Add complete UPS monitoring system with monthly battery testing
This commit adds a comprehensive UPS monitoring and management system for the Proxmox cluster with automated shutdown orchestration and monthly battery health testing. Features: - NUT (Network UPS Tools) configuration for INNO TECH USB UPS - Automated cluster shutdown on power failure (3-minute grace period) - Monthly automated battery testing with health evaluation - Email notifications via PVE::Notify system - WinNUT monitoring client for Windows VM 201 Components added: - config/: NUT configuration files (ups.conf, upsd.conf, upsmon.conf, etc.) - scripts/ups-shutdown-cluster.sh: Orchestrated cluster shutdown - scripts/ups-monthly-test.sh: Monthly battery test with email reports - scripts/upssched-cmd: Event handler for UPS state changes - docs/: Complete installation and usage documentation Key findings: - UPS battery.charge reporting has 10-40 second delay after test start - Test must monitor voltage drop (1.5-2V) and charge drop (9-27%) - Battery health evaluation: EXCELLENT/GOOD/FAIR/POOR based on discharge rate - Email notifications use Handlebars templates without Unicode emojis for compatibility Configuration: - UPS: INNO TECH (Voltronic protocol, vendor 0665:5161) - Primary node: pvemini (10.0.20.201) with USB connection - Monthly test: cron 0 0 1 * * /opt/scripts/ups-monthly-test.sh - Shutdown timer: 180 seconds on battery before cluster shutdown Documentation includes complete installation guides for NUT server, WinNUT client, and troubleshooting procedures. 🤖 Generated with [Claude Code](https://claude.com/claude-code) Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
415
proxmox/ups/README.md
Normal file
415
proxmox/ups/README.md
Normal file
@@ -0,0 +1,415 @@
|
||||
# Documentație UPS - Cluster Proxmox
|
||||
|
||||
## Despre
|
||||
|
||||
Această documentație descrie configurarea completă a sistemului UPS (Uninterruptible Power Supply) pentru cluster-ul Proxmox, incluzând monitorizare automată și shutdown orchestrat.
|
||||
|
||||
## Structură Directoare
|
||||
|
||||
```
|
||||
proxmox/ups/
|
||||
├── README.md # Acest fișier
|
||||
├── config/ # Fișiere de configurare NUT
|
||||
│ ├── ups.conf # Configurare driver UPS
|
||||
│ ├── upsd.conf # Configurare server NUT
|
||||
│ ├── upsd.users # Utilizatori și permisiuni
|
||||
│ ├── upsmon.conf # Configurare monitor local
|
||||
│ └── upssched.conf # Scheduler evenimente UPS
|
||||
├── scripts/ # Scripturi de shutdown și testare
|
||||
│ ├── ups-shutdown-cluster.sh # Script principal shutdown orchestrat
|
||||
│ ├── ups-shutdown-test.sh # Script test (dry-run)
|
||||
│ ├── upssched-cmd # Handler evenimente upssched
|
||||
│ └── ups-monthly-test.sh # Test lunar automat baterie (NOU!)
|
||||
└── docs/ # Documentație
|
||||
├── INSTALARE-NUT.md # Ghid instalare NUT pe Proxmox
|
||||
├── INSTALARE-WINNUT.md # Ghid instalare WinNUT pe Windows
|
||||
├── UPS-SHUTDOWN-README.md # Documentație completă sistem
|
||||
└── UPS-MONTHLY-TEST.md # Documentație test lunar baterie (NOU!)
|
||||
```
|
||||
|
||||
🎯 Utilizare:
|
||||
Pentru instalare nouă:
|
||||
Citește README.md
|
||||
Urmează docs/INSTALARE-NUT.md
|
||||
Copiază fișiere din config/ și scripts/ pe server
|
||||
Pentru backup:
|
||||
Tot ce trebuie este salvat în proxmox/ups/
|
||||
Versionat în Git
|
||||
Pentru recovery:
|
||||
Restaurează fișiere din config/ în /etc/nut/
|
||||
Restaurează fișiere din scripts/ în /usr/local/bin/
|
||||
Restart servicii
|
||||
|
||||
## Arhitectură Sistem
|
||||
|
||||
### Hardware
|
||||
- **UPS:** INNO TECH USB to Serial (Vendor ID: 0665, Product ID: 5161)
|
||||
- **Conectat la:** pvemini (10.0.20.201) via USB
|
||||
- **Tip:** Voltronic/Megatec protocol (driver: nutdrv_qx)
|
||||
|
||||
### Cluster Proxmox
|
||||
- **pvemini (10.0.20.201)** - Nod PRIMARY
|
||||
- Are UPS-ul conectat fizic
|
||||
- Rulează NUT server și driver
|
||||
- Ultimul nod care se oprește
|
||||
- **pve1 (10.0.20.200)** - Nod SECONDARY
|
||||
- Se oprește primul în caz de baterie critică
|
||||
- **pve2 (10.0.20.202)** - Nod SECONDARY
|
||||
- Se oprește primul în caz de baterie critică
|
||||
|
||||
### Monitorizare
|
||||
- **VM 201 (Windows 11)** - Monitorizare vizuală via WinNUT
|
||||
- Afișează status UPS în timp real
|
||||
- NU controlează shutdown-ul
|
||||
|
||||
## Flux Automat Shutdown
|
||||
|
||||
### Scenario 1: Întrerupere scurtă (< 3 minute)
|
||||
1. Curent se întrerupe → UPS trece pe baterie (status: OB)
|
||||
2. upssched pornește timer de 180 secunde
|
||||
3. Curent revine înainte de 3 minute
|
||||
4. Timer anulat → **Niciun sistem nu se oprește**
|
||||
|
||||
### Scenario 2: Întrerupere lungă (> 3 minute)
|
||||
1. Curent se întrerupe → UPS pe baterie
|
||||
2. Timer 180 secunde expiră
|
||||
3. `/usr/local/bin/ups-shutdown-cluster.sh` pornește:
|
||||
- **Step 1:** Oprește toate VM-urile de pe toate nodurile (paralel)
|
||||
- **Step 2:** Așteaptă 90 secunde pentru oprire graceful
|
||||
- **Step 3:** Shutdown pve1 și pve2 (noduri secundare)
|
||||
- **Step 4:** Așteaptă 30 secunde
|
||||
- **Step 5:** Shutdown pvemini (nod primary - ultimul)
|
||||
|
||||
### Scenario 3: Baterie scăzută imediată
|
||||
1. UPS raportează LOWBATT (baterie critică)
|
||||
2. Shutdown **IMEDIAT** (fără timer)
|
||||
3. Același flux de shutdown orchestrat ca mai sus
|
||||
|
||||
## Quick Start
|
||||
|
||||
### Pentru Administrator Nou
|
||||
|
||||
1. **Citește documentația:**
|
||||
- Start: [`docs/UPS-SHUTDOWN-README.md`](docs/UPS-SHUTDOWN-README.md)
|
||||
- Detalii NUT: [`docs/INSTALARE-NUT.md`](docs/INSTALARE-NUT.md)
|
||||
- WinNUT: [`docs/INSTALARE-WINNUT.md`](docs/INSTALARE-WINNUT.md)
|
||||
|
||||
2. **Verifică status UPS:**
|
||||
```bash
|
||||
ssh root@10.0.20.201
|
||||
upsc nutdev1
|
||||
```
|
||||
|
||||
3. **Test dry-run:**
|
||||
```bash
|
||||
ssh root@10.0.20.201
|
||||
/usr/local/bin/ups-shutdown-test.sh
|
||||
cat /var/log/ups-shutdown-test.log
|
||||
```
|
||||
|
||||
4. **Monitorizează în WinNUT:**
|
||||
- Pornește WinNUT pe VM 201
|
||||
- Verifică că se conectează la 10.0.20.201:3493
|
||||
|
||||
### Verificare Săptămânală
|
||||
|
||||
```bash
|
||||
# Conectează-te la pvemini
|
||||
ssh root@10.0.20.201
|
||||
|
||||
# Status UPS
|
||||
upsc nutdev1 ups.status battery.charge input.voltage
|
||||
|
||||
# Status servicii
|
||||
systemctl status nut-server nut-monitor
|
||||
|
||||
# Logs evenimente recente
|
||||
tail -20 /var/log/ups-events.log
|
||||
|
||||
# Test dry-run
|
||||
/usr/local/bin/ups-shutdown-test.sh
|
||||
```
|
||||
|
||||
### Verificare Lunară
|
||||
|
||||
**🔋 Test Automat Baterie (1 ale lunii la 00:00):**
|
||||
|
||||
Scriptul `/opt/scripts/ups-monthly-test.sh` rulează automat lunar și:
|
||||
- Testează capacitatea reală a bateriei
|
||||
- Monitorizează scăderea charge și voltage
|
||||
- Evaluează sănătatea bateriei (EXCELLENT/GOOD/FAIR/POOR)
|
||||
- Trimite raport HTML prin email via PVE::Notify
|
||||
|
||||
**Verificare rezultat test:**
|
||||
```bash
|
||||
ssh root@10.0.20.201
|
||||
# Vezi ultimul test
|
||||
tail -50 /var/log/ups-monthly-test.log
|
||||
|
||||
# Rulare manuală (pentru testare)
|
||||
/opt/scripts/ups-monthly-test.sh
|
||||
```
|
||||
|
||||
**Documentație completă:** [`docs/UPS-MONTHLY-TEST.md`](docs/UPS-MONTHLY-TEST.md)
|
||||
|
||||
---
|
||||
|
||||
**Test fizic manual (opțional):**
|
||||
- Deconectează UPS de la priză timp de 30 secunde
|
||||
- Verifică că WinNUT detectează schimbarea (On Battery)
|
||||
- Verifică logs: `tail -f /var/log/ups-events.log`
|
||||
- Reconectează **înainte de 3 minute** pentru a evita shutdown
|
||||
|
||||
**Verificare SSH între noduri:**
|
||||
```bash
|
||||
ssh root@10.0.20.201
|
||||
ssh root@10.0.20.200 "hostname"
|
||||
ssh root@10.0.20.202 "hostname"
|
||||
```
|
||||
|
||||
## Instalare de la Zero
|
||||
|
||||
### 1. Instalare NUT pe pvemini
|
||||
|
||||
```bash
|
||||
# Instalare pachete
|
||||
apt update
|
||||
apt install -y nut nut-client nut-server
|
||||
|
||||
# Copiere fișiere de configurare
|
||||
cd /path/to/ROMFASTSQL/proxmox/ups
|
||||
scp config/* root@10.0.20.201:/etc/nut/
|
||||
|
||||
# Copiere scripturi shutdown
|
||||
scp scripts/ups-shutdown-cluster.sh scripts/ups-shutdown-test.sh scripts/upssched-cmd root@10.0.20.201:/usr/local/bin/
|
||||
ssh root@10.0.20.201 "chmod +x /usr/local/bin/ups-*.sh /usr/local/bin/upssched-cmd"
|
||||
|
||||
# Copiere script test lunar
|
||||
scp scripts/ups-monthly-test.sh root@10.0.20.201:/opt/scripts/
|
||||
ssh root@10.0.20.201 "chmod +x /opt/scripts/ups-monthly-test.sh"
|
||||
|
||||
# Configurare cron pentru test lunar
|
||||
ssh root@10.0.20.201 "(crontab -l 2>/dev/null | grep -v ups-monthly-test; echo '# UPS Monthly Battery Test'; echo '0 0 1 * * /opt/scripts/ups-monthly-test.sh') | crontab -"
|
||||
|
||||
# Configurare permisiuni
|
||||
ssh root@10.0.20.201 "chown nut:nut /etc/nut/ups*.conf /etc/nut/upsd.*"
|
||||
ssh root@10.0.20.201 "chmod 640 /etc/nut/upsd.users"
|
||||
|
||||
# Pornire servicii
|
||||
ssh root@10.0.20.201 "systemctl enable nut-server nut-monitor"
|
||||
ssh root@10.0.20.201 "systemctl start nut-server nut-monitor"
|
||||
|
||||
# Verificare
|
||||
ssh root@10.0.20.201 "upsc nutdev1"
|
||||
```
|
||||
|
||||
### 2. Instalare WinNUT pe VM 201
|
||||
|
||||
Vezi ghid detaliat: [`docs/INSTALARE-WINNUT.md`](docs/INSTALARE-WINNUT.md)
|
||||
|
||||
```
|
||||
Server: 10.0.20.201
|
||||
Port: 3493
|
||||
UPS: nutdev1
|
||||
User: admin
|
||||
Pass: parola99
|
||||
Polling: 15
|
||||
```
|
||||
|
||||
## Troubleshooting Rapid
|
||||
|
||||
### UPS nu răspunde
|
||||
|
||||
```bash
|
||||
ssh root@10.0.20.201
|
||||
|
||||
# Verifică UPS conectat
|
||||
lsusb | grep 0665
|
||||
|
||||
# Restart driver
|
||||
upsdrvctl stop && upsdrvctl start
|
||||
|
||||
# Verifică status
|
||||
upsc nutdev1
|
||||
```
|
||||
|
||||
### WinNUT nu se conectează
|
||||
|
||||
1. **Verifică Polling Interval ≠ 0** (pune 15)
|
||||
2. **Test port:**
|
||||
```powershell
|
||||
Test-NetConnection -ComputerName 10.0.20.201 -Port 3493
|
||||
```
|
||||
3. **Verifică server:**
|
||||
```bash
|
||||
ssh root@10.0.20.201 "ss -tulpn | grep 3493"
|
||||
```
|
||||
|
||||
### Scriptul de shutdown nu funcționează
|
||||
|
||||
```bash
|
||||
# Test SSH între noduri
|
||||
ssh root@10.0.20.201 "ssh root@10.0.20.200 hostname"
|
||||
|
||||
# Dacă eșuează, reconfigurează SSH keys
|
||||
ssh root@10.0.20.201
|
||||
ssh-keygen -f /root/.ssh/known_hosts -R 10.0.20.200
|
||||
ssh-keyscan -H 10.0.20.200 >> /root/.ssh/known_hosts
|
||||
```
|
||||
|
||||
## Logs Important
|
||||
|
||||
| Fișier | Scop |
|
||||
|--------|------|
|
||||
| `/var/log/ups-shutdown.log` | Shutdown orchestrat real |
|
||||
| `/var/log/ups-shutdown-test.log` | Test dry-run |
|
||||
| `/var/log/ups-events.log` | Evenimente UPS (upssched) |
|
||||
| `/var/log/ups-monthly-test.log` | **Test lunar baterie (NOU!)** |
|
||||
| `journalctl -u nut-server` | Server NUT |
|
||||
| `journalctl -u nut-monitor` | Monitor NUT |
|
||||
|
||||
## Comenzi Utile
|
||||
|
||||
```bash
|
||||
# Status UPS complet
|
||||
upsc nutdev1
|
||||
|
||||
# Doar câmpuri importante
|
||||
upsc nutdev1 ups.status battery.charge input.voltage output.voltage
|
||||
|
||||
# Comenzi disponibile
|
||||
upscmd -l nutdev1
|
||||
|
||||
# Conexiuni active NUT
|
||||
ss -tnp | grep 3493
|
||||
|
||||
# Monitoring live
|
||||
watch -n 2 'upsc nutdev1 ups.status battery.charge input.voltage'
|
||||
|
||||
# Test shutdown (DRY RUN - nu oprește nimic)
|
||||
/usr/local/bin/ups-shutdown-test.sh
|
||||
|
||||
# Test lunar baterie (cu raport email)
|
||||
/opt/scripts/ups-monthly-test.sh
|
||||
|
||||
# Verifică ultimul test lunar
|
||||
tail -50 /var/log/ups-monthly-test.log
|
||||
```
|
||||
|
||||
## Configurare Personalizată
|
||||
|
||||
### Modificare timp de așteptare (default: 3 minute)
|
||||
|
||||
Editează `/etc/nut/upssched.conf` pe pvemini:
|
||||
|
||||
```bash
|
||||
# Schimbă din 180 (3 min) la 300 (5 min)
|
||||
AT ONBATT * START-TIMER onbatt 300
|
||||
```
|
||||
|
||||
Apoi:
|
||||
```bash
|
||||
systemctl restart nut-monitor
|
||||
```
|
||||
|
||||
### Adăugare noduri noi în cluster
|
||||
|
||||
Editează `/usr/local/bin/ups-shutdown-cluster.sh`:
|
||||
|
||||
```bash
|
||||
# Adaugă IP-ul noului nod
|
||||
NODES=("10.0.20.200" "10.0.20.202" "10.0.20.XXX")
|
||||
```
|
||||
|
||||
## Backup și Restore
|
||||
|
||||
### Backup configurație
|
||||
|
||||
```bash
|
||||
# De pe stația locală
|
||||
cd /path/to/ROMFASTSQL/proxmox/ups
|
||||
|
||||
# Backup configurație
|
||||
ssh root@10.0.20.201 "tar czf /tmp/nut-backup.tar.gz /etc/nut/*.conf /usr/local/bin/ups*.sh /usr/local/bin/upssched-cmd"
|
||||
scp root@10.0.20.201:/tmp/nut-backup.tar.gz ./nut-backup-$(date +%Y%m%d).tar.gz
|
||||
```
|
||||
|
||||
### Restore configurație
|
||||
|
||||
```bash
|
||||
# Extrage backup
|
||||
tar xzf nut-backup-YYYYMMDD.tar.gz
|
||||
|
||||
# Copiază pe server
|
||||
scp -r etc/nut/* root@10.0.20.201:/etc/nut/
|
||||
scp usr/local/bin/* root@10.0.20.201:/usr/local/bin/
|
||||
|
||||
# Restart servicii
|
||||
ssh root@10.0.20.201 "systemctl restart nut-server nut-monitor"
|
||||
```
|
||||
|
||||
## Securitate
|
||||
|
||||
### Parole
|
||||
|
||||
**IMPORTANT:** Schimbă parolele default!
|
||||
|
||||
```bash
|
||||
ssh root@10.0.20.201
|
||||
nano /etc/nut/upsd.users
|
||||
|
||||
# Schimbă "parola99" cu ceva sigur
|
||||
# Apoi restart:
|
||||
systemctl restart nut-server
|
||||
```
|
||||
|
||||
### Firewall
|
||||
|
||||
NUT portul 3493 trebuie accesibil din rețea locală. Dacă ai firewall:
|
||||
|
||||
```bash
|
||||
# Permite port 3493 din subnet local
|
||||
iptables -A INPUT -p tcp --dport 3493 -s 10.0.20.0/24 -j ACCEPT
|
||||
```
|
||||
|
||||
## Suport și Documentație
|
||||
|
||||
- **NUT Official:** https://networkupstools.org/
|
||||
- **NUT Documentation:** https://networkupstools.org/docs/user-manual.chunked/
|
||||
- **Hardware Compatibility:** https://networkupstools.org/stable-hcl.html
|
||||
- **WinNUT GitHub:** https://github.com/gawindx/WinNUT-V2
|
||||
|
||||
## Funcționalități Complete
|
||||
|
||||
### ✅ Shutdown Orchestrat Automat
|
||||
- Detectare întrerupere curent (3 minute grace period)
|
||||
- Oprire ordonată: VM-uri → noduri secundare → nod primary
|
||||
- Notificări în timp real prin upssched
|
||||
|
||||
### ✅ Test Lunar Automat Baterie (NOU!)
|
||||
- Rulare automată pe 1 ale lunii la 00:00
|
||||
- Test real capacitate baterie (comutare pe baterie ~10 secunde)
|
||||
- Evaluare sănătate: EXCELLENT/GOOD/FAIR/POOR
|
||||
- Rapoarte HTML + email prin PVE::Notify
|
||||
- Recomandări automate pentru înlocuire baterie
|
||||
- Log detaliat istoric teste
|
||||
|
||||
### ✅ Monitorizare Continuă
|
||||
- WinNUT pe VM 201 (Windows 11) pentru vizualizare real-time
|
||||
- NUT server pe pvemini expune date la toate nodurile
|
||||
- Logging complet evenimente și teste
|
||||
|
||||
## Autori și Istoric
|
||||
|
||||
- **Creat:** 2025-10-06
|
||||
- **Versiune:** 1.1
|
||||
- **Ultima modificare:** 2025-10-06
|
||||
- **Autor:** Configurat automat via Claude Code
|
||||
- **Changelog:**
|
||||
- v1.1 (2025-10-06): Adăugat test lunar automat baterie cu notificări PVE::Notify
|
||||
- v1.0 (2025-10-06): Release inițial cu shutdown orchestrat și monitorizare NUT
|
||||
|
||||