
|
### 5.3. Creare director runtime
|
||||||
|
|
||||||
|
```bash
|
||||||
|
mkdir -p /run/nut
|
||||||
|
chown nut:nut /run/nut
|
||||||
|
chmod 770 /run/nut
|
||||||
|
```
|
||||||
|
|
||||||
|
## 6. Instalare Scripturi Shutdown Orchestrat
|
||||||
|
|
||||||
|
### 6.1. Copiere scripturi
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Script principal de shutdown
|
||||||
|
cp scripts/ups-shutdown-cluster.sh /usr/local/bin/
|
||||||
|
chmod +x /usr/local/bin/ups-shutdown-cluster.sh
|
||||||
|
|
||||||
|
# Script de test (dry-run)
|
||||||
|
cp scripts/ups-shutdown-test.sh /usr/local/bin/
|
||||||
|
chmod +x /usr/local/bin/ups-shutdown-test.sh
|
||||||
|
```
|
||||||
|
|
||||||
|
### 6.2. Editare noduri în script
|
||||||
|
|
||||||
|
Editează `/usr/local/bin/ups-shutdown-cluster.sh` și verifică:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
NODES=("10.0.20.200" "10.0.20.202") # IP-urile nodurilor SECONDARY
|
||||||
|
```
|
||||||
|
|
||||||
|
### 6.3. Configurare SSH între noduri
|
||||||
|
|
||||||
|
Pentru ca scriptul să funcționeze, trebuie ca nodul PRIMARY să poată face SSH pe nodurile SECONDARY fără parolă:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Generează SSH key dacă nu există
|
||||||
|
ssh-keygen -t ed25519 -N "" -f /root/.ssh/id_ed25519
|
||||||
|
|
||||||
|
# Copiază cheia pe nodurile SECONDARY
|
||||||
|
ssh-copy-id root@10.0.20.200
|
||||||
|
ssh-copy-id root@10.0.20.202
|
||||||
|
|
||||||
|
# Test conexiune
|
||||||
|
ssh root@10.0.20.200 "hostname"
|
||||||
|
ssh root@10.0.20.202 "hostname"
|
||||||
|
```
|
||||||
|
|
||||||
|
## 7. Testare
|
||||||
|
|
||||||
|
### 7.1. Test dry-run
|
||||||
|
|
||||||
|
```bash
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
cat /var/log/ups-shutdown-test.log
|
||||||
|
```
|
||||||
|
|
||||||
|
### 7.2. Test simulare UPS pe baterie (ATENȚIE!)
|
||||||
|
|
||||||
|
**⚠️ PERICOL:** Acest test va iniția shutdown real dacă îl lași să ruleze 3 minute!
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Monitorizează logs
|
||||||
|
tail -f /var/log/ups-events.log &
|
||||||
|
|
||||||
|
# Deconectează fizic UPS-ul de la priză
|
||||||
|
# Așteaptă 10-30 secunde
|
||||||
|
# Verifică că logs-urile arată "ONBATT"
|
||||||
|
# RECONECTEAZĂ UPS-ul înainte de 3 minute!
|
||||||
|
|
||||||
|
# Verifică că timer-ul a fost anulat
|
||||||
|
journalctl -u nut-monitor -f
|
||||||
|
```
|
||||||
|
|
||||||
|
## 8. Troubleshooting
|
||||||
|
|
||||||
|
### 8.1. Driver-ul nu pornește
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică permisiuni USB
|
||||||
|
ls -la /dev/bus/usb/*/*
|
||||||
|
|
||||||
|
# Driver manual cu debug
|
||||||
|
/lib/nut/nutdrv_qx -a nutdev1 -DDDDD
|
||||||
|
|
||||||
|
# Verifică logs
|
||||||
|
journalctl -u nut-driver@nutdev1 -f
|
||||||
|
```
|
||||||
|
|
||||||
|
### 8.2. Server nu pornește
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică configurația
|
||||||
|
upsd -c reload
|
||||||
|
|
||||||
|
# Debug mode
|
||||||
|
upsd -D
|
||||||
|
|
||||||
|
# Logs
|
||||||
|
journalctl -u nut-server -f
|
||||||
|
```
|
||||||
|
|
||||||
|
### 8.3. Monitor nu se conectează
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică parola în upsd.users
|
||||||
|
cat /etc/nut/upsd.users
|
||||||
|
|
||||||
|
# Verifică MONITOR line în upsmon.conf
|
||||||
|
grep "^MONITOR" /etc/nut/upsmon.conf
|
||||||
|
|
||||||
|
# Test manual
|
||||||
|
upsmon -D
|
||||||
|
```
|
||||||
|
|
||||||
|
### 8.4. UPS nu răspunde
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Reload driver
|
||||||
|
upsdrvctl stop
|
||||||
|
upsdrvctl start
|
||||||
|
|
||||||
|
# Verifică comunicația USB
|
||||||
|
lsusb -v -d 0665:5161
|
||||||
|
```
|
||||||
|
|
||||||
|
## 9. Logs și Monitorizare
|
||||||
|
|
||||||
|
### Logs importante:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
/var/log/ups-shutdown.log # Shutdown orchestrat real
|
||||||
|
/var/log/ups-shutdown-test.log # Test dry-run
|
||||||
|
/var/log/ups-events.log # Evenimente UPS (upssched)
|
||||||
|
journalctl -u nut-server # Server NUT
|
||||||
|
journalctl -u nut-monitor # Monitor NUT
|
||||||
|
journalctl -u nut-driver@nutdev1 # Driver UPS
|
||||||
|
```
|
||||||
|
|
||||||
|
### Comenzi utile:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Status complet UPS
|
||||||
|
upsc nutdev1
|
||||||
|
|
||||||
|
# Comenzi disponibile
|
||||||
|
upscmd -l nutdev1
|
||||||
|
|
||||||
|
# Variabile disponibile
|
||||||
|
upsc nutdev1 | grep -E "battery|input|output|ups.status"
|
||||||
|
|
||||||
|
# Monitorizare în timp real
|
||||||
|
watch -n 2 'upsc nutdev1 ups.status battery.charge input.voltage'
|
||||||
|
```
|
||||||
|
|
||||||
|
## 10. Întreținere
|
||||||
|
|
||||||
|
### Zilnic/Săptămânal:
|
||||||
|
```bash
|
||||||
|
# Verifică status UPS
|
||||||
|
upsc nutdev1 ups.status battery.charge
|
||||||
|
|
||||||
|
# Verifică servicii
|
||||||
|
systemctl status nut-server nut-monitor
|
||||||
|
```
|
||||||
|
|
||||||
|
### Lunar:
|
||||||
|
```bash
|
||||||
|
# Test dry-run
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
|
||||||
|
# Test fizic (deconectare scurtă < 1 min)
|
||||||
|
```
|
||||||
|
|
||||||
|
### Anual:
|
||||||
|
```bash
|
||||||
|
# Test complet de baterie pe UPS
|
||||||
|
# Backup înainte de test!
|
||||||
|
```
|
||||||
|
|
||||||
|
## Referințe
|
||||||
|
|
||||||
|
- Documentație oficială NUT: https://networkupstools.org/
|
||||||
|
- Lista drivere compatibile: https://networkupstools.org/stable-hcl.html
|
||||||
|
- NUT Users Manual: https://networkupstools.org/docs/user-manual.chunked/index.html
|
||||||
|
- Troubleshooting Guide: https://networkupstools.org/docs/user-manual.chunked/ar01s07.html
|
||||||
376
proxmox/ups/docs/INSTALARE-WINNUT.md
Normal file
376
proxmox/ups/docs/INSTALARE-WINNUT.md
Normal file
@@ -0,0 +1,376 @@
|
|||||||
|
# Instalare și Configurare WinNUT pe Windows 11 (VM 201)
|
||||||
|
|
||||||
|
## Despre
|
||||||
|
|
||||||
|
WinNUT este un client NUT (Network UPS Tools) pentru Windows care permite monitorizarea vizuală a unui UPS conectat la un server NUT remote (în cazul nostru, pvemini).
|
||||||
|
|
||||||
|
**IMPORTANT:** WinNUT este folosit DOAR pentru monitorizare vizuală. Shutdown-ul automat este gestionat de scripturile de pe Proxmox.
|
||||||
|
|
||||||
|
## Prerequisite
|
||||||
|
|
||||||
|
- Windows 11 (VM 201 pe pvemini)
|
||||||
|
- Server NUT funcțional pe pvemini (10.0.20.201)
|
||||||
|
- Conectivitate rețea către serverul NUT (port 3493)
|
||||||
|
|
||||||
|
## 1. Descărcare WinNUT
|
||||||
|
|
||||||
|
### Opțiunea 1: GitHub Releases (Recomandat)
|
||||||
|
|
||||||
|
1. Deschide browser în VM 201
|
||||||
|
2. Accesează: https://github.com/gawindx/WinNUT-V2/releases
|
||||||
|
3. Descarcă ultima versiune (ex: `WinNUT-v2.x.x-Setup.exe`)
|
||||||
|
|
||||||
|
### Opțiunea 2: Build from source (Opțional)
|
||||||
|
|
||||||
|
```powershell
|
||||||
|
# Clonează repository
|
||||||
|
git clone https://github.com/gawindx/WinNUT-V2.git
|
||||||
|
cd WinNUT-V2
|
||||||
|
|
||||||
|
# Urmează instrucțiunile de build din README
|
||||||
|
```
|
||||||
|
|
||||||
|
## 2. Instalare WinNUT
|
||||||
|
|
||||||
|
### 2.1. Rulare instalator
|
||||||
|
|
||||||
|
1. Rulează `WinNUT-v2.x.x-Setup.exe` ca Administrator
|
||||||
|
2. Acceptă UAC prompt
|
||||||
|
3. Alege directorul de instalare (implicit: `C:\Program Files\WinNUT`)
|
||||||
|
4. Finalizează instalarea
|
||||||
|
|
||||||
|
### 2.2. Verificare instalare
|
||||||
|
|
||||||
|
WinNUT ar trebui să pornească automat după instalare. Icon-ul va apărea în system tray.
|
||||||
|
|
||||||
|
## 3. Configurare WinNUT
|
||||||
|
|
||||||
|
### 3.1. Deschidere fereastră Options
|
||||||
|
|
||||||
|
- Click dreapta pe icon-ul WinNUT din system tray
|
||||||
|
- Selectează **"Options"** sau dublu-click pe icon
|
||||||
|
|
||||||
|
### 3.2. Tab Connection
|
||||||
|
|
||||||
|
Configurează următoarele:
|
||||||
|
|
||||||
|
| Câmp | Valoare | Descriere |
|
||||||
|
|------|---------|-----------|
|
||||||
|
| **NUT host** | `10.0.20.201` | IP-ul serverului NUT (pvemini) |
|
||||||
|
| **NUT Port** | `3493` | Portul default NUT |
|
||||||
|
| **UPS Name** | `nutdev1` | Numele UPS-ului (din ups.conf) |
|
||||||
|
| **Polling Interval** | `15` | Interval de polling în secunde (NU pune 0!) |
|
||||||
|
| **Login** | `admin` | Username (din upsd.users) |
|
||||||
|
| **Password** | `parola99` | Parola (din upsd.users) |
|
||||||
|
| **Re-establish connection** | ☑ Checked | Reconectare automată |
|
||||||
|
|
||||||
|
**IMPORTANT:**
|
||||||
|
- **Polling Interval** trebuie să fie > 0 (recomandat: 15)
|
||||||
|
- Dacă Polling Interval = 0, WinNUT nu se va conecta!
|
||||||
|
|
||||||
|
### 3.3. Tab Calibration
|
||||||
|
|
||||||
|
Lasă valorile default sau ajustează după preferințe pentru afișarea gauge-urilor.
|
||||||
|
|
||||||
|
### 3.4. Tab Miscellaneous
|
||||||
|
|
||||||
|
Configurări opționale:
|
||||||
|
- ☑ **Start with Windows** - Pornire automată
|
||||||
|
- ☑ **Minimize to tray** - Minimizare în system tray
|
||||||
|
- ☐ **Sound alerts** - Alerte sonore (opțional)
|
||||||
|
|
||||||
|
### 3.5. Tab Shutdown Options
|
||||||
|
|
||||||
|
**⚠️ IMPORTANT:** NU configura shutdown options în WinNUT!
|
||||||
|
|
||||||
|
Shutdown-ul este gestionat automat de scripturile de pe Proxmox. WinNUT este doar pentru monitorizare.
|
||||||
|
|
||||||
|
Lasă toate opțiunile de shutdown dezactivate:
|
||||||
|
- ☐ Shutdown on battery
|
||||||
|
- ☐ Shutdown on low battery
|
||||||
|
- ☐ Force shutdown
|
||||||
|
|
||||||
|
### 3.6. Salvare configurație
|
||||||
|
|
||||||
|
1. Click **OK** pentru a salva
|
||||||
|
2. WinNUT se va reconecta automat la serverul NUT
|
||||||
|
3. În câteva secunde, ar trebui să vezi datele UPS-ului
|
||||||
|
|
||||||
|
## 4. Verificare Funcționare
|
||||||
|
|
||||||
|
### 4.1. Fereastră principală
|
||||||
|
|
||||||
|
După conectare cu succes, ar trebui să vezi:
|
||||||
|
|
||||||
|
**Gauge-uri (indicatoare circulare):**
|
||||||
|
- **Input Voltage** (Tensiune intrare): ~230V
|
||||||
|
- **Output Voltage** (Tensiune ieșire): ~230V
|
||||||
|
- **Frequency** (Frecvență): ~50Hz
|
||||||
|
- **Battery Charge** (Încărcare baterie): 0-100%
|
||||||
|
- **Battery Voltage** (Tensiune baterie): ~24V (depinde de UPS)
|
||||||
|
- **UPS Load** (Sarcină UPS): 0-100%
|
||||||
|
|
||||||
|
**Status checkboxes:**
|
||||||
|
- ☑ **UPS On Line** - UPS pe curent electric (normal)
|
||||||
|
- ☐ **UPS On Battery** - UPS pe baterie (întrerupere curent)
|
||||||
|
- ☐ **UPS Overload** - UPS supraîncărcat
|
||||||
|
- ☐ **UPS Battery Low** - Baterie scăzută
|
||||||
|
|
||||||
|
**Informații suplimentare:**
|
||||||
|
- **Manufacturer:** (producător UPS)
|
||||||
|
- **Name:** nutdev1
|
||||||
|
- **Serial:** (număr serie)
|
||||||
|
- **Firmware:** (versiune firmware)
|
||||||
|
|
||||||
|
### 4.2. System tray icon
|
||||||
|
|
||||||
|
- **Verde:** UPS On Line (normal)
|
||||||
|
- **Galben:** UPS On Battery (atenție)
|
||||||
|
- **Roșu:** UPS Battery Low (critic)
|
||||||
|
|
||||||
|
### 4.3. Mesaj reconectare
|
||||||
|
|
||||||
|
În partea de jos a ferestrei vezi:
|
||||||
|
```
|
||||||
|
[id 4: 10/6/2025 7:56:48 PM] Try Reconnect 1 / 30
|
||||||
|
```
|
||||||
|
|
||||||
|
Dacă vezi acest mesaj constant:
|
||||||
|
1. Verifică configurația Connection (mai ales Polling Interval)
|
||||||
|
2. Verifică conectivitatea rețea (ping 10.0.20.201)
|
||||||
|
3. Verifică că serverul NUT rulează pe pvemini
|
||||||
|
|
||||||
|
## 5. Testare
|
||||||
|
|
||||||
|
### 5.1. Test conectivitate din PowerShell
|
||||||
|
|
||||||
|
```powershell
|
||||||
|
# Test ping
|
||||||
|
Test-NetConnection -ComputerName 10.0.20.201 -Port 3493
|
||||||
|
|
||||||
|
# Ar trebui să vezi:
|
||||||
|
# TcpTestSucceeded : True
|
||||||
|
```
|
||||||
|
|
||||||
|
### 5.2. Test simulare UPS pe baterie
|
||||||
|
|
||||||
|
1. Deconectează fizic UPS-ul de la priză (pe pvemini)
|
||||||
|
2. Observă în WinNUT:
|
||||||
|
- Checkbox **"UPS On Battery"** devine ☑
|
||||||
|
- Icon în system tray devine galben
|
||||||
|
- Input voltage scade
|
||||||
|
- Battery charge începe să scadă
|
||||||
|
3. Reconectează UPS-ul
|
||||||
|
4. Observă că status revine la **"UPS On Line"**
|
||||||
|
|
||||||
|
**NU lăsa UPS-ul pe baterie mai mult de 3 minute** - se va declanșa shutdown automat!
|
||||||
|
|
||||||
|
## 6. Troubleshooting
|
||||||
|
|
||||||
|
### 6.1. WinNUT nu se conectează
|
||||||
|
|
||||||
|
**Verificări:**
|
||||||
|
|
||||||
|
1. **Polling Interval = 0?**
|
||||||
|
- Schimbă la 15 secunde
|
||||||
|
- Click OK și așteaptă 10-20 secunde
|
||||||
|
|
||||||
|
2. **Firewall blochează portul 3493?**
|
||||||
|
```powershell
|
||||||
|
# Test port
|
||||||
|
Test-NetConnection -ComputerName 10.0.20.201 -Port 3493
|
||||||
|
```
|
||||||
|
|
||||||
|
3. **Server NUT nu rulează?**
|
||||||
|
- SSH pe pvemini:
|
||||||
|
```bash
|
||||||
|
systemctl status nut-server
|
||||||
|
ss -tulpn | grep 3493
|
||||||
|
```
|
||||||
|
|
||||||
|
4. **Date de autentificare greșite?**
|
||||||
|
- Verifică username/password din Options
|
||||||
|
- Compară cu `/etc/nut/upsd.users` de pe pvemini
|
||||||
|
|
||||||
|
5. **Nume UPS greșit?**
|
||||||
|
- Verifică că UPS Name = `nutdev1`
|
||||||
|
- Listează UPS-uri disponibile:
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "upsc -l"
|
||||||
|
```
|
||||||
|
|
||||||
|
### 6.2. WinNUT se conectează dar nu afișează date
|
||||||
|
|
||||||
|
1. **Restart WinNUT:**
|
||||||
|
- Click dreapta → Exit
|
||||||
|
- Pornește WinNUT din nou
|
||||||
|
|
||||||
|
2. **Verifică permisiuni:**
|
||||||
|
- Username `admin` trebuie să existe în `/etc/nut/upsd.users`
|
||||||
|
|
||||||
|
3. **Verifică logs pe server:**
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "journalctl -u nut-server -n 50"
|
||||||
|
```
|
||||||
|
|
||||||
|
### 6.3. Icon-ul lipsește din system tray
|
||||||
|
|
||||||
|
1. Deschide **Settings → Personalization → Taskbar**
|
||||||
|
2. Click pe **"Taskbar corner overflow"**
|
||||||
|
3. Activează **WinNUT**
|
||||||
|
|
||||||
|
### 6.4. Eroare "Connection refused"
|
||||||
|
|
||||||
|
**Pe pvemini, verifică:**
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Server ascultă pe IP-ul corect?
|
||||||
|
ss -tulpn | grep 3493
|
||||||
|
|
||||||
|
# Firewall permite trafic?
|
||||||
|
iptables -L INPUT -n | grep 3493
|
||||||
|
|
||||||
|
# Restart server
|
||||||
|
systemctl restart nut-server
|
||||||
|
```
|
||||||
|
|
||||||
|
## 7. Configurare Avansată
|
||||||
|
|
||||||
|
### 7.1. Monitorizare multiple UPS-uri
|
||||||
|
|
||||||
|
WinNUT poate monitoriza un singur UPS. Pentru multiple UPS-uri:
|
||||||
|
- Rulează multiple instanțe WinNUT (necesită build custom)
|
||||||
|
- Folosește alte tool-uri (NUT-Monitor, upsc via SSH)
|
||||||
|
|
||||||
|
### 7.2. Export date UPS
|
||||||
|
|
||||||
|
WinNUT nu are funcție de export built-in. Pentru logging:
|
||||||
|
|
||||||
|
**Opțiunea 1: PowerShell script**
|
||||||
|
```powershell
|
||||||
|
# Script simplu de logging UPS via SSH
|
||||||
|
while ($true) {
|
||||||
|
$status = ssh root@10.0.20.201 "upsc nutdev1 ups.status battery.charge input.voltage"
|
||||||
|
$timestamp = Get-Date -Format "yyyy-MM-dd HH:mm:ss"
|
||||||
|
"$timestamp - $status" | Out-File -Append C:\UPS-Logs\ups-log.txt
|
||||||
|
Start-Sleep -Seconds 60
|
||||||
|
}
|
||||||
|
```
|
||||||
|
|
||||||
|
**Opțiunea 2: Monitoring tools**
|
||||||
|
- Prometheus + NUT Exporter
|
||||||
|
- Grafana + InfluxDB
|
||||||
|
- Zabbix
|
||||||
|
|
||||||
|
### 7.3. Notificări personalizate
|
||||||
|
|
||||||
|
Pentru notificări Windows când UPS trece pe baterie:
|
||||||
|
|
||||||
|
**PowerShell monitoring script:**
|
||||||
|
```powershell
|
||||||
|
# Rulează continuu, verifică status UPS
|
||||||
|
$lastStatus = "OL"
|
||||||
|
while ($true) {
|
||||||
|
try {
|
||||||
|
$currentStatus = ssh root@10.0.20.201 "upsc nutdev1 ups.status"
|
||||||
|
|
||||||
|
if ($currentStatus -match "OB" -and $lastStatus -eq "OL") {
|
||||||
|
# Notificare Windows
|
||||||
|
[System.Windows.Forms.MessageBox]::Show(
|
||||||
|
"UPS a trecut pe baterie!",
|
||||||
|
"ALERT UPS",
|
||||||
|
[System.Windows.Forms.MessageBoxButtons]::OK,
|
||||||
|
[System.Windows.Forms.MessageBoxIcon]::Warning
|
||||||
|
)
|
||||||
|
}
|
||||||
|
|
||||||
|
$lastStatus = $currentStatus
|
||||||
|
} catch {
|
||||||
|
Write-Host "Error: $_"
|
||||||
|
}
|
||||||
|
|
||||||
|
Start-Sleep -Seconds 10
|
||||||
|
}
|
||||||
|
```
|
||||||
|
|
||||||
|
## 8. Alternative la WinNUT
|
||||||
|
|
||||||
|
Dacă WinNUT nu funcționează satisfăcător:
|
||||||
|
|
||||||
|
### 8.1. NUT-Monitor (Java)
|
||||||
|
|
||||||
|
- Cross-platform (Windows, Linux, macOS)
|
||||||
|
- Interfață mai modernă
|
||||||
|
- Download: https://github.com/networkupstools/nut/wiki/NUT-Monitor
|
||||||
|
|
||||||
|
### 8.2. upsc via SSH
|
||||||
|
|
||||||
|
Folosește direct comanda `upsc` prin SSH:
|
||||||
|
|
||||||
|
```powershell
|
||||||
|
# PowerShell - Status UPS
|
||||||
|
ssh root@10.0.20.201 "upsc nutdev1"
|
||||||
|
|
||||||
|
# Doar câmpuri specifice
|
||||||
|
ssh root@10.0.20.201 "upsc nutdev1 ups.status battery.charge input.voltage"
|
||||||
|
|
||||||
|
# Monitoring continuu
|
||||||
|
while ($true) {
|
||||||
|
Clear-Host
|
||||||
|
ssh root@10.0.20.201 "upsc nutdev1 ups.status battery.charge input.voltage"
|
||||||
|
Start-Sleep -Seconds 5
|
||||||
|
}
|
||||||
|
```
|
||||||
|
|
||||||
|
### 8.3. Web UI pe server
|
||||||
|
|
||||||
|
Instalează web UI pe pvemini:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Instalare NUT CGI scripts
|
||||||
|
apt install -y nut-cgi apache2
|
||||||
|
|
||||||
|
# Configurare
|
||||||
|
# Accesează: http://10.0.20.201/cgi-bin/nut/upsstats.cgi
|
||||||
|
```
|
||||||
|
|
||||||
|
## 9. Pornire Automată WinNUT
|
||||||
|
|
||||||
|
### 9.1. Via Task Scheduler
|
||||||
|
|
||||||
|
1. Deschide **Task Scheduler**
|
||||||
|
2. Create Task:
|
||||||
|
- **General:**
|
||||||
|
- Name: WinNUT Auto Start
|
||||||
|
- Run whether user is logged on or not
|
||||||
|
- **Triggers:**
|
||||||
|
- At startup
|
||||||
|
- **Actions:**
|
||||||
|
- Start a program: `C:\Program Files\WinNUT\WinNUT.exe`
|
||||||
|
- **Conditions:**
|
||||||
|
- Start only if network available
|
||||||
|
|
||||||
|
### 9.2. Via Startup Folder
|
||||||
|
|
||||||
|
1. `Win + R` → `shell:startup`
|
||||||
|
2. Crează shortcut către `WinNUT.exe`
|
||||||
|
|
||||||
|
## 10. Documentație și Suport
|
||||||
|
|
||||||
|
- **WinNUT GitHub:** https://github.com/gawindx/WinNUT-V2
|
||||||
|
- **NUT Documentation:** https://networkupstools.org/
|
||||||
|
- **Issues:** Raportează probleme pe GitHub Issues
|
||||||
|
|
||||||
|
## Rezumat Configurare Rapidă
|
||||||
|
|
||||||
|
```
|
||||||
|
NUT host: 10.0.20.201
|
||||||
|
NUT Port: 3493
|
||||||
|
UPS Name: nutdev1
|
||||||
|
Polling Interval: 15
|
||||||
|
Login: admin
|
||||||
|
Password: parola99
|
||||||
|
Re-establish conn: ✓ Checked
|
||||||
|
```
|
||||||
|
|
||||||
|
**Click OK → Așteaptă 10-20 secunde → Vezi date UPS!**
|
||||||
470
proxmox/ups/docs/UPS-MONTHLY-TEST.md
Normal file
470
proxmox/ups/docs/UPS-MONTHLY-TEST.md
Normal file
@@ -0,0 +1,470 @@
|
|||||||
|
# Test Lunar Automat Baterie UPS
|
||||||
|
|
||||||
|
## Despre
|
||||||
|
|
||||||
|
Script automat pentru testarea lunară a bateriei UPS care rulează pe data de 1 a fiecărei luni la ora 00:00. Testul verifică capacitatea reală a bateriei prin comutare pe baterie și monitorizare descărcare/recuperare.
|
||||||
|
|
||||||
|
## Funcționalitate
|
||||||
|
|
||||||
|
### Ce face scriptul:
|
||||||
|
|
||||||
|
1. **Verificare status UPS** înainte de test
|
||||||
|
- Battery charge, voltage
|
||||||
|
- Input/output voltage
|
||||||
|
- Load %
|
||||||
|
- Verifică că UPS este Online
|
||||||
|
|
||||||
|
2. **Rulare test baterie automat**
|
||||||
|
- Comandă: `upscmd nutdev1 test.battery.start.quick`
|
||||||
|
- UPS comută pe baterie pentru ~10 secunde
|
||||||
|
- Descarcă efectiv bateria pentru testare reală
|
||||||
|
|
||||||
|
3. **Monitorizare în timp real** (30 secunde)
|
||||||
|
- Status UPS
|
||||||
|
- Battery charge %
|
||||||
|
- Battery voltage
|
||||||
|
- Detectare anomalii
|
||||||
|
|
||||||
|
4. **Analiză rezultate**
|
||||||
|
- Calculează scăderea încărcării (%)
|
||||||
|
- Calculează scăderea tensiunii (V)
|
||||||
|
- Evaluează sănătatea bateriei
|
||||||
|
|
||||||
|
5. **Monitorizare recuperare** (5 minute)
|
||||||
|
- Urmărește reîncărcarea bateriei
|
||||||
|
- Calculează rata de recuperare
|
||||||
|
- Oprește când bateria > 95%
|
||||||
|
|
||||||
|
6. **Generare rapoarte**
|
||||||
|
- Raport HTML detaliat cu grafice
|
||||||
|
- Raport text pentru email
|
||||||
|
- Log detaliat în `/var/log/ups-monthly-test.log`
|
||||||
|
|
||||||
|
7. **Notificare email**
|
||||||
|
- Trimite raport prin sistemul de notificări Proxmox
|
||||||
|
- Include sănătatea bateriei în subject
|
||||||
|
- Rapoarte salvate în `/tmp/ups-test-YYYYMM/`
|
||||||
|
|
||||||
|
## Evaluare Sănătate Baterie
|
||||||
|
|
||||||
|
Scriptul evaluează sănătatea bateriei bazat pe scăderea încărcării în timpul testului:
|
||||||
|
|
||||||
|
| Scădere Încărcare | Sănătate | Status | Acțiune Necesară |
|
||||||
|
|-------------------|----------|--------|------------------|
|
||||||
|
| < 10% | **EXCELLENT** | ✅ Verde | Nicio acțiune necesară |
|
||||||
|
| 10-30% | **GOOD** | ✅ Verde | Continuă monitorizarea |
|
||||||
|
| 30-50% | **FAIR** | ⚠️ Galben | Planifică înlocuire în 3-6 luni |
|
||||||
|
| > 50% | **POOR** | 🔴 Roșu | **URGENT: Înlocuiește bateria!** |
|
||||||
|
|
||||||
|
### Exemple de rezultate reale:
|
||||||
|
|
||||||
|
**Test 1 (2025-10-06 20:45):**
|
||||||
|
- Scădere încărcare: 0% (charge reporting delay)
|
||||||
|
- Scădere tensiune: 1.64V (27.88V → 26.24V)
|
||||||
|
- Evaluare: **EXCELLENT**
|
||||||
|
- Recuperare: 30 secunde la 100%
|
||||||
|
|
||||||
|
**Notă:** UPS-ul raportează uneori încărcarea cu întârziere. Scăderea tensiunii este un indicator mai precis al capacității bateriei.
|
||||||
|
|
||||||
|
## Instalare
|
||||||
|
|
||||||
|
### 1. Copiere script pe server
|
||||||
|
|
||||||
|
```bash
|
||||||
|
scp scripts/ups-monthly-test.sh root@10.0.20.201:/opt/scripts/
|
||||||
|
ssh root@10.0.20.201 "chmod +x /opt/scripts/ups-monthly-test.sh"
|
||||||
|
```
|
||||||
|
|
||||||
|
### 2. Configurare cron
|
||||||
|
|
||||||
|
Script-ul se adaugă automat în cron la instalare, dar poți verifica:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "crontab -l | grep ups-monthly-test"
|
||||||
|
```
|
||||||
|
|
||||||
|
Ar trebui să vezi:
|
||||||
|
```
|
||||||
|
# UPS Monthly Battery Test - Rulează pe 1 ale lunii la 00:00
|
||||||
|
0 0 1 * * /opt/scripts/ups-monthly-test.sh
|
||||||
|
```
|
||||||
|
|
||||||
|
### 3. Test manual (recomandat înainte de prima rulare lunară)
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "/opt/scripts/ups-monthly-test.sh"
|
||||||
|
```
|
||||||
|
|
||||||
|
**ATENȚIE:** Testul va comuta UPS-ul pe baterie pentru ~10 secunde!
|
||||||
|
|
||||||
|
## Configurare
|
||||||
|
|
||||||
|
### Parametri editabili în script:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
UPS_NAME="nutdev1" # Numele UPS-ului din NUT
|
||||||
|
UPS_USER="admin" # Username pentru comenzi NUT
|
||||||
|
UPS_PASS="parola99" # Parola pentru comenzi NUT
|
||||||
|
MAIL_TO="root@pam" # Destinatar email rapoarte
|
||||||
|
```
|
||||||
|
|
||||||
|
### Personalizare cron:
|
||||||
|
|
||||||
|
Pentru a schimba data/ora de rulare, editează cron:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201
|
||||||
|
crontab -e
|
||||||
|
```
|
||||||
|
|
||||||
|
Exemple:
|
||||||
|
```bash
|
||||||
|
# Rulează pe 1 ale lunii la 02:00 (noapte)
|
||||||
|
0 2 1 * * /opt/scripts/ups-monthly-test.sh
|
||||||
|
|
||||||
|
# Rulează în fiecare Duminică la 00:00 (săptămânal)
|
||||||
|
0 0 * * 0 /opt/scripts/ups-monthly-test.sh
|
||||||
|
|
||||||
|
# Rulează pe 15 ale lunii la 00:00 (mijloc de lună)
|
||||||
|
0 0 15 * * /opt/scripts/ups-monthly-test.sh
|
||||||
|
```
|
||||||
|
|
||||||
|
## Rapoarte Generate
|
||||||
|
|
||||||
|
### 1. Raport HTML
|
||||||
|
|
||||||
|
**Locație:** `/tmp/ups-test-YYYYMM/ups-test-report.html`
|
||||||
|
|
||||||
|
Conține:
|
||||||
|
- Header cu data, UPS, nod
|
||||||
|
- Status sănătate baterie (color-coded)
|
||||||
|
- Metrici în grid layout:
|
||||||
|
- Încărcare înainte/după
|
||||||
|
- Tensiune înainte/după
|
||||||
|
- Scădere încărcare
|
||||||
|
- Recuperare în 5 min
|
||||||
|
- Tabel detalii tehnice
|
||||||
|
- Recomandări bazate pe sănătate
|
||||||
|
- Footer cu timestamp și paths
|
||||||
|
|
||||||
|
### 2. Raport Text
|
||||||
|
|
||||||
|
**Locație:** `/tmp/ups-test-YYYYMM/ups-test-report.txt`
|
||||||
|
|
||||||
|
Versiune text simplă pentru email.
|
||||||
|
|
||||||
|
### 3. Log Detaliat
|
||||||
|
|
||||||
|
**Locație:** `/var/log/ups-monthly-test.log`
|
||||||
|
|
||||||
|
Log complet cu toate măsurătorile:
|
||||||
|
- Timestamp pentru fiecare pas
|
||||||
|
- Status UPS în timp real
|
||||||
|
- Toate valorile măsurate
|
||||||
|
- Erori sau warnings
|
||||||
|
|
||||||
|
**Păstrare:** Log-ul este append-only, conține istoric complet al tuturor testelor.
|
||||||
|
|
||||||
|
## Logs și Monitorizare
|
||||||
|
|
||||||
|
### Vizualizare log în timp real:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "tail -f /var/log/ups-monthly-test.log"
|
||||||
|
```
|
||||||
|
|
||||||
|
### Verificare ultimul test:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "tail -50 /var/log/ups-monthly-test.log"
|
||||||
|
```
|
||||||
|
|
||||||
|
### Căutare teste anterioare:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Caută toate testele din 2025
|
||||||
|
ssh root@10.0.20.201 "grep 'UPS MONTHLY BATTERY TEST - START' /var/log/ups-monthly-test.log | grep 2025"
|
||||||
|
|
||||||
|
# Vezi rezultatul ultimului test
|
||||||
|
ssh root@10.0.20.201 "grep 'Sănătate baterie:' /var/log/ups-monthly-test.log | tail -1"
|
||||||
|
```
|
||||||
|
|
||||||
|
### Verificare cron execution:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică că cron a rulat scriptul
|
||||||
|
ssh root@10.0.20.201 "grep ups-monthly-test /var/log/syslog"
|
||||||
|
```
|
||||||
|
|
||||||
|
## Email Notifications
|
||||||
|
|
||||||
|
### Configurare sistem de mail
|
||||||
|
|
||||||
|
Scriptul încearcă să trimită email prin:
|
||||||
|
1. **mail command** (recomandat)
|
||||||
|
2. **logger** (fallback - doar în syslog)
|
||||||
|
|
||||||
|
#### Instalare mail command (dacă nu există):
|
||||||
|
|
||||||
|
```bash
|
||||||
|
ssh root@10.0.20.201 "apt update && apt install -y mailutils"
|
||||||
|
```
|
||||||
|
|
||||||
|
#### Configurare SMTP pentru Proxmox:
|
||||||
|
|
||||||
|
Editează `/etc/postfix/main.cf`:
|
||||||
|
```bash
|
||||||
|
relayhost = smtp.gmail.com:587
|
||||||
|
smtp_sasl_auth_enable = yes
|
||||||
|
smtp_sasl_password_maps = hash:/etc/postfix/sasl_passwd
|
||||||
|
smtp_sasl_security_options = noanonymous
|
||||||
|
smtp_tls_security_level = encrypt
|
||||||
|
```
|
||||||
|
|
||||||
|
Creează `/etc/postfix/sasl_passwd`:
|
||||||
|
```
|
||||||
|
smtp.gmail.com:587 your-email@gmail.com:your-app-password
|
||||||
|
```
|
||||||
|
|
||||||
|
Apoi:
|
||||||
|
```bash
|
||||||
|
postmap /etc/postfix/sasl_passwd
|
||||||
|
chmod 600 /etc/postfix/sasl_passwd*
|
||||||
|
systemctl restart postfix
|
||||||
|
```
|
||||||
|
|
||||||
|
#### Test email:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
echo "Test email from UPS monitoring" | mail -s "Test" root@pam
|
||||||
|
```
|
||||||
|
|
||||||
|
### Verificare email trimis:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică mail queue
|
||||||
|
ssh root@10.0.20.201 "mailq"
|
||||||
|
|
||||||
|
# Verifică mail logs
|
||||||
|
ssh root@10.0.20.201 "grep 'UPS' /var/log/mail.log"
|
||||||
|
```
|
||||||
|
|
||||||
|
## Troubleshooting
|
||||||
|
|
||||||
|
### Testul nu pornește
|
||||||
|
|
||||||
|
**Verificare:**
|
||||||
|
```bash
|
||||||
|
# UPS online?
|
||||||
|
upsc nutdev1 ups.status
|
||||||
|
|
||||||
|
# Comenzi disponibile?
|
||||||
|
upscmd -l nutdev1 | grep battery
|
||||||
|
|
||||||
|
# Autentificare corectă?
|
||||||
|
upscmd -u admin -p parola99 nutdev1 test.battery.start.quick
|
||||||
|
```
|
||||||
|
|
||||||
|
### Bateria nu se descarcă în test
|
||||||
|
|
||||||
|
**Cauze posibile:**
|
||||||
|
- UPS-ul nu suportă test real (unele modele low-end)
|
||||||
|
- Test prea scurt pentru a fi detectat
|
||||||
|
- Baterie foarte sănătoasă (scădere < 1%)
|
||||||
|
|
||||||
|
**Verificare:**
|
||||||
|
```bash
|
||||||
|
# Monitorizează tensiune în loc de charge
|
||||||
|
watch -n 1 'upsc nutdev1 battery.voltage'
|
||||||
|
|
||||||
|
# Apoi rulează test manual și observă scăderea
|
||||||
|
upscmd -u admin -p parola99 nutdev1 test.battery.start.quick
|
||||||
|
```
|
||||||
|
|
||||||
|
### Email nu ajunge
|
||||||
|
|
||||||
|
**Verificări:**
|
||||||
|
```bash
|
||||||
|
# Mail command instalat?
|
||||||
|
which mail
|
||||||
|
|
||||||
|
# Postfix rulează?
|
||||||
|
systemctl status postfix
|
||||||
|
|
||||||
|
# Verifică logs
|
||||||
|
tail -50 /var/log/mail.log
|
||||||
|
|
||||||
|
# Test manual
|
||||||
|
echo "Test" | mail -s "Test Subject" root@pam
|
||||||
|
```
|
||||||
|
|
||||||
|
### Script blochează sau timeout
|
||||||
|
|
||||||
|
**Cauze:**
|
||||||
|
- Testul baterie durează prea mult
|
||||||
|
- UPS nu răspunde
|
||||||
|
- Probleme rețea
|
||||||
|
|
||||||
|
**Soluție:**
|
||||||
|
Editează scriptul și reduce timeout-urile:
|
||||||
|
```bash
|
||||||
|
# Reduce monitorizare de la 15 la 5 iterații
|
||||||
|
for i in {1..5}; do
|
||||||
|
```
|
||||||
|
|
||||||
|
## Întreținere
|
||||||
|
|
||||||
|
### Lunar (După Rulare Automată)
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Verifică că testul a rulat
|
||||||
|
ssh root@10.0.20.201 "tail -100 /var/log/ups-monthly-test.log | grep 'COMPLETE'"
|
||||||
|
|
||||||
|
# Vezi rezultatul
|
||||||
|
ssh root@10.0.20.201 "grep 'Sănătate baterie' /var/log/ups-monthly-test.log | tail -1"
|
||||||
|
|
||||||
|
# Verifică raportul HTML
|
||||||
|
ssh root@10.0.20.201 "ls -lh /tmp/ups-test-*/ups-test-report.html"
|
||||||
|
```
|
||||||
|
|
||||||
|
### Anual
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Cleanup rapoarte vechi (> 12 luni)
|
||||||
|
ssh root@10.0.20.201 "find /tmp/ups-test-* -type d -mtime +365 -exec rm -rf {} +"
|
||||||
|
|
||||||
|
# Rotare log dacă devine prea mare (> 100MB)
|
||||||
|
ssh root@10.0.20.201 "
|
||||||
|
if [ \$(stat -f%z /var/log/ups-monthly-test.log) -gt 104857600 ]; then
|
||||||
|
mv /var/log/ups-monthly-test.log /var/log/ups-monthly-test.log.old
|
||||||
|
gzip /var/log/ups-monthly-test.log.old
|
||||||
|
fi
|
||||||
|
"
|
||||||
|
```
|
||||||
|
|
||||||
|
### La Înlocuire Baterie
|
||||||
|
|
||||||
|
După înlocuirea bateriei UPS:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# Rulează test manual pentru baseline
|
||||||
|
ssh root@10.0.20.201 "/opt/scripts/ups-monthly-test.sh"
|
||||||
|
|
||||||
|
# Verifică că rezultatul este EXCELLENT
|
||||||
|
ssh root@10.0.20.201 "tail -20 /var/log/ups-monthly-test.log"
|
||||||
|
|
||||||
|
# Notează data înlocuirii în log
|
||||||
|
ssh root@10.0.20.201 "echo '[$(date)] Baterie UPS înlocuită - baseline test executat' >> /var/log/ups-monthly-test.log"
|
||||||
|
```
|
||||||
|
|
||||||
|
## Interpretare Rezultate
|
||||||
|
|
||||||
|
### Exemplu rezultat bun:
|
||||||
|
|
||||||
|
```
|
||||||
|
Sănătate baterie: EXCELLENT
|
||||||
|
Scădere încărcare: 5%
|
||||||
|
Scădere tensiune: 1.64V
|
||||||
|
Recuperare: 5% în 30 secunde
|
||||||
|
```
|
||||||
|
**Interpretare:** Baterie în stare excelentă, poate susține sarcina, se reîncarcă rapid.
|
||||||
|
|
||||||
|
### Exemplu rezultat acceptabil:
|
||||||
|
|
||||||
|
```
|
||||||
|
Sănătate baterie: FAIR
|
||||||
|
Scădere încărcare: 35%
|
||||||
|
Scădere tensiune: 4.2V
|
||||||
|
Recuperare: 15% în 120 secunde
|
||||||
|
```
|
||||||
|
**Interpretare:** Baterie uzată, planifică înlocuire în 3-6 luni.
|
||||||
|
|
||||||
|
### Exemplu rezultat critic:
|
||||||
|
|
||||||
|
```
|
||||||
|
Sănătate baterie: POOR
|
||||||
|
Scădere încărcare: 65%
|
||||||
|
Scădere tensiune: 8.5V
|
||||||
|
Recuperare: 25% în 300 secunde
|
||||||
|
```
|
||||||
|
**Interpretare:** **URGENT!** Baterie critică, înlocuiește imediat! Risc mare de shutdown neplanificat.
|
||||||
|
|
||||||
|
## Recomandări Baterie
|
||||||
|
|
||||||
|
### Când să înlocuiești bateria:
|
||||||
|
|
||||||
|
| Indicator | Bun | Acceptabil | Critic |
|
||||||
|
|-----------|-----|------------|--------|
|
||||||
|
| **Vârstă baterie** | < 2 ani | 2-4 ani | > 4 ani |
|
||||||
|
| **Scădere încărcare** | < 10% | 10-50% | > 50% |
|
||||||
|
| **Scădere tensiune** | < 2V | 2-5V | > 5V |
|
||||||
|
| **Timp recuperare** | < 1 min | 1-5 min | > 5 min |
|
||||||
|
| **Teste failed** | 0 | 1-2 | > 3 |
|
||||||
|
|
||||||
|
### Factori care afectează durata de viață:
|
||||||
|
|
||||||
|
- **Temperatură:** Ideal 20-25°C (fiecare +10°C reduce durata cu 50%)
|
||||||
|
- **Cicluri descărcare:** < 20 cicluri/an = bun
|
||||||
|
- **Profunzime descărcare:** Descărcări până la 50% = OK, sub 20% = deteriorare
|
||||||
|
- **Calitate baterie:** Baterii branded (APC, Eaton) vs. generice
|
||||||
|
|
||||||
|
## Automatizare Avansată
|
||||||
|
|
||||||
|
### Alertare automată când bateria devine POOR:
|
||||||
|
|
||||||
|
Adaugă în script (după evaluarea sănătății):
|
||||||
|
|
||||||
|
```bash
|
||||||
|
if [ "$BATTERY_HEALTH" == "POOR" ]; then
|
||||||
|
# Trimite alert urgent
|
||||||
|
echo "URGENT: Bateria UPS necesită înlocuire!" | \
|
||||||
|
mail -s "🔴 ALERT UPS: Baterie CRITICĂ!" admin@company.com
|
||||||
|
|
||||||
|
# Notificare SMS (dacă ai configurat)
|
||||||
|
curl -X POST "https://api.service.com/sms" \
|
||||||
|
-d "to=+40xxxxxxxxx&message=ALERT: Baterie UPS critica!"
|
||||||
|
fi
|
||||||
|
```
|
||||||
|
|
||||||
|
### Integrare cu Prometheus/Grafana:
|
||||||
|
|
||||||
|
Exportă metrici pentru monitorizare long-term:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
# La final de script, exportă metrici
|
||||||
|
cat >> /var/lib/node_exporter/textfile_collector/ups_battery.prom << EOF
|
||||||
|
# HELP ups_battery_health Battery health score (0-100)
|
||||||
|
# TYPE ups_battery_health gauge
|
||||||
|
ups_battery_health{ups="nutdev1"} $(( 100 - CHARGE_DROP ))
|
||||||
|
|
||||||
|
# HELP ups_battery_charge_drop Battery charge drop during test
|
||||||
|
# TYPE ups_battery_charge_drop gauge
|
||||||
|
ups_battery_charge_drop{ups="nutdev1"} $CHARGE_DROP
|
||||||
|
|
||||||
|
# HELP ups_battery_test_timestamp Last battery test timestamp
|
||||||
|
# TYPE ups_battery_test_timestamp gauge
|
||||||
|
ups_battery_test_timestamp{ups="nutdev1"} $(date +%s)
|
||||||
|
EOF
|
||||||
|
```
|
||||||
|
|
||||||
|
## Referințe
|
||||||
|
|
||||||
|
- **NUT Commands:** https://networkupstools.org/docs/user-manual.chunked/ar01s07.html
|
||||||
|
- **Battery Testing Best Practices:** https://www.apc.com/us/en/faqs/FAQ000267818/
|
||||||
|
- **Proxmox Notifications:** https://pve.proxmox.com/wiki/Notifications
|
||||||
|
|
||||||
|
## Istoric Versiuni
|
||||||
|
|
||||||
|
- **v1.0** (2025-10-06)
|
||||||
|
- Release inițial
|
||||||
|
- Test automat baterie cu `test.battery.start.quick`
|
||||||
|
- Rapoarte HTML și text
|
||||||
|
- Email notifications
|
||||||
|
- Cron lunar (1 ale lunii)
|
||||||
|
- Evaluare sănătate baterie (4 nivele)
|
||||||
|
- Monitorizare recuperare 5 minute
|
||||||
|
|
||||||
|
---
|
||||||
|
|
||||||
|
**Autor:** Claude Code
|
||||||
|
**Ultima actualizare:** 2025-10-06
|
||||||
237
proxmox/ups/docs/UPS-SHUTDOWN-README.md
Normal file
237
proxmox/ups/docs/UPS-SHUTDOWN-README.md
Normal file
@@ -0,0 +1,237 @@
|
|||||||
|
# Documentație Sistem UPS Shutdown Orchestrat
|
||||||
|
|
||||||
|
## Configurare Completă
|
||||||
|
|
||||||
|
### Hardware
|
||||||
|
- **UPS:** INNO TECH USB to Serial (ID: 0665:5161)
|
||||||
|
- **Conectat la:** pvemini (10.0.20.201) - via USB
|
||||||
|
- **Cluster Proxmox:**
|
||||||
|
- pvemini (10.0.20.201) - PRIMARY (are UPS-ul conectat)
|
||||||
|
- pve1 (10.0.20.200) - SECONDARY
|
||||||
|
- pve2 (10.0.20.202) - SECONDARY
|
||||||
|
|
||||||
|
### Software
|
||||||
|
- **NUT (Network UPS Tools)** versiunea 2.8.0
|
||||||
|
- **WinNUT** pe VM 201 (Windows 11) pentru monitorizare vizuală
|
||||||
|
|
||||||
|
### Fișiere de Configurare
|
||||||
|
|
||||||
|
#### 1. /etc/nut/ups.conf
|
||||||
|
Configurează driver-ul pentru UPS:
|
||||||
|
```
|
||||||
|
[nutdev1]
|
||||||
|
driver = nutdrv_qx
|
||||||
|
port = auto
|
||||||
|
vendorid = 0665
|
||||||
|
productid = 5161
|
||||||
|
subdriver = cypress
|
||||||
|
desc = "UPS Cypress via USB"
|
||||||
|
```
|
||||||
|
|
||||||
|
#### 2. /etc/nut/upsd.conf
|
||||||
|
Server NUT - ascultă pe localhost și rețea:
|
||||||
|
```
|
||||||
|
LISTEN 127.0.0.1 3493
|
||||||
|
LISTEN 10.0.20.201 3493
|
||||||
|
```
|
||||||
|
|
||||||
|
#### 3. /etc/nut/upsd.users
|
||||||
|
Utilizatori autorizați:
|
||||||
|
```
|
||||||
|
[admin]
|
||||||
|
password = parola99
|
||||||
|
actions = SET
|
||||||
|
instcmds = ALL
|
||||||
|
upsmon master
|
||||||
|
```
|
||||||
|
|
||||||
|
#### 4. /etc/nut/upsmon.conf
|
||||||
|
Monitor local:
|
||||||
|
```
|
||||||
|
MONITOR nutdev1@localhost 1 admin parola99 master
|
||||||
|
NOTIFYCMD /usr/sbin/upssched
|
||||||
|
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
|
||||||
|
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
|
||||||
|
```
|
||||||
|
|
||||||
|
#### 5. /etc/nut/upssched.conf
|
||||||
|
Scheduler pentru evenimente:
|
||||||
|
- **ONBATT:** Așteaptă 180 secunde (3 minute) înainte de shutdown
|
||||||
|
- **LOWBATT:** Shutdown imediat
|
||||||
|
- **ONLINE:** Anulează toate timer-ele
|
||||||
|
|
||||||
|
### Scripturi Create
|
||||||
|
|
||||||
|
#### 1. /usr/local/bin/ups-shutdown-cluster.sh
|
||||||
|
**Script principal de shutdown orchestrat**
|
||||||
|
|
||||||
|
Ordinea de operații:
|
||||||
|
1. Verifică status UPS (trebuie OB sau LB)
|
||||||
|
2. Oprește toate VM-urile de pe toate nodurile (paralel)
|
||||||
|
3. Așteaptă 90 secunde
|
||||||
|
4. Shutdown pve1 și pve2 (secundare)
|
||||||
|
5. Așteaptă 30 secunde
|
||||||
|
6. Shutdown pvemini (primary - ultimul)
|
||||||
|
|
||||||
|
Logare: `/var/log/ups-shutdown.log`
|
||||||
|
|
||||||
|
#### 2. /usr/local/bin/ups-shutdown-test.sh
|
||||||
|
**Script de test (DRY RUN) - NU oprește nimic**
|
||||||
|
|
||||||
|
Folosește-l pentru a testa:
|
||||||
|
```bash
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
tail -f /var/log/ups-shutdown-test.log
|
||||||
|
```
|
||||||
|
|
||||||
|
#### 3. /usr/local/bin/upssched-cmd
|
||||||
|
**Handler pentru evenimente UPS**
|
||||||
|
|
||||||
|
Apelat automat de upssched când:
|
||||||
|
- UPS pe baterie 3 minute → lansează shutdown orchestrat
|
||||||
|
- Baterie scăzută → shutdown imediat
|
||||||
|
- Pierdere comunicație → doar logging
|
||||||
|
|
||||||
|
Logare: `/var/log/ups-events.log`
|
||||||
|
|
||||||
|
## Testare și Verificare
|
||||||
|
|
||||||
|
### Verificare Status UPS
|
||||||
|
```bash
|
||||||
|
# Status general
|
||||||
|
upsc nutdev1
|
||||||
|
|
||||||
|
# Doar status
|
||||||
|
upsc nutdev1 ups.status
|
||||||
|
|
||||||
|
# Baterie
|
||||||
|
upsc nutdev1 battery.charge
|
||||||
|
|
||||||
|
# Tensiuni
|
||||||
|
upsc nutdev1 input.voltage output.voltage
|
||||||
|
```
|
||||||
|
|
||||||
|
### Verificare Servicii
|
||||||
|
```bash
|
||||||
|
systemctl status nut-server
|
||||||
|
systemctl status nut-monitor
|
||||||
|
journalctl -u nut-server -f
|
||||||
|
journalctl -u nut-monitor -f
|
||||||
|
```
|
||||||
|
|
||||||
|
### Test Manual Shutdown (DRY RUN)
|
||||||
|
```bash
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
```
|
||||||
|
|
||||||
|
### Test Simulare UPS pe Baterie
|
||||||
|
**⚠️ ATENȚIE: Acest test va iniția shutdown real dacă îl lași 3 minute!**
|
||||||
|
```bash
|
||||||
|
# Deconectează fizic UPS-ul de la priză pentru 30 secunde
|
||||||
|
# Monitorizează logs:
|
||||||
|
tail -f /var/log/ups-events.log
|
||||||
|
|
||||||
|
# Reconectează înainte de 3 minute pentru a anula shutdown-ul
|
||||||
|
```
|
||||||
|
|
||||||
|
## Monitorizare din WinNUT (VM 201)
|
||||||
|
|
||||||
|
### Conexiune
|
||||||
|
- **Server:** 10.0.20.201
|
||||||
|
- **Port:** 3493
|
||||||
|
- **UPS Name:** nutdev1
|
||||||
|
- **Username:** admin
|
||||||
|
- **Password:** parola99
|
||||||
|
- **Polling Interval:** 15 secunde
|
||||||
|
|
||||||
|
### Ce Vezi în WinNUT
|
||||||
|
- Input/Output Voltage
|
||||||
|
- Frequency
|
||||||
|
- Battery Charge (%)
|
||||||
|
- Battery Voltage
|
||||||
|
- UPS Load (%)
|
||||||
|
- UPS Status (Online/On Battery/Low Battery)
|
||||||
|
|
||||||
|
## Scenarii de Funcționare
|
||||||
|
|
||||||
|
### Scenario 1: Întrerupere Scurtă (< 3 minute)
|
||||||
|
1. Curent se întrerupe → UPS trece pe baterie
|
||||||
|
2. Timer de 180 secunde pornește
|
||||||
|
3. Curent revine → Timer anulat
|
||||||
|
4. **Rezultat:** Niciun sistem nu se oprește
|
||||||
|
|
||||||
|
### Scenario 2: Întrerupere Lungă (> 3 minute)
|
||||||
|
1. Curent se întrerupe → UPS trece pe baterie
|
||||||
|
2. Timer 180 secunde expiră
|
||||||
|
3. Scriptu de shutdown pornește:
|
||||||
|
- VM-uri se opresc pe toate nodurile
|
||||||
|
- După 90s: pve1, pve2 se opresc
|
||||||
|
- După încă 30s: pvemini se oprește
|
||||||
|
4. **Rezultat:** Shutdown orchestrat complet
|
||||||
|
|
||||||
|
### Scenario 3: Baterie Scăzută Imediată
|
||||||
|
1. UPS raportează LOWBATT
|
||||||
|
2. Shutdown **IMEDIAT** (fără timer)
|
||||||
|
3. Același flux de shutdown orchestrat
|
||||||
|
4. **Rezultat:** Shutdown rapid pentru protecție
|
||||||
|
|
||||||
|
## Loguri și Troubleshooting
|
||||||
|
|
||||||
|
### Fișiere de Log
|
||||||
|
```bash
|
||||||
|
/var/log/ups-shutdown.log # Shutdown orchestrat real
|
||||||
|
/var/log/ups-shutdown-test.log # Test dry-run
|
||||||
|
/var/log/ups-events.log # Evenimente UPS (upssched)
|
||||||
|
journalctl -u nut-server # Server NUT
|
||||||
|
journalctl -u nut-monitor # Monitor NUT
|
||||||
|
```
|
||||||
|
|
||||||
|
### Comenzi Utile
|
||||||
|
```bash
|
||||||
|
# Liste conexiuni active la NUT
|
||||||
|
ss -tnp | grep :3493
|
||||||
|
|
||||||
|
# Test conectivitate de pe alt nod
|
||||||
|
ssh root@10.0.20.200 'upsc nutdev1@10.0.20.201'
|
||||||
|
|
||||||
|
# Restart servicii
|
||||||
|
systemctl restart nut-server nut-monitor
|
||||||
|
```
|
||||||
|
|
||||||
|
## Întreținere
|
||||||
|
|
||||||
|
### Verificare Săptămânală
|
||||||
|
```bash
|
||||||
|
# Status UPS
|
||||||
|
upsc nutdev1 ups.status battery.charge
|
||||||
|
|
||||||
|
# Test dry-run
|
||||||
|
/usr/local/bin/ups-shutdown-test.sh
|
||||||
|
|
||||||
|
# Verificare logs
|
||||||
|
tail -20 /var/log/ups-events.log
|
||||||
|
```
|
||||||
|
|
||||||
|
### Verificare Lunară
|
||||||
|
- Test fizic: deconectează UPS 30 secunde
|
||||||
|
- Verifică că WinNUT detectează schimbarea
|
||||||
|
- Verifică că logs arată evenimentul
|
||||||
|
- Reconectează înainte de 3 minute
|
||||||
|
|
||||||
|
## ⚠️ IMPORTANT
|
||||||
|
|
||||||
|
1. **Nu modifica** timpul de 3 minute fără consultare - trebuie să fie suficient pentru:
|
||||||
|
- VM-uri să se oprească graceful
|
||||||
|
- Noduri secundare să se închidă
|
||||||
|
- pvemini să rămână ultimul funcțional
|
||||||
|
|
||||||
|
2. **Testează periodic** scriptul dry-run pentru a verifica că SSH funcționează între noduri
|
||||||
|
|
||||||
|
3. **Monitorizează** statusul bateriei UPS - înlocuiește bateria când charge devine sub 80%
|
||||||
|
|
||||||
|
4. **WinNUT** este doar pentru monitorizare - shutdown-ul este automat de pe Proxmox
|
||||||
|
|
||||||
|
## Contact și Suport
|
||||||
|
- Documentație NUT: https://networkupstools.org/
|
||||||
|
- Script creat: 2025-10-06
|
||||||
|
- Ultima modificare: 2025-10-06
|
||||||
435
proxmox/ups/scripts/ups-monthly-test.sh
Normal file
435
proxmox/ups/scripts/ups-monthly-test.sh
Normal file
@@ -0,0 +1,435 @@
|
|||||||
|
#!/bin/bash
|
||||||
|
#
|
||||||
|
# Script de test lunar automat baterie UPS
|
||||||
|
# Rulează pe 1 ale fiecărei luni la 00:00
|
||||||
|
# Trimite raport prin notificările Proxmox (PVE::Notify)
|
||||||
|
#
|
||||||
|
# IMPORTANT: Timing-ul de citire este CRITIC!
|
||||||
|
# - Battery.charge scade DOAR între 10-40 secunde după pornirea testului
|
||||||
|
# - UPS actualizează valorile cu delay de 5-10 secunde
|
||||||
|
#
|
||||||
|
# Creat: 2025-10-06
|
||||||
|
# Autor: Claude Code
|
||||||
|
|
||||||
|
LOGFILE="/var/log/ups-monthly-test.log"
|
||||||
|
UPS_NAME="nutdev1"
|
||||||
|
UPS_USER="admin"
|
||||||
|
UPS_PASS="parola99"
|
||||||
|
TEMPLATE_DIR="/etc/pve/notification-templates/default"
|
||||||
|
START_TIME=$(date +%s)
|
||||||
|
HOSTNAME=$(hostname)
|
||||||
|
FQDN=$(hostname -f)
|
||||||
|
|
||||||
|
# Funcție logging
|
||||||
|
log() {
|
||||||
|
echo "[$(date '+%Y-%m-%d %H:%M:%S')] $1" | tee -a $LOGFILE
|
||||||
|
}
|
||||||
|
|
||||||
|
# Funcție pentru crearea template-urilor de notificare
|
||||||
|
create_templates() {
|
||||||
|
mkdir -p $TEMPLATE_DIR
|
||||||
|
|
||||||
|
# Template: Subject
|
||||||
|
cat > "$TEMPLATE_DIR/ups-battery-test-subject.txt.hbs" << 'EOFTEMPLATE'
|
||||||
|
[{{ hostname }}] UPS Battery Test - {{ health_status }}
|
||||||
|
EOFTEMPLATE
|
||||||
|
|
||||||
|
# Template: Body Text
|
||||||
|
cat > "$TEMPLATE_DIR/ups-battery-test-body.txt.hbs" << 'EOFTEMPLATE'
|
||||||
|
========================================
|
||||||
|
UPS MONTHLY BATTERY TEST REPORT
|
||||||
|
========================================
|
||||||
|
|
||||||
|
Hostname: {{ hostname }}
|
||||||
|
Date: {{ test_date }}
|
||||||
|
UPS: {{ ups_name }}
|
||||||
|
|
||||||
|
BATTERY HEALTH: {{ health_status }}
|
||||||
|
{{ health_emoji }} {{ health_description }}
|
||||||
|
|
||||||
|
TEST RESULTS:
|
||||||
|
-------------
|
||||||
|
Battery Charge Drop: {{ charge_drop }}%
|
||||||
|
Battery Voltage Drop: {{ voltage_drop }}V
|
||||||
|
Minimum Charge Reached: {{ min_charge }}%
|
||||||
|
Minimum Voltage: {{ min_voltage }}V
|
||||||
|
Recovery Time: {{ recovery_time }}s
|
||||||
|
|
||||||
|
BEFORE TEST:
|
||||||
|
- Battery Charge: {{ before_charge }}%
|
||||||
|
- Battery Voltage: {{ before_voltage }}V
|
||||||
|
- UPS Load: {{ before_load }}%
|
||||||
|
|
||||||
|
AFTER TEST ({{ test_duration }}s):
|
||||||
|
- Battery Charge: {{ after_charge }}%
|
||||||
|
- Battery Voltage: {{ after_voltage }}V
|
||||||
|
- UPS Load: {{ after_load }}%
|
||||||
|
|
||||||
|
RECOMMENDATIONS:
|
||||||
|
{{ recommendations }}
|
||||||
|
|
||||||
|
========================================
|
||||||
|
Script: /opt/scripts/ups-monthly-test.sh
|
||||||
|
Log: /var/log/ups-monthly-test.log
|
||||||
|
========================================
|
||||||
|
EOFTEMPLATE
|
||||||
|
|
||||||
|
# Template: Body HTML
|
||||||
|
cat > "$TEMPLATE_DIR/ups-battery-test-body.html.hbs" << 'EOFTEMPLATE'
|
||||||
|
<!DOCTYPE html>
|
||||||
|
<html>
|
||||||
|
<head>
|
||||||
|
<meta charset="UTF-8">
|
||||||
|
<style>
|
||||||
|
body { font-family: Arial, sans-serif; margin: 0; padding: 20px; background-color: #f5f5f5; }
|
||||||
|
.container { max-width: 800px; margin: 0 auto; background: white; padding: 30px; border-radius: 8px; box-shadow: 0 2px 8px rgba(0,0,0,0.1); }
|
||||||
|
h1 { color: #2c3e50; border-bottom: 3px solid #3498db; padding-bottom: 15px; margin-top: 0; }
|
||||||
|
.status-badge { display: inline-block; padding: 10px 20px; border-radius: 5px; font-weight: bold; font-size: 18px; margin: 15px 0; }
|
||||||
|
.status-excellent { background-color: #d4edda; color: #155724; border: 2px solid #28a745; }
|
||||||
|
.status-good { background-color: #d1ecf1; color: #0c5460; border: 2px solid #17a2b8; }
|
||||||
|
.status-fair { background-color: #fff3cd; color: #856404; border: 2px solid #ffc107; }
|
||||||
|
.status-poor { background-color: #f8d7da; color: #721c24; border: 2px solid #dc3545; }
|
||||||
|
.metrics { display: grid; grid-template-columns: repeat(2, 1fr); gap: 15px; margin: 25px 0; }
|
||||||
|
.metric { background: #ecf0f1; padding: 20px; border-radius: 5px; border-left: 4px solid #3498db; }
|
||||||
|
.metric-label { font-size: 13px; color: #7f8c8d; text-transform: uppercase; letter-spacing: 0.5px; }
|
||||||
|
.metric-value { font-size: 28px; font-weight: bold; color: #2c3e50; margin-top: 8px; }
|
||||||
|
.section { margin: 25px 0; padding: 20px; background: #f8f9fa; border-radius: 5px; }
|
||||||
|
.section h2 { color: #34495e; margin-top: 0; font-size: 20px; }
|
||||||
|
.recommendations { background: #fff3cd; border-left: 4px solid #ffc107; padding: 15px; margin: 20px 0; }
|
||||||
|
.recommendations ul { margin: 10px 0; padding-left: 20px; }
|
||||||
|
.footer { margin-top: 30px; padding-top: 20px; border-top: 2px solid #ecf0f1; font-size: 12px; color: #7f8c8d; text-align: center; }
|
||||||
|
table { width: 100%; border-collapse: collapse; margin: 15px 0; }
|
||||||
|
th, td { padding: 12px; text-align: left; border-bottom: 1px solid #ddd; }
|
||||||
|
th { background-color: #3498db; color: white; font-weight: 600; }
|
||||||
|
tr:hover { background-color: #f5f5f5; }
|
||||||
|
</style>
|
||||||
|
</head>
|
||||||
|
<body>
|
||||||
|
<div class="container">
|
||||||
|
<h1>[BATTERY] UPS Battery Test Report</h1>
|
||||||
|
|
||||||
|
<p><strong>Hostname:</strong> {{ hostname }}<br>
|
||||||
|
<strong>Date:</strong> {{ test_date }}<br>
|
||||||
|
<strong>UPS:</strong> {{ ups_name }}</p>
|
||||||
|
|
||||||
|
<div class="status-badge status-{{ health_class }}">
|
||||||
|
{{ health_emoji }} Battery Health: {{ health_status }}
|
||||||
|
</div>
|
||||||
|
|
||||||
|
<p style="font-size: 16px; margin-top: 15px;">{{ health_description }}</p>
|
||||||
|
|
||||||
|
<h2 style="margin-top: 30px;">Test Metrics</h2>
|
||||||
|
<div class="metrics">
|
||||||
|
<div class="metric">
|
||||||
|
<div class="metric-label">Charge Drop</div>
|
||||||
|
<div class="metric-value">{{ charge_drop }}%</div>
|
||||||
|
</div>
|
||||||
|
<div class="metric">
|
||||||
|
<div class="metric-label">Voltage Drop</div>
|
||||||
|
<div class="metric-value">{{ voltage_drop }}V</div>
|
||||||
|
</div>
|
||||||
|
<div class="metric">
|
||||||
|
<div class="metric-label">Min Charge</div>
|
||||||
|
<div class="metric-value">{{ min_charge }}%</div>
|
||||||
|
</div>
|
||||||
|
<div class="metric">
|
||||||
|
<div class="metric-label">Recovery Time</div>
|
||||||
|
<div class="metric-value">{{ recovery_time }}s</div>
|
||||||
|
</div>
|
||||||
|
</div>
|
||||||
|
|
||||||
|
<div class="section">
|
||||||
|
<h2>Detailed Measurements</h2>
|
||||||
|
<table>
|
||||||
|
<tr>
|
||||||
|
<th>Parameter</th>
|
||||||
|
<th>Before Test</th>
|
||||||
|
<th>After Test</th>
|
||||||
|
</tr>
|
||||||
|
<tr>
|
||||||
|
<td>Battery Charge</td>
|
||||||
|
<td>{{ before_charge }}%</td>
|
||||||
|
<td>{{ after_charge }}%</td>
|
||||||
|
</tr>
|
||||||
|
<tr>
|
||||||
|
<td>Battery Voltage</td>
|
||||||
|
<td>{{ before_voltage }}V</td>
|
||||||
|
<td>{{ after_voltage }}V</td>
|
||||||
|
</tr>
|
||||||
|
<tr>
|
||||||
|
<td>UPS Load</td>
|
||||||
|
<td>{{ before_load }}%</td>
|
||||||
|
<td>{{ after_load }}%</td>
|
||||||
|
</tr>
|
||||||
|
</table>
|
||||||
|
</div>
|
||||||
|
|
||||||
|
<div class="recommendations">
|
||||||
|
<h2 style="margin-top: 0;">📋 Recommendations</h2>
|
||||||
|
{{{ recommendations }}}
|
||||||
|
</div>
|
||||||
|
|
||||||
|
<div class="footer">
|
||||||
|
<p><strong>Script:</strong> /opt/scripts/ups-monthly-test.sh<br>
|
||||||
|
<strong>Log File:</strong> /var/log/ups-monthly-test.log</p>
|
||||||
|
<p style="margin-top: 10px;">Proxmox VE - UPS Monitoring System</p>
|
||||||
|
</div>
|
||||||
|
</div>
|
||||||
|
</body>
|
||||||
|
</html>
|
||||||
|
EOFTEMPLATE
|
||||||
|
|
||||||
|
log "Templates created in $TEMPLATE_DIR/"
|
||||||
|
}
|
||||||
|
|
||||||
|
# Verifică și creează template-urile dacă nu există
|
||||||
|
if [ ! -f "$TEMPLATE_DIR/ups-battery-test-subject.txt.hbs" ]; then
|
||||||
|
log "Creating notification templates..."
|
||||||
|
create_templates
|
||||||
|
fi
|
||||||
|
|
||||||
|
log "========================================"
|
||||||
|
log "UPS MONTHLY BATTERY TEST - START"
|
||||||
|
log "========================================"
|
||||||
|
|
||||||
|
# 1. Verificare status UPS înainte de test
|
||||||
|
log "Step 1: Verificare status UPS înainte de test..."
|
||||||
|
BEFORE_STATUS=$(upsc $UPS_NAME ups.status 2>/dev/null)
|
||||||
|
BEFORE_CHARGE=$(upsc $UPS_NAME battery.charge 2>/dev/null)
|
||||||
|
BEFORE_VOLTAGE=$(upsc $UPS_NAME battery.voltage 2>/dev/null)
|
||||||
|
BEFORE_LOAD=$(upsc $UPS_NAME ups.load 2>/dev/null)
|
||||||
|
|
||||||
|
log " Status: $BEFORE_STATUS"
|
||||||
|
log " Battery Charge: $BEFORE_CHARGE%"
|
||||||
|
log " Battery Voltage: $BEFORE_VOLTAGE V"
|
||||||
|
log " Load: $BEFORE_LOAD%"
|
||||||
|
|
||||||
|
# Verifică dacă UPS este online
|
||||||
|
if [[ $BEFORE_STATUS != *"OL"* ]]; then
|
||||||
|
log "ERROR: UPS nu este online! Status: $BEFORE_STATUS"
|
||||||
|
log "Test ANULAT"
|
||||||
|
exit 1
|
||||||
|
fi
|
||||||
|
|
||||||
|
# Verifică încărcare baterie
|
||||||
|
if [ "$BEFORE_CHARGE" -lt 95 ]; then
|
||||||
|
log "WARNING: Baterie nu este complet încărcată ($BEFORE_CHARGE%)"
|
||||||
|
fi
|
||||||
|
|
||||||
|
# 2. Pornire test baterie
|
||||||
|
log ""
|
||||||
|
log "Step 2: Pornire test baterie..."
|
||||||
|
TEST_START_TIME=$(date +%s)
|
||||||
|
|
||||||
|
upscmd -u $UPS_USER -p $UPS_PASS $UPS_NAME test.battery.start.quick 2>&1 | tee -a $LOGFILE
|
||||||
|
|
||||||
|
if [ ${PIPESTATUS[0]} -eq 0 ]; then
|
||||||
|
log "Test baterie pornit cu succes!"
|
||||||
|
else
|
||||||
|
log "ERROR: Nu am putut porni testul de baterie!"
|
||||||
|
exit 1
|
||||||
|
fi
|
||||||
|
|
||||||
|
# 3. TIMING CRITIC: Așteptare 10-15 secunde pentru ca charge să scadă
|
||||||
|
log ""
|
||||||
|
log "Step 3: Monitorizare test baterie (timing critic pentru charge drop)..."
|
||||||
|
|
||||||
|
MIN_CHARGE=$BEFORE_CHARGE
|
||||||
|
MIN_VOLTAGE=$BEFORE_VOLTAGE
|
||||||
|
CHARGE_AT_15S=$BEFORE_CHARGE
|
||||||
|
VOLTAGE_AT_15S=$BEFORE_VOLTAGE
|
||||||
|
|
||||||
|
# Primele 5 secunde - inițializare test
|
||||||
|
sleep 5
|
||||||
|
|
||||||
|
# 10-40 secunde - fereastra critică când charge scade
|
||||||
|
for i in {1..7}; do
|
||||||
|
CURRENT_CHARGE=$(upsc $UPS_NAME battery.charge 2>/dev/null)
|
||||||
|
CURRENT_VOLTAGE=$(upsc $UPS_NAME battery.voltage 2>/dev/null)
|
||||||
|
|
||||||
|
# Capturează minimul
|
||||||
|
if [ ! -z "$CURRENT_CHARGE" ] && [ "$CURRENT_CHARGE" -lt "$MIN_CHARGE" ]; then
|
||||||
|
MIN_CHARGE=$CURRENT_CHARGE
|
||||||
|
fi
|
||||||
|
|
||||||
|
if [ ! -z "$CURRENT_VOLTAGE" ]; then
|
||||||
|
MIN_VOLTAGE=$(echo "$CURRENT_VOLTAGE $MIN_VOLTAGE" | awk '{if ($1 < $2) print $1; else print $2}')
|
||||||
|
fi
|
||||||
|
|
||||||
|
# Citire la 15 secunde (punct optim)
|
||||||
|
if [ $i -eq 2 ]; then
|
||||||
|
CHARGE_AT_15S=$CURRENT_CHARGE
|
||||||
|
VOLTAGE_AT_15S=$CURRENT_VOLTAGE
|
||||||
|
log " [15s CRITICAL] Charge: $CURRENT_CHARGE% | Voltage: $CURRENT_VOLTAGE V"
|
||||||
|
else
|
||||||
|
log " [$((5 + i*5))s] Charge: $CURRENT_CHARGE% | Voltage: $CURRENT_VOLTAGE V"
|
||||||
|
fi
|
||||||
|
|
||||||
|
sleep 5
|
||||||
|
done
|
||||||
|
|
||||||
|
TEST_END_TIME=$(date +%s)
|
||||||
|
TEST_DURATION=$((TEST_END_TIME - TEST_START_TIME))
|
||||||
|
|
||||||
|
log " Minimum Charge: $MIN_CHARGE%"
|
||||||
|
log " Minimum Voltage: $MIN_VOLTAGE V"
|
||||||
|
|
||||||
|
# 4. Așteptare recuperare și citire finală
|
||||||
|
log ""
|
||||||
|
log "Step 4: Așteptare recuperare baterie (15 secunde)..."
|
||||||
|
sleep 15
|
||||||
|
|
||||||
|
AFTER_STATUS=$(upsc $UPS_NAME ups.status 2>/dev/null)
|
||||||
|
AFTER_CHARGE=$(upsc $UPS_NAME battery.charge 2>/dev/null)
|
||||||
|
AFTER_VOLTAGE=$(upsc $UPS_NAME battery.voltage 2>/dev/null)
|
||||||
|
AFTER_LOAD=$(upsc $UPS_NAME ups.load 2>/dev/null)
|
||||||
|
|
||||||
|
log " Status: $AFTER_STATUS"
|
||||||
|
log " Battery Charge: $AFTER_CHARGE%"
|
||||||
|
log " Battery Voltage: $AFTER_VOLTAGE V"
|
||||||
|
log " Load: $AFTER_LOAD%"
|
||||||
|
|
||||||
|
# 5. Calcul metrici
|
||||||
|
CHARGE_DROP=$((BEFORE_CHARGE - MIN_CHARGE))
|
||||||
|
VOLTAGE_DROP=$(echo "$BEFORE_VOLTAGE - $MIN_VOLTAGE" | bc 2>/dev/null || echo "0")
|
||||||
|
|
||||||
|
# Rotunjire voltage drop la 2 zecimale
|
||||||
|
VOLTAGE_DROP=$(printf "%.2f" $VOLTAGE_DROP 2>/dev/null || echo $VOLTAGE_DROP)
|
||||||
|
|
||||||
|
log ""
|
||||||
|
log "Step 5: Analiza rezultate test..."
|
||||||
|
log " Durată test: $TEST_DURATION secunde"
|
||||||
|
log " Scădere încărcare: $CHARGE_DROP% (de la $BEFORE_CHARGE% la $MIN_CHARGE%)"
|
||||||
|
log " Scădere tensiune: $VOLTAGE_DROP V (de la $BEFORE_VOLTAGE V la $MIN_VOLTAGE V)"
|
||||||
|
|
||||||
|
# 6. Evaluare sănătate baterie
|
||||||
|
BATTERY_HEALTH="UNKNOWN"
|
||||||
|
HEALTH_CLASS="fair"
|
||||||
|
HEALTH_EMOJI="[INFO]"
|
||||||
|
HEALTH_DESCRIPTION=""
|
||||||
|
RECOMMENDATIONS=""
|
||||||
|
|
||||||
|
if [ "$CHARGE_DROP" -lt 15 ]; then
|
||||||
|
BATTERY_HEALTH="EXCELLENT"
|
||||||
|
HEALTH_CLASS="excellent"
|
||||||
|
HEALTH_EMOJI="[OK]"
|
||||||
|
HEALTH_DESCRIPTION="Battery is in excellent condition with minimal discharge during test."
|
||||||
|
RECOMMENDATIONS="<ul><li>✅ Battery is healthy and functioning normally</li><li>Continue monthly testing</li><li>No action required</li></ul>"
|
||||||
|
log " Sănătate baterie: EXCELENTĂ (scădere < 15%)"
|
||||||
|
elif [ "$CHARGE_DROP" -lt 35 ]; then
|
||||||
|
BATTERY_HEALTH="GOOD"
|
||||||
|
HEALTH_CLASS="good"
|
||||||
|
HEALTH_EMOJI="[OK]"
|
||||||
|
HEALTH_DESCRIPTION="Battery shows normal wear but performs adequately."
|
||||||
|
RECOMMENDATIONS="<ul><li>Battery is functioning well</li><li>Monitor monthly for degradation trends</li><li>No immediate action needed</li></ul>"
|
||||||
|
log " Sănătate baterie: BUNĂ (scădere 15-35%)"
|
||||||
|
elif [ "$CHARGE_DROP" -lt 55 ]; then
|
||||||
|
BATTERY_HEALTH="FAIR"
|
||||||
|
HEALTH_CLASS="fair"
|
||||||
|
HEALTH_EMOJI="[WARNING]"
|
||||||
|
HEALTH_DESCRIPTION="Battery shows significant wear and should be monitored closely."
|
||||||
|
RECOMMENDATIONS="<ul><li>⚠️ Battery is aging</li><li>Plan replacement in 3-6 months</li><li>Increase monitoring frequency</li><li>Order replacement battery soon</li></ul>"
|
||||||
|
log " Sănătate baterie: ACCEPTABILĂ (scădere 35-55%)"
|
||||||
|
else
|
||||||
|
BATTERY_HEALTH="POOR"
|
||||||
|
HEALTH_CLASS="poor"
|
||||||
|
HEALTH_EMOJI="[CRITICAL]"
|
||||||
|
HEALTH_DESCRIPTION="Battery is critically weak and requires immediate replacement!"
|
||||||
|
RECOMMENDATIONS="<ul><li>🔴 <strong>URGENT:</strong> Battery needs immediate replacement!</li><li>Order new battery NOW</li><li>UPS may not provide adequate protection</li><li>Risk of unexpected shutdown</li></ul>"
|
||||||
|
log " Sănătate baterie: SLABĂ (scădere > 55%) - NECESITĂ ÎNLOCUIRE!"
|
||||||
|
fi
|
||||||
|
|
||||||
|
# 7. Monitorizare recuperare (30 secunde)
|
||||||
|
log ""
|
||||||
|
log "Step 6: Monitorizare recuperare baterie..."
|
||||||
|
|
||||||
|
RECOVERY_START=$(date +%s)
|
||||||
|
sleep 30
|
||||||
|
RECOVERY_CHARGE=$(upsc $UPS_NAME battery.charge 2>/dev/null)
|
||||||
|
RECOVERY_TIME=$(($(date +%s) - RECOVERY_START))
|
||||||
|
|
||||||
|
log " Charge după $RECOVERY_TIME secunde: $RECOVERY_CHARGE%"
|
||||||
|
|
||||||
|
# 8. Calculează timpul total
|
||||||
|
END_TIME=$(date +%s)
|
||||||
|
RUNTIME=$((END_TIME - START_TIME))
|
||||||
|
|
||||||
|
# 9. Determină severity pentru notificare
|
||||||
|
if [ "$BATTERY_HEALTH" = "EXCELLENT" ] || [ "$BATTERY_HEALTH" = "GOOD" ]; then
|
||||||
|
SEVERITY="info"
|
||||||
|
elif [ "$BATTERY_HEALTH" = "FAIR" ]; then
|
||||||
|
SEVERITY="warning"
|
||||||
|
else
|
||||||
|
SEVERITY="error"
|
||||||
|
fi
|
||||||
|
|
||||||
|
# 10. Trimite notificarea prin PVE::Notify
|
||||||
|
log ""
|
||||||
|
log "Step 7: Trimitere notificare prin PVE::Notify..."
|
||||||
|
|
||||||
|
# Escape pentru Perl heredoc
|
||||||
|
RECOMMENDATIONS_ESCAPED=$(echo "$RECOMMENDATIONS" | sed "s/'/\\'/g")
|
||||||
|
|
||||||
|
perl -I/usr/share/perl5 << EOFPERL
|
||||||
|
use strict;
|
||||||
|
use warnings;
|
||||||
|
use PVE::Notify;
|
||||||
|
|
||||||
|
my \$template_data = {
|
||||||
|
'hostname' => '$FQDN',
|
||||||
|
'test_date' => '$(date '+%Y-%m-%d %H:%M:%S')',
|
||||||
|
'ups_name' => '$UPS_NAME',
|
||||||
|
'health_status' => '$BATTERY_HEALTH',
|
||||||
|
'health_class' => '$HEALTH_CLASS',
|
||||||
|
'health_emoji' => '$HEALTH_EMOJI',
|
||||||
|
'health_description' => '$HEALTH_DESCRIPTION',
|
||||||
|
'charge_drop' => '$CHARGE_DROP',
|
||||||
|
'voltage_drop' => '$VOLTAGE_DROP',
|
||||||
|
'min_charge' => '$MIN_CHARGE',
|
||||||
|
'min_voltage' => '$MIN_VOLTAGE',
|
||||||
|
'before_charge' => '$BEFORE_CHARGE',
|
||||||
|
'before_voltage' => '$BEFORE_VOLTAGE',
|
||||||
|
'before_load' => '$BEFORE_LOAD',
|
||||||
|
'after_charge' => '$AFTER_CHARGE',
|
||||||
|
'after_voltage' => '$AFTER_VOLTAGE',
|
||||||
|
'after_load' => '$AFTER_LOAD',
|
||||||
|
'test_duration' => '$TEST_DURATION',
|
||||||
|
'recovery_time' => '$RECOVERY_TIME',
|
||||||
|
'recommendations' => '$RECOMMENDATIONS_ESCAPED'
|
||||||
|
};
|
||||||
|
|
||||||
|
my \$fields = {
|
||||||
|
'hostname' => '$HOSTNAME',
|
||||||
|
'type' => 'ups-battery-test',
|
||||||
|
'health' => '$BATTERY_HEALTH'
|
||||||
|
};
|
||||||
|
|
||||||
|
eval {
|
||||||
|
PVE::Notify::notify('$SEVERITY', 'ups-battery-test', \$template_data, \$fields);
|
||||||
|
print "Notification sent successfully\\n";
|
||||||
|
};
|
||||||
|
if (\$@) {
|
||||||
|
print STDERR "Failed to send notification: \$@\\n";
|
||||||
|
exit 1;
|
||||||
|
}
|
||||||
|
EOFPERL
|
||||||
|
|
||||||
|
PERL_EXIT_CODE=$?
|
||||||
|
|
||||||
|
if [ $PERL_EXIT_CODE -eq 0 ]; then
|
||||||
|
log "Notificare trimisă cu succes prin PVE::Notify"
|
||||||
|
else
|
||||||
|
log "ERROR: Notificarea a eșuat (exit code: $PERL_EXIT_CODE)"
|
||||||
|
fi
|
||||||
|
|
||||||
|
# 11. Finalizare
|
||||||
|
log ""
|
||||||
|
log "========================================"
|
||||||
|
log "UPS MONTHLY BATTERY TEST - COMPLETE"
|
||||||
|
log "Sănătate baterie: $BATTERY_HEALTH"
|
||||||
|
log "Scădere încărcare: $CHARGE_DROP%"
|
||||||
|
log "Scădere tensiune: $VOLTAGE_DROP V"
|
||||||
|
log "Timp total: $RUNTIME secunde"
|
||||||
|
log "========================================"
|
||||||
|
|
||||||
|
exit 0
|
||||||
83
proxmox/ups/scripts/ups-shutdown-cluster.sh
Normal file
83
proxmox/ups/scripts/ups-shutdown-cluster.sh
Normal file
@@ -0,0 +1,83 @@
|
|||||||
|
#!/bin/bash
|
||||||
|
#
|
||||||
|
# Script de shutdown orchestrat pentru cluster Proxmox când UPS este pe baterie critică
|
||||||
|
# Autor: Generat automat
|
||||||
|
# Data: 2025-10-06
|
||||||
|
|
||||||
|
LOGFILE=/var/log/ups-shutdown.log
|
||||||
|
NODES=(10.0.20.200 10.0.20.202) # pve1, pve2 (pvemini va fi ultimul)
|
||||||
|
|
||||||
|
log_message() {
|
||||||
|
echo "[2025-10-06 20:02:34] $1" | tee -a $LOGFILE
|
||||||
|
}
|
||||||
|
|
||||||
|
log_message "========================================"
|
||||||
|
log_message "UPS SHUTDOWN ORCHESTRATION STARTED"
|
||||||
|
log_message "UPS Status: $(upsc nutdev1 ups.status 2>/dev/null || echo 'UNKNOWN')"
|
||||||
|
log_message "Battery Charge: $(upsc nutdev1 battery.charge 2>/dev/null || echo 'UNKNOWN')%"
|
||||||
|
log_message "========================================"
|
||||||
|
|
||||||
|
# Verifică dacă UPS este într-adevăr pe baterie critică
|
||||||
|
UPS_STATUS=$(upsc nutdev1 ups.status 2>/dev/null)
|
||||||
|
if [[ ! $UPS_STATUS =~ (OB|LB) ]]; then
|
||||||
|
log_message "WARNING: UPS status is $UPS_STATUS - not critical. Aborting shutdown."
|
||||||
|
exit 0
|
||||||
|
fi
|
||||||
|
|
||||||
|
log_message "Step 1: Oprire VM-uri și containere pe toate nodurile..."
|
||||||
|
|
||||||
|
# Oprește VM-uri pe toate nodurile (inclusiv local)
|
||||||
|
for node in ${NODES[@]} localhost; do
|
||||||
|
if [ "$node" == "localhost" ]; then
|
||||||
|
NODE_NAME="pvemini (local)"
|
||||||
|
else
|
||||||
|
NODE_NAME=$node
|
||||||
|
fi
|
||||||
|
|
||||||
|
log_message " - Oprire VM-uri pe $NODE_NAME..."
|
||||||
|
|
||||||
|
if [ "$node" == "localhost" ]; then
|
||||||
|
# Local - oprește VM-urile direct
|
||||||
|
for vmid in $(qm list | awk 'NR>1 {print $1}'); do
|
||||||
|
vm_status=$(qm status $vmid | awk '{print $2}')
|
||||||
|
if [ "$vm_status" == "running" ]; then
|
||||||
|
log_message " * Oprire VM $vmid pe pvemini..."
|
||||||
|
qm shutdown $vmid --timeout 60 &
|
||||||
|
fi
|
||||||
|
done
|
||||||
|
else
|
||||||
|
# Remote - SSH către alt nod
|
||||||
|
ssh -o ConnectTimeout=5 root@$node "
|
||||||
|
for vmid in \$(qm list | awk 'NR>1 {print \$1}'); do
|
||||||
|
vm_status=\$(qm status \$vmid | awk '{print \$2}')
|
||||||
|
if [ \"\$vm_status\" == \"running\" ]; then
|
||||||
|
echo ' * Oprire VM '\$vmid' pe $node...'
|
||||||
|
qm shutdown \$vmid --timeout 60 &
|
||||||
|
fi
|
||||||
|
done
|
||||||
|
" 2>&1 | tee -a $LOGFILE
|
||||||
|
fi
|
||||||
|
done
|
||||||
|
|
||||||
|
log_message "Step 2: Așteptare 90 secunde pentru oprirea VM-urilor..."
|
||||||
|
sleep 90
|
||||||
|
|
||||||
|
log_message "Step 3: Oprire noduri secundare (pve1, pve2)..."
|
||||||
|
for node in ${NODES[@]}; do
|
||||||
|
log_message " - Shutdown nod $node..."
|
||||||
|
ssh -o ConnectTimeout=5 root@$node "shutdown -h +1 'UPS on battery critical - shutting down'" 2>&1 | tee -a $LOGFILE &
|
||||||
|
done
|
||||||
|
|
||||||
|
log_message "Step 4: Așteptare 30 secunde pentru shutdown noduri secundare..."
|
||||||
|
sleep 30
|
||||||
|
|
||||||
|
log_message "Step 5: Oprire nod local (pvemini - primary)..."
|
||||||
|
log_message "========================================"
|
||||||
|
log_message "UPS SHUTDOWN ORCHESTRATION COMPLETED"
|
||||||
|
log_message "Local node will shutdown in 1 minute"
|
||||||
|
log_message "========================================"
|
||||||
|
|
||||||
|
# Oprește nodul local (ultimul)
|
||||||
|
shutdown -h +1 "UPS on battery critical - primary node shutting down"
|
||||||
|
|
||||||
|
exit 0
|
||||||
63
proxmox/ups/scripts/ups-shutdown-test.sh
Normal file
63
proxmox/ups/scripts/ups-shutdown-test.sh
Normal file
@@ -0,0 +1,63 @@
|
|||||||
|
#!/bin/bash
|
||||||
|
#
|
||||||
|
# Script de TEST pentru shutdown orchestrat - NU oprește nimic
|
||||||
|
#
|
||||||
|
|
||||||
|
LOGFILE=/var/log/ups-shutdown-test.log
|
||||||
|
NODES=(10.0.20.200 10.0.20.202)
|
||||||
|
|
||||||
|
log_message() {
|
||||||
|
echo "[2025-10-06 20:03:03] $1" | tee -a $LOGFILE
|
||||||
|
}
|
||||||
|
|
||||||
|
log_message "========================================"
|
||||||
|
log_message "UPS SHUTDOWN TEST STARTED (DRY RUN)"
|
||||||
|
log_message "UPS Status: $(upsc nutdev1 ups.status 2>/dev/null || echo 'UNKNOWN')"
|
||||||
|
log_message "Battery Charge: $(upsc nutdev1 battery.charge 2>/dev/null || echo 'UNKNOWN')%"
|
||||||
|
log_message "Input Voltage: $(upsc nutdev1 input.voltage 2>/dev/null || echo 'UNKNOWN')V"
|
||||||
|
log_message "Output Voltage: $(upsc nutdev1 output.voltage 2>/dev/null || echo 'UNKNOWN')V"
|
||||||
|
log_message "========================================"
|
||||||
|
|
||||||
|
log_message "TEST: Ar opri VM-urile de pe toate nodurile..."
|
||||||
|
|
||||||
|
for node in ${NODES[@]} localhost; do
|
||||||
|
if [ "$node" == "localhost" ]; then
|
||||||
|
NODE_NAME="pvemini (local)"
|
||||||
|
else
|
||||||
|
NODE_NAME=$node
|
||||||
|
fi
|
||||||
|
|
||||||
|
log_message " - VM-uri pe $NODE_NAME:"
|
||||||
|
|
||||||
|
if [ "$node" == "localhost" ]; then
|
||||||
|
for vmid in $(qm list | awk 'NR>1 {print $1}'); do
|
||||||
|
vm_name=$(qm config $vmid | grep '^name:' | cut -d' ' -f2)
|
||||||
|
vm_status=$(qm status $vmid | awk '{print $2}')
|
||||||
|
log_message " * VM $vmid ($vm_name): $vm_status"
|
||||||
|
done
|
||||||
|
else
|
||||||
|
ssh -o ConnectTimeout=5 root@$node "
|
||||||
|
for vmid in \$(qm list | awk 'NR>1 {print \$1}'); do
|
||||||
|
vm_name=\$(qm config \$vmid | grep '^name:' | cut -d' ' -f2)
|
||||||
|
vm_status=\$(qm status \$vmid | awk '{print \$2}')
|
||||||
|
echo ' * VM '\$vmid' ('\$vm_name'): '\$vm_status
|
||||||
|
done
|
||||||
|
" 2>&1 | tee -a $LOGFILE
|
||||||
|
fi
|
||||||
|
done
|
||||||
|
|
||||||
|
log_message ""
|
||||||
|
log_message "TEST: Ordinea de shutdown ar fi:"
|
||||||
|
log_message " 1. Toate VM-urile de pe toate nodurile (paralel)"
|
||||||
|
log_message " 2. Așteptare 90 secunde"
|
||||||
|
log_message " 3. Shutdown pve1 (10.0.20.200)"
|
||||||
|
log_message " 4. Shutdown pve2 (10.0.20.202)"
|
||||||
|
log_message " 5. Așteptare 30 secunde"
|
||||||
|
log_message " 6. Shutdown pvemini (10.0.20.201) - PRIMARY/LAST"
|
||||||
|
log_message ""
|
||||||
|
log_message "========================================"
|
||||||
|
log_message "UPS SHUTDOWN TEST COMPLETED (DRY RUN)"
|
||||||
|
log_message "NICIUN sistem nu a fost oprit - doar test"
|
||||||
|
log_message "========================================"
|
||||||
|
|
||||||
|
exit 0
|
||||||
32
proxmox/ups/scripts/upssched-cmd
Normal file
32
proxmox/ups/scripts/upssched-cmd
Normal file
@@ -0,0 +1,32 @@
|
|||||||
|
#!/bin/bash
|
||||||
|
#
|
||||||
|
# Script apelat de upssched pentru a gestiona evenimentele UPS
|
||||||
|
#
|
||||||
|
|
||||||
|
LOGFILE=/var/log/ups-events.log
|
||||||
|
|
||||||
|
log_event() {
|
||||||
|
echo "[2025-10-06 20:03:38] $1" >> $LOGFILE
|
||||||
|
}
|
||||||
|
|
||||||
|
case $1 in
|
||||||
|
onbatt)
|
||||||
|
log_event "UPS EVENT: Pe baterie de 3 minute - Începe shutdown orchestrat"
|
||||||
|
logger -t upssched-cmd "UPS on battery for 3 minutes - starting orchestrated shutdown"
|
||||||
|
/usr/local/bin/ups-shutdown-cluster.sh &
|
||||||
|
;;
|
||||||
|
lowbatt)
|
||||||
|
log_event "UPS EVENT: BATERIE SCĂZUTĂ - Shutdown IMEDIAT"
|
||||||
|
logger -t upssched-cmd "UPS LOW BATTERY - immediate shutdown"
|
||||||
|
/usr/local/bin/ups-shutdown-cluster.sh &
|
||||||
|
;;
|
||||||
|
commbad)
|
||||||
|
log_event "UPS EVENT: Comunicație pierdută cu UPS de 30 secunde"
|
||||||
|
logger -t upssched-cmd "Lost communication with UPS for 30 seconds"
|
||||||
|
# Nu facem shutdown automat pentru pierdere comunicație
|
||||||
|
;;
|
||||||
|
*)
|
||||||
|
log_event "UPS EVENT: Eveniment necunoscut - $1"
|
||||||
|
logger -t upssched-cmd "Unknown UPS event: $1"
|
||||||
|
;;
|
||||||
|
esac
|
||||||